FC410LPS-R/W
(certified EN54-23)
FC410LPBS
(certified EN54-23)
FC430LPBSB
(certified EN54-23)
In the programming menu choose the channel,
sounder or beacon you wish to program.
Before the alarm conditions, the user interface will
display:
SOUNDER = BEACON
YES NO
If you choose YES, the alarm conditions are selected
and applied to both channels. If you choose NO,
the channel selection is displayed and the alarm
conditions are valid for the selected channel.
3 Key - SW zone
The SW zone option in the PROGRAMMING menu
activates the screen used to select and program the
software zone. See Figure 26, 0.
In this phase, the keypad and keys have the
following functions:
Alphanumeric keypad
Use the alphanumeric keypad to select the zone
number (ID).
Cursor keys
Table 37: Cursor key functions in SW zone
Key
Function
Up
No function
Down
No function
Right
Use to select the next available
SW zone
Left
Use to select the previous
available SW zone
ESC and ENTER keys
Table 38: ESC and ENTER key function in SW zone
Key
Function
ESC
Use to delete the procedure and
return to the previous screen
ENTER
Use to accept the SW zone
selection and activate the loop
device programming screen
If the SW zone does not exist, the following warning
screen displays for 5 seconds: "WRONG VALUE!
Enter the parameter again". After 5 seconds the
user interface returns to the chosen SW zone
screens.
Zone name
Enter the zone label (20 characters maximum) using
the alphanumeric entry procedures.
SW zone in WALK TEST
After selecting the SW zone, enable or disable the
option Zone in WALK TEST (OFF).
•
If the option All Devices (ALL) is selected, all
the devices assigned to the zone in the WALK
TEST mode do not generate an alarm if they
are activated but do reach the TEST status.
•
If the option detector (DET) is selected, only
the detectors assigned to the zone in the
WALK TEST mode will not generate an alarm
in the case of their activation but will reach
the TEST status.
•
If the call points (CP) option is selected, only
the call-points assigned to zone in WALK TEST
mode will not generate alarm in the case of
their activation but will reach the TEST status.
The presence of a zone in WALK TEST mode is
signaled by the TEST yellow LED on the User
Interface. More than one zone can be put in
WALK TEST mode at the same time.
In this phase the keypad and keys have the
following functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
Table 39: Cursor key functions in SW zone in
WALK TEST
Key
Function
Up
No function
Down
No function
Right
Use to select the next ON-OFF-
ALL-det-CP
Left
Use to select the previous ON-
OFF-ALL-det-CP
FC503 and FC506 Addressable Fire Control Panels
52