3.1 - POPULAR BOILERHOUSE - TECHNICAL DETAILS
Firebird Enviromax Popular Boilerhouse C Range
Dimensions (mm)
Model Output
Weight
kg
Di
m
e
n
sio
n
s(
mm
)
Kw/h
r
(i
n
cl. Bu
rn
e
r
) H
W
D
B
C
E
F
G
Popula
r
C20
110
684 441 381 202 220 163 99 122 502
Popula
r
C26
112
684 441 381 202 220 163 99 122 502
Popula
r
C35
115
684 441 381 202 220 163 99 122 502
Popula
r
C44
182
820 470 533 202 154 154 97 123 620
Popula
r
C58
190
820 470 533 253 154 154 97 123 620
Popula
r
C73
210
877 530 527 253 265 155 97 123 670
BURNER
DEPTH
F
r
o
n
t View
Side View
Top View
C
E
D
W
G
H
F
B
B
Boiler Model
C20/26
C35
C44/58
C73
Max Heat Output
Kw
20/26
35
44 / 58
73
Btu/h (‘000)
68/89
119
150 / 198
249
CONNECTIONS
Heating Flow
1” Bsp.
1” Bsp.
1
1
/
2
” Bsp
1
1
/
2
” Bsp.
Heating Return
1” Bsp.
1” Bsp.
1
1
/
2
” Bsp.
1
1
/
2
” Bsp.
Drain Off Cock
1
/
2
”
Bsp
.
1
/
2
”
Bsp
.
1
/
2
”
Bsp
.
1
/
2
”
Bsp
.
Condense Drain Off Connection.
22 mm PLASTIC
22 mm PLASTIC
22 mm PLASTIC
22 mm PLASTIC
WATER CONTENT
Water Content Boiler
24
24
43.5
54
FLUE (Indoor Boilers) Concentric Flue
Balanced Flue Assembly
(mm)
125 (5”)
125 (5”)
155 (6”)
170 (7”)
Conventional flue Socket.
(mm)
130 id.
130 id.
155 id.
170 id.
Flue Draught Reqd.
(Min WG.)
0.040”
0.040”
0.040”
0.040”
Conventional Flue
(Max WG.)
0.15”
0.15”
0.15”
0.15”
MAINS WATER SUPPLY
Limescale excess: When over 150/200 ppm. Fit appropriate scale reducer.
Pressure Max
10 bar max (Fit pressure reducing valve as necessary)
Min
1 bar min. For user Comfort reduce pressure at tap to between 1 and 5 Bar.
TEMPERATURE CONTROL
Boiler Central Heating Control 60˚C - 80˚C +- 3˚C
Boiler Safety Limit 110˚C +- 3˚C
HEATING SYSTEM (SEALED) Fit in accordance with BS 7074 Part 1, BS 5449, OFTEC Standards, etc
Boiler Test Pressure 4.5 Bar
Safety Valve Operating Pressure Gauge 0 to 4 Bar
WATER SIDE RESISTANCE
Flow Rate To Give A Nominal Output At 10k Differential
Flow Rate To Give A Nominal Output At 20k Differential
Flow Rate Measured
(Kg h
-1
)
2874.24
Flow Rate Measured
(Kg h
-1
)
1522.92
Waterside Resistance
(mbar)
0.18
Waterside Resistance
(mbar)
0.19
Pressure Jet Oil Burners
RIELLO RDB 2.2 up to C35 & RIELLO RDB 4.2 up to C58 - C73
Fuel C2
Kerosene
Electrical Supply
230v. AC 50Hz To be fused at 5amp.
Copper Pipe Not Plastic to be used for a minimum of 1 metre off the boiler