Optional Modules
46
Document #15668 Rev.I 04/20/98 P/N 15668:I
2.15 Optional Modules
The MS-9200 supports option modules using connectors J6, J11 and J16 on the main circuit board. There are four
optional modules available for the MS-9200:
• RTM-8F Relay/transmitter Module
• PIM-24 Printer/PC Interface Module
• UDACT-F Universal Digital Alarm Communicator/Transmitter
• DIM-485 Display Interface Module (for use with LCD-40 Series annunciators)
Jumper JP4 must be cut before installation of the RTM-8F module to enable module placement supervision. Note
that devices connected to the standard EIA-485 connector, the optional EIA-232 connector, the optional EIA-485
connector via the PIM-24 or DIM-485 modules or SLC loop may be protected from voltage transients by using one of
the UL listed compatible surge suppressors listed in the Fire•Lite Device Compatibility Document.
2.15.1 UDACT-F Universal Digital Alarm Communicator/Transmitter
The UDACT-F transmits system status to UL listed Central Station receivers via
the public switched telephone network. It is capable of reporting up to 56 soft-
ware zones or up to 198 addressable points. The UDACT-F may be mounted
directly to the MS-9200 main circuit board or remotely in a UBS-1F or ABS-8RF
enclosure. The MS-9200 requires software P/N 73580 or higher to support the
UDACT-F. For additional information, refer to the UDACT-F Manual.
FIGURE 2-28:
Option Module Locations
J11 accepts PIM-24 or DIM-485
J16 accepts UDACT-F
Cut JP4 for RTM-8F supervision
J6 accepts RTM-8F
FIGURE 2-29:
UBS-1F