Document #15668 Rev. I 04/20/98 P/N 15668:I
71
Alarm Operation
item for one minute or until the Acknowledge/Step key is pressed again. As the Acknowledge/Step key is pressed,
the MS-9200 displays events in the following priority order:
1.
Alarms in address order
2.
Supervisories in address order
3.
Troubles in address order
4.5
Alarm Operation
Alarm operation is similar to trouble operation, but with the following differences:
• The piezo sounder produces a steady output, not pulsed
• The System Alarm (not Trouble) LED flashes
• ALARM: device name, type and address are displayed
• Alarms latch and are not allowed to clear automatically
• Alarms activate software zones (control-by-event logic) if so programmed
• Timers (Silence Inhibit, Autosilence, Trouble Reminder) are started
• Alarms activate the general alarm relay and zone Z00 (NAC 1 and NAC 2)
• The trouble relay is not activated
A typical alarm display would be:
4.6
Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
• The piezo sounder is a warbling sound
• The Supervisory LED (not Alarm) flashes
• The Display Status label is Active
• Supervisory relay is activated
• Silenced alarms are not resounded
• Timers are not started
• The alarm relay is not activated
A typical Supervisory event would display:
$/$5038//67$7,210
$'-!1281!=11
$&7,9(7$03(50
$'-!1281!=11