background image

                  Document #15668    Rev.  I     04/20/98     P/N 15668:I

69

Trouble Operation

4.4

Trouble Operation

With no alarms, the detection of a trouble in the system will cause the piezo to sound, the System Trouble LED to 
flash and the trouble relay to activate.  A message will appear on the LCD display indicating the trouble condition.  
The same message is sent to the printer and history file along with time and date.  A ground fault will also cause the 
yellow Ground Fault LED, located on the bottom of the main circuit board, to turn on.

Addressable Smoke Detectors

For addressable Ionization or Photoelectric smoke detectors, the following is a typical message that could appear on 
the LCD display for a detector in trouble.

The information displayed in the first line in the example above provides the following information:

• The type of event - in this example, TRBL indicates Device Trouble

• The Specific Device Trouble for a Detector - the # symbol will be replace by a digit representing a specific 

trouble condition (refer to the list of Specific Device Troubles listed below)

• Type of device - in this example, SMOKE DET indicates smoke detector

• Point type and address - in this example, P01 indicates Photoelectric detector assigned to address 01

The information displayed in the second line in the example above provides the following information:

• <ADJ> - user programmed adjective descriptor from library list or custom entry (five characters maximum)

• <NOUN> - user programmed noun descriptor from library list or custom entry (ten characters maximum)

• Zone - zone to which the point is assigned

The # symbol in the display will be replaced by a digit that represents the Specific Device Troubles as listed below:

TABLE 4-1:

Specific Device Troubles for a Detector

#

Specific Device Troubles

1

An Invalid Reply may be due to:
(1) incorrect pulse width received from a detector
(2) no answer from a detector due to either a complete device failure or removal from the SLC loop
(3) an incorrect identification code received, i.e. a photo detector replaced by an ion detector or vice-versa

2

Maintenance Alert - indicates that a detector has been within 80% of its alarm threshold for 24 hours, 
indicating that the detector needs cleaning

3

Fail Automatic Test - indicates that a detector's sensing chamber and electronics (which are tested for nor-
mal safe operation every two hours) has failed the test

75%/602.('(73

$'-!1281!=

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание MS-9200

Страница 1: ...llation Maintenance and Operating Instruction Manual 12 Clintonville Road Northford CT 06472 Phone 203 484 7161 FAX 203 484 7118 P N 15668 I ECN 97 332 I Document 15668 04 20 98 Rev 1998 Fire Lite Technical Manuals Online http www tech man com firealarmresources com ...

Страница 2: ...y made up of smoke detectors heat detectors manual pull stations audi ble warning devices and a fire alarm control with remote noti fication capability can provide early warning of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire Any fire alarm system may fail for a variety of reasons Smoke detectors may not sense fire...

Страница 3: ...Power 25 2 2 1 AC Power and Earth Ground Connections 25 2 2 2 Battery Power 25 2 2 3 DC Power Output Connections 25 FIGURE 2 5 DC Power Outputs 25 2 3 Standard Relays 26 FIGURE 2 6 Relay Connections 26 2 4 Notification Appliance Circuits 26 FIGURE 2 7 NAC Connections 26 2 5 UL Power limited Wiring Requirements 27 FIGURE 2 8 Typical UL Power limited Wiring Requirements 27 2 6 Wiring the Signaling L...

Страница 4: ...48 2 15 2 ACM 8RF Relay Control Module 49 FIGURE 2 33 ABS 8RF Enclosure 49 FIGURE 2 34 ACM 8RF Relay Control Module Installation 49 2 15 3 RTM 8F Option Module Installation 50 FIGURE 2 35 RTM 8F Module Installation 50 FIGURE 2 36 RTM 8F Relay Transmitter Module 51 2 16 Printer PC Interface Module 52 FIGURE 2 37 Remote Serial Printer and Computer Connections 52 TABLE 2 2 Typical Printer Settings 52...

Страница 5: ...ABLE A 2 Filtered Load in Standby External Devices Connected to TB4 Only 78 TABLE A 3 Filtered Load in Alarm External Devices Connected to TB2 TB4 Only 79 TABLE A 4 Battery Calculations 80 Appendix B Software Zones 81 FIGURE B 1 Zoning Example 82 TABLE B 1 Detector Programming Sheet Example 83 TABLE B 2 Module Programming Sheet Example 84 FIGURE B 2 Blank Zoning Sheet 85 TABLE B 3 Blank Detector P...

Страница 6: ...Document 15668 Rev I 04 20 98 P N 15668 I 3 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 7: ...4 Document 15668 Rev I 04 20 98 P N 15668 I Technical Manuals Online http www tech man com firealarmresources com ...

Страница 8: ...Document 15668 Rev I 04 20 98 P N 15668 I 5 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 9: ...tective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1076 Proprietary Burglar Alarm Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN ULC S524 M91 Sta...

Страница 10: ...Document 15668 Rev I 04 20 98 P N 15668 I 7 MS 9200 C Main Circuit Board Technical Manuals Online http www tech man com firealarmresources com ...

Страница 11: ...with local energy reverse polarity transmitter Optional ACM 8RF Relay Control Module Optional Printer PC Interface Module 3 6 amps system power expandable to 6 6 amps 3 0 amps NAC power expandable to 6 0 amps 40 character LCD display backlit Real time clock calendar History file with 500 event capacity Advanced fire technology features Automatic device type code verification Auto detector test Mai...

Страница 12: ...nsulation Battery Lead Acid Only J3 Maximum Charging Circuit Normal Flat Charge 27 6V 0 8 amp Maximum Battery Capacity 17 Amp Hour new MS 9200 cabinet available September 1 1998 holds maximum 12 Amp Hour batteries Batteries greater than 12 Amp Hour up to 18 Amp Hour require Fire Lite BB 17F or other UL listed battery cabinet For 25 to 120 Amp Hour batteries use the CHG 120F Battery Charger only if...

Страница 13: ... 2 Operating voltage range 18V to 30V Total DC current available for powering external devices is 2 5 amps2 This power is not recommended for AFM LDM or LCD 40 annunciators Power limited circuit 1 3 Controls and Indicators LCD Display The MS 9200 uses a 40 character 2 lines X 20 characters high viewing angle LCD display with a character height of 3 16 The display includes a long life LED backlight...

Страница 14: ... conditions 1 4 Circuits SLC Communication Loop One SLC loop configurable for NFPA Style 4 6 or 7 is provided for communication to addressable monitor initiat ing device and control output device modules Output Circuits The following output circuits are available on the FACP 24 Volt Resettable Power Output 300 mA 24 Volt Nonresettable Power Output 300 mA 24 Volt Battery Charger up to 17 AH batteri...

Страница 15: ...kbox or DP 1 R for newer backbox which mounts to the inside of the cabinet required and included on the ULC version The dress panel must be installed to meet FM requirements refer to Dress Panel on page 16 Transformer Assembly One 100VA transformer is provided standard with the panel 3 6 amps maximum An optional 100 VA transformer XRM 24 is available to provide maximum accessory power 6 6 amp tota...

Страница 16: ...onal initiating devices and notification appliances All modules respond to an address that is set by the installer via two built in rotary decimal switches A flashing LED indicates power is applied to the mod ules except for M301 A thermoplastic cover is provided with all modules except the M301 for mounting to a 4 square mounting box M300 The M300 is an addressable monitor module that can be used...

Страница 17: ... decimal switches on the pull station The manual pull station includes a Fire Lite key I300 The loop isolator module is an automatic switch which opens the circuit voltage to the SLC Loop branch es whenever a wire to wire short circuit is detected on that loop The remainder of the communications loop leading up to the I300 will continue to operate unaffected by the short The isolator module is bi ...

Страница 18: ...amming information Refer to Figure 2 37 Remote Serial Printer and Computer Connections on page 52 for information on connec tions and System Edit on page 61 for information on programming the MS 9200 for use with a printer or PC Note that the PIM 24 option cannot be used simultaneously with the DIM 485 LCD 40 option PK 9200 W Kit for Local Downloading The PK 9200 W Programming Utility can be used ...

Страница 19: ...FM approval It is important to note that FM approval is contingent on the proper installation of the dress panel 1 7 2 Battery Box BB 17F The BB 17F battery box may be used to house two 12 AH required with older backbox or 18 AH required with older or newer backbox batteries The battery box mounts directly below the MS 9200 cabinet The box is red and is provided with knockouts BB 55F The BB 55F ba...

Страница 20: ... power or batteries until the system is completely wired and ready for testing Set the CHG 120F Voltage Select switch SW1 to match the AC power source voltage 120VAC or 240 VAC With the breaker at the main power distribution panel turned off connect AC power wires to CHG 120F TB1 as shown below Wire the CHG 120F to the MS 9200 as shown Cut Jumper JP1 on the newer versions of the MS 9200 main circu...

Страница 21: ...16ATF The Annunciator Fixed Module 16ATF contains 16 red alarm and 16 yellow trouble LEDs a System Trouble LED an On Line Power LED and a local piezo sounder with switches for MS 9200 Acknowledge Silence Reset and Drill The AFM 16ATF is fixed at address 1 and communication is via the EIA 485 data line AFM 32AX The Annunciator Fixed Module 32AX contains 32 red alarm LEDs a System Trouble LED an On ...

Страница 22: ...connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions Refer to the LDM Series Lamp Drive Modules Manual for a complete description See AFM and LDM Series Wiring on page 89 for wiring requirements and System Edit on page 61 for details on programming the MS 9200 for annunciator use The LDM 32F The Lamp Drive Module LDM 32F has 32 alarm lamp...

Страница 23: ...s 3 and 4 During the inactive state the remote power supply supervises its NAC field wiring for short and open circuits If a fault is detected the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED Output Circuits 1 4 However once the NACs are activated the supervision is disabled and the circuits are no longer super vised Supervision of other power supply fault...

Страница 24: ...es to be installed Sufficient knockouts are provided for wiring convenience Select the appropriate knockout s and pull the required conductors into the box All wiring should be in accordance with the National and or Local codes for fire alarm systems Note Effective September 1 1998 the cabinet illustrated in Figure 2 1 and Figure 2 2 will be discontinued The dimensions for the new cabinet which wi...

Страница 25: ...mounting bolts using the dimensions shown 3 Install two upper fasteners in the wall with the screw heads protruding 4 Using the upper keyholes mount the backbox over the two screws 5 Mark and drill the lower two holes 6 Secure backbox by installing the remaining fasteners Tighten all screws 7 When the location is dry and free of construction dust reinstall the main PC board TR 1 R Trim Ring 16 GA ...

Страница 26: ...binet illustrated in this Figure will begin shipping on September 1 1998 FIGURE 2 3 MS 9200 Cabinet Dimensions new version To remove entire knockout strike here To remove inner knockout strike here BB 17F Technical Manuals Online http www tech man com firealarmresources com ...

Страница 27: ...I 04 20 98 P N 15668 I The new cabinet illustrated in this figure will begin shipping on September 1 1998 FIGURE 2 4 MS 9200 Cabinet Mounting new version TR 4 R Trim Ring Technical Manuals Online http www tech man com firealarmresources com ...

Страница 28: ...erve polarity when connecting the battery Connect the battery cable to J3 on the MS 9200 main circuit board using the plug in connector provided See Power Supply Calculations on page 77 for calculation of the correct battery rating WARNING Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fab rics If contact is made with sulfuric acid immediately flus...

Страница 29: ... two NACs Notifi cation Appliance Circuits located on the main circuit board may be expanded via the Fire Lite FCPS 24F Field Charger Power Supply Surge protection for notification appliances may be provided by using one of the UL listed compatible surge suppressors listed in the Fire Lite Device Compatibility Document FIGURE 2 6 Relay Connections 1 2 3 4 5 6 7 8 TB3 SUPV ALARM TROUBLE NO C NO NC ...

Страница 30: ... Power limited Circuit Nonpower limited Circuit Nonpower limited Circuit No connection Power limited Circuit Power limited Circuit Power limited Circuit Nonpower limited Circuit Nonpower limited Circuit Nonpower limited Circuit RTM 8F UL Power limited Wiring Requirements Nonpower limited and power limited wiring must have a minimum distance of 0 25 wire to wire If this module is used to drive nonp...

Страница 31: ...ules Through addressable Control Modules the control panel can selectively activate Notification Appliance Circuits or Form C output relays see Figure 2 23 and Figure 2 24 Addressable Detectors Through the communications loop the MS 9200 communicates with addressable ionization photoelectric and photo electric thermal detectors see Figure 2 27 Device Capacity The capacity of each MS 9200 includes ...

Страница 32: ...at a time and measure the DC resistance from the beginning of the loop to the end of that particular branch The total resistance from panel to each branch end cannot exceed 40 ohms Repeat this procedure for all remaining branches For Each Loop Add the lengths of all the branches on one loop This sum cannot exceed 10 000 feet 3 000 m using 12 AWG 3 25 mm2 twisted shielded wire Branch In this exampl...

Страница 33: ...y be T tapped 1 2 3 4 5 6 T B 6 A B B A B A Shield FIGURE 2 11 Two Wire Communications Loop Connect to TB6 3 Connect to TB6 5 BG 10LX SD300 C304 M300 I300 I300 Note I300 devices are not required to meet NFPA Style 4 CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision Separate T tap to other loop devices NO NC COM Technical Manuals Online http www tech man com fire...

Страница 34: ...not be T tapped 1 2 3 4 5 6 T B 6 A B B A B A Shield FIGURE 2 12 Four Wire Communications Loop Connect Loop Out to TB6 3 and TB6 5 Connect Loop Return to TB6 4 and TB6 6 BG 10LX SD300 C304 M300 I300 I300 Note I300 devices are not required to meet NFPA Style 6 CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision NO NC COM Technical Manuals Online http www tech man c...

Страница 35: ...nger be able to communicate with Zone 02 a trouble signal s will be generated for that device No T tapping or branching is allowed on this circuit The ratings and characteristics are the same as for a 4 wire circuit meeting NFPA Style 6 requirements FIGURE 2 13 4 Wire Communications Loop 1 2 3 4 5 6 T B 6 A B B A B A Shield Connect Loop Out to TB6 3 and TB6 5 Connect Loop Return to TB6 4 and TB6 6...

Страница 36: ... to the outside of the cabinet via a BX type connector FIGURE 2 15 Shield Termination in Full Conduit MS 9200 Cabinet Shield Drain Wire The shield must not be connected to earth ground at any point SLC Loop SLC Loop Shield All Styles of Wiring The shield drain wire must be connected to the shield terminal TB6 Terminal 1 or 2 Do not allow the shield drain wire or the shield foil to touch the system...

Страница 37: ...on the loop branch In Figure 2 17 a short on any T tapped branch off an I300 Isolator Module on the communication loop meeting NFPA Style 4 wiring requirements will be isolated from all devices installed both upstream of the I300 Communica tion Loop In and on the continuation of the loop shown as a dotted line As an example if a short were to occur on Branch A of the first I300 shown the Isolator ...

Страница 38: ...in Figure 2 20 Style D Circuit using M300 on page 38 Note that this circuit cannot be T tapped or branched in any fashion Connect the 4 wire circuit to M300 Terminals 6 and 9 then 7 and 8 Test Switch The M300 includes a magnetic test switch located near the center front of the module Activation of this switch will cause an open circuit indication in the Style B D loop 2 10 The M301 Monitor Module ...

Страница 39: ...A Style D Initiating Device Circuit Connect 2 wire smoke detectors to M302 Terminals 6 B and 9 D 7 B and 8 D as illustrated in Figure 2 22 Style D Circuit using M302 on page 40 IDC installation wiring must not exceed 25 ohms 12 18 AWG 0 75 3 25 mm2 wire Power Connections Power must be switched 24 VDC isolated filtered and battery backed Connect to M302 Terminals 3 and 4 as illustrated in Figure 2 ...

Страница 40: ... 4 5 6 T B 4 MS 9200 SLC TB6 3 SLC TB6 5 24V TB4 5 24V TB4 6 M300 To Next Device on Loop CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision Resettable 24 VDC 4 wire smoke detector power 300 mA max Heat Detector Manual Pull Station UL listed Power Supervision Relay must be wired as last device on loop as shown 24 VDC 4 Wire Smoke Detector End of Line Resistor 47K ...

Страница 41: ...6 T B 4 MS 9200 SLC TB6 3 SLC TB6 5 24V TB4 5 24V TB4 6 M300 To Next Device on Loop CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision Resettable 24 VDC 4 wire smoke detector power 300 mA max Heat Detector UL listed Power Supervision Relay must be wired as last device on loop as shown 24 VDC 4 Wire Smoke Detector Manual Pull Station Loop Out See note Note An ELR ...

Страница 42: ... B A Shield 1 2 3 4 5 6 T B 4 MS 9200 SLC TB6 3 SLC TB6 5 24V TB4 5 24V TB4 6 M302 To Next Device on Loop CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision Resettable 24 VDC 4 wire smoke detector power 300 mA max UL listed Compatible Smoke Detector End of Line Resistor 3 9K ohm included UL listed Compatible Smoke Detector UL listed Compatible Smoke Detector Loop...

Страница 43: ... A B A Shield 1 2 3 4 5 6 T B 4 MS 9200 SLC TB6 3 SLC TB6 5 24V TB4 5 24V TB4 6 M302 To Next Device on Loop CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision Resettable 24 VDC 4 wire smoke detector power 300 mA max UL listed Compatible Smoke Detector Loop Out UL listed Compatible Smoke Detector UL listed Compatible Smoke Detector End of Line Resistor 3 9K ohm in...

Страница 44: ...nstall an ELR since one is built into the C304 Control Module Notification Appliance Power Connect notification appliance power from MS 9200 TB4 Terminal 1 to C304 Terminal 4 24 VDC and MS 9200 TB4 Terminal 2 to C304 Terminal 3 24 VDC This power must be supervised by a UL listed Power Supervision Relay wired as shown in Figure 2 25 Coded Operation Connect notification appliance power from either T...

Страница 45: ...ngs Resistive 2 amps 30 VDC1 Inductive 1 amp 30 VDC 0 6 PF Pilot Duty 0 6 amps 30 VDC 0 35 PF 0 3 amps 110 VDC 0 35 PF 0 3 amps 120 VAC 0 35 PF 1 Certain electromechanical devices exhibit inductive loading characteristics For these types of devices derate the outputs to 1 amp Refer to the Device Compatibility Document for load characteristics by device FIGURE 2 24 C304 Control Module Utilized as F...

Страница 46: ... loop wiring under any terminals Break wire run to maintain supervision Resettable 24 VDC 4 wire smoke detector power 300 mA max UL listed Power Supervision Relay must be wired as last device on loop as shown 24 VDC Notification Appliance End of Line Resistor 47K ohm watt resistor N ELR in Canada Loop Out Note If more than one C304 NAC is provided install the power supervision relay after the last...

Страница 47: ...a BG 10LX pull station 1 Connect the MS 9200 Communications SLC loop to Terminal screws and on the BG 10LX 2 The BG 10LX is factory preset to address 00 Set the address by using a screwdriver to turn the rotary address switches on the back of the unit to the appropriate settings FIGURE 2 26 Addressable Manual Pull Station Wiring BG 10LX back view SLC TB6 3 SLC TB6 5 Technical Manuals Online http w...

Страница 48: ... on the remov able block 3 Before installing the appropriate addressable detector head set the detector s address on the head with a small flathead screwdriver Mark this address on the head 4 Place the removable terminal block into the connector in the detector head Be certain to properly align and snap in securely FIGURE 2 27 Wiring Detector with Removable Plug in Connector Channel Channel Channe...

Страница 49: ...r SLC loop may be protected from voltage transients by using one of the UL listed compatible surge suppressors listed in the Fire Lite Device Compatibility Document 2 15 1 UDACT F Universal Digital Alarm Communicator Transmitter The UDACT F transmits system status to UL listed Central Station receivers via the public switched telephone network It is capable of reporting up to 56 soft ware zones or...

Страница 50: ...d one alu minum in the appropriate holes located on the right side of the MS 9200 main circuit board as illustrated in Figure 2 31 UDACT F Mounting to MS 9200 on page 47 Position J10 located on the back of the UDACT F over con nector J16 which is located to the center right on the MS 9200 main circuit board and carefully connect Secure the UDACT F to the aluminum standoff with the screw provided C...

Страница 51: ...enclosure from Earth Ground terminal on the UDACT F to a solid building earth ground Conduit alone will not provide a reliable earth ground 7 UDACT F may be located up to 6 000 feet 1 800 m away from the host control panel 8 Refer to Specifications on page 9 for power requirements 9 UDACT F TB1 Terminals 6 and 7 are for future use Make no connections to these terminals FIGURE 2 32 External UDACT F...

Страница 52: ...be power limited and may be provided by the FACP or a UL listed power supply such as the FCPS 24F Up to 32 ACM 8RF Relay Control Modules may be placed onto the EIA 485 communication bus if no other devices are installed on the bus Removable terminal blocks are provided for ease of wiring installation and servicing Refer to the ACM 8RF Manual for UL power limited wiring requirements and switch SW4 ...

Страница 53: ...uit board with connector J1 on the RTM 8F option board Press firmly on the RTM 8F until it locks in place on the standoffs Be certain to tighten the screw into the metal standoff on the lower right corner This is critical to the RTM 8F transient protection Affix the terminal identification labels provided with the option module FIGURE 2 35 RTM 8F Module Installation RTM 8F Main Circuit Board alumi...

Страница 54: ...hms 4 To prevent the yellow Trouble LED from turning on when the Transmitter Output is not used no connections move jumper JP2 to the Local Energy Municipal Box position bottom two pins and install a dummy load across the Transmitter Output terminals as shown below The dummy load is a 1N4004 diode The cathode must be connected to the terminal labeled normal in Figure 2 36 and the anode must be con...

Страница 55: ...ain circuit board and the attached cable to the serial EIA 232 port on the printer or PC Use the DB25 adapter if a nine pin connector is not available on your printer or PC Note that a ground fault may occur on the MS 9200 panel dependent on the printer used when this connection is made For this reason it is important that there be no preexisting ground fault on the panel Consult the factory for r...

Страница 56: ... for this purpose When a programmed system is normal with no active alarms troubles or supervisories the SYSTEMS ALL NORMAL screen will be displayed as shown below In order to 1 program the system 2 read system status 3 print 4 edit or 5 walktest the ENTER key must first be pressed After pressing ENTER the screen shown below is displayed Pressing 1 will select system Programming which may only be ...

Страница 57: ...e AC line voltage The AC BAT fea ture is NOT password protected The following screen is displayed upon entering AC BAT Initial Power up describes initial programming procedures for a new system The same procedures are used to modify programming in an existing system Make certain the SW1 Write Protect switch is in the down position before attempting any Level 1 Programming functions 3 1 Initial Pow...

Страница 58: ...hich will access two different screens as indicated in the preceding section From either of the screens access to specific system and device programming may be obtained All programming entries are stored in nonvolatile memory The factory set passwords can be changed by the user and a method exists to clear one or both passwords Note that for Canadian applications both passwords must be changed fro...

Страница 59: ...The panel communicates with each individual addressable device and displays the type of device at each address location starting with detectors and then modules While autoprogramming the system the MS 9200 will display the following Verification of each device address and type installed on the SLC may now occur If information is correct press the ENTER key if incorrect press the left arrow key to ...

Страница 60: ...n arrow key or by pressing the appropriate numeric key Custom words may be entered via the keypad The alphanumeric operation of the keypad changes a blinking letter in the ADJ and NOUN fields For example to enter the letter R repeatedly press the 7 key to step through 7 P R and S stopping when R is displayed Press the right arrow key do not press ENTER at this time to move to the next let ter disp...

Страница 61: ... they are also incremented overflow The above increment function may be repeated with each press of the Zero key As an example the user could quickly enter FLR_3_ROOM_305 as follows 1 The cursor is on the first letter of the ADJ field Press the Zero key twice to display FLR_3 2 With the cursor on the first letter of the NOUN field press the zero key twice to recall the display ROOM_304 The cursor ...

Страница 62: ...ection of a type code may change the functional operation of the addressable device Follow the same procedure as described in New Detectors section for editing of the ADJ and NOUN fields The default zone selection is Z00 main circuit board NAC outputs 1 2 and may be set to Z01 through Z56 if desired See Software Zones on page 81 Control Module Autoprogramming A typical control module Autoprogram s...

Страница 63: ...ng display will appear For example select Detector address 3 program edit by pressing key detector followed by numeric key 3 fol lowed by ENTER Select Module address 3 program edit by pressing the key module followed by the numeric key 3 followed by ENTER If there is no device installed at this address the panel displays the next higher address where a device is installed After editing is complete...

Страница 64: ...e Inhibit N one Y 60 seconds1 AS Autosilence N one Y 10 minutes1 PS Presignal N one Y 3 minutes with 15 second Acknowledge1 CD Bell Code 1 M arch Time N one Note Bell 2 is fixed steady T Temporal C California AN Annunciators N one Z 56 Zones ZU 56 Zones Annunciator with UDACT F2 P 198 Points PU 198 Points Annunciator with UDACT F2 ST SLC loop style 4 Style 4 6 Style 6 REM Alarm Trbl Reminder N o Y...

Страница 65: ...e Y 120 seconds I Silence Inhibit N one Y 60 seconds1 A Autosilence N one Y 10 minutes1 P Presignal N one Y 3 minutes with 15 second Acknowledge1 C Bell Code N one M March Time T Temporal C California A U Annunciators N one Z 56 Zones with or without UDACT F ZU 56 Zones Annunciator with UDACT F2 P 198 Points PU 198 Points Annunciator with UDACT F2 L P LCD 40 or N one L LCD 40 Series installed requ...

Страница 66: ...ation When the Load option is selected the fol lowing screen will be displayed The left arrow key may be used to return to the program change screen The PC connects to the EIA 232 printer interface instructions provided with the Upload Download software kit Continue to press the left arrow key to return to the main program screen 3 4 Program Change Level 2 While the MS 9200 system is normal with n...

Страница 67: ...ENABLE blinking The current status label may show NORMAL TROUBL DISABL ALARM ACTIVE PROGRM TEST 01 ON OFF The status label can be changed to DISABL or back to its present status by pressing the up or down arrow keys The disable status is entered stored in memory by pressing ENTER The display then returns to the DIS ABLE ENABLE screen shown above The operator may then enter a new point number or ma...

Страница 68: ...ry buffer After pressing either 1 or 2 the screen shown below will appear If ENTER is pressed the second line goes blank and the unit is in Walktest mode Walktest may be stopped at any time by pressing the left arrow key backspace returning the unit to the main screen A one hour time out automati cally returns the system to normal operation Shorted Alarm Condition When in Walktest the panel respon...

Страница 69: ...ys the following 3 4 4 Set Time and Date If 4 is pressed the following is displayed The first digit of the hours is flashing and may be changed with the numeric pad The right arrow moves to the next digit The up and down arrows select A M or P M day of the week month day and year Pressing the ENTER key stores the time and date and returns to the Level 2 screen 3 4 5 Check Program selection 5 perfo...

Страница 70: ...vent 4 1 2 Alarm Silence The Alarm Silence key performs the same functions as Acknowledge Step In addition if an alarm exists it turns off all silenceable circuits and causes the Alarm Silence LED to turn on It also sends an Alarm Silenced message to the printer the history file and the LCD 40 A subsequent new alarm will resound the system 4 1 3 Drill Hold 2 Sec When the Drill key is held for two ...

Страница 71: ...lence This is a yellow LED that turns on after the Alarm Silence key is pressed preceded by a fire alarm condition It turns off when the Drill or System Reset key is pressed System Trouble This is a yellow LED that flashes when one or more trouble conditions occur It stays on steady when the Acknowl edge Step or Alarm Silence key is pressed The LED turns off when all trouble conditions are cleared...

Страница 72: ...tor Point type and address in this example P01 indicates Photoelectric detector assigned to address 01 The information displayed in the second line in the example above provides the following information ADJ user programmed adjective descriptor from library list or custom entry five characters maximum NOUN user programmed noun descriptor from library list or custom entry ten characters maximum Zon...

Страница 73: ... file If the trouble clears either before or after Acknowl edge the Clear Trouble message is sent to the printer as illustrated by the following example CLR TRBL_ SMOKE DET P01 ADJ NOUN ZONE TIME and DATE If all troubles clear and there are no supervisory or fire conditions active in the system the system returns to normal operation status and the Systems All Normal message is shown on the LCD dis...

Страница 74: ...d to clear automatically Alarms activate software zones control by event logic if so programmed Timers Silence Inhibit Autosilence Trouble Reminder are started Alarms activate the general alarm relay and zone Z00 NAC 1 and NAC 2 The trouble relay is not activated A typical alarm display would be 4 6 Supervisory Operation Supervisory operation is similar to alarm operation but with the following di...

Страница 75: ... for output control points but it is not necessary to list Z00 for input points as this is the default zone Z00 is not activated by supervi sory points When an input device detector M300 series modules alarms and is not disabled it activates all software zones assigned to it An output device control module or NAC that is not disabled is turned on when any of the software zones to which it is mappe...

Страница 76: ...he notification appliances will not activate for up to three minutes After three minutes the NACs will activate if the source of the alarm is not cleared This does not affect monitor modules programmed as waterflow or supervisory Presignal operation requires the approval of the local Authority Having Jurisdiction 4 13 Special System Timers 4 13 1 Silence Inhibit Timer None or 60 Seconds This optio...

Страница 77: ...ll not function 4 13 6 Disable Enable Operation Input points which are disabled do not cause an alarm or any CBE Control By Event activity Disabled output points are held in the off state All disabled points are treated as if they were in trouble with the exception being the status label that will be displayed is DISABL 4 14 Style 6 Wiring If the SLC is wired and programmed for Style 6 and a singl...

Страница 78: ... and Current System Status or History File press the 2 and then the Enter key A new menu appears which prompts the user to press 1 to print Program Status or 2 to print History file During this and all subsequent operations except print operations a two minute timer is started that will cause the panel to return to the previous display if no key is pressed within two minutes Each key press restart...

Страница 79: ... presses All events are recorded with the time and date His tory events are stored in volatile memory therefore removal of primary AC power and secondary battery power will clear the history buffer To clear the History file without removing power see Clear History on page 65 To view events in the history file use the Up and Down arrow keys to step through the events Print Program All user programm...

Страница 80: ... source to the fire alarm control panel Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code as well as local codes Use 14 AWG 2 00 mm2 wire with 600 volt insulation for this branch circuit Use Table A 1 to determine the total amount of current in AC amps that must be supplied to the fire alarm system Discontinued and replaced with CHG 120F effective...

Страница 81: ...ltered 24 VDC 5 120Hz ripple 10 mVRMS 3 TB4 Terminals 5 6 filtered 24 VDC 5 120Hz ripple 10 mVRMS 4 TB4 Terminals 3 4 nonresettable auxiliary power 300 mA 5 TB4 Terminals 5 6 resettable smoke detector power 300 mA 6 Refer to Current Limitations on following page TABLE A 2 Filtered Load in Standby External Devices Connected to TB4 Only Device Type of Devices Standby Current amps Total Current amps ...

Страница 82: ...If the normally open contact is used current consumption increases to 100 mA 6 LDM 32F with LEDs on 7 M302 Monitor Module current limited at 90 mA in alarm 8 This column must not exceed total system current draw of 6 6 amps TABLE A 3 Filtered Load in Alarm External Devices Connected to TB2 TB4 Only Device Type of Devices Alarm Current amps Total Current1 amps Main Circuit Board 1 X 0 168 0 168 RTM...

Страница 83: ... allows disabling of FACP battery charger the CHG 120F Battery Charger for 25 AH to 100 AH batteries requires separate housing TABLE A 4 Battery Calculations Standby Load Current amps X Required Standby Time in Hours 24 or 60 Hours __________ Alarm Load Current amps X Required Alarm Time in Hours i e 5 minutes 0 084 __________ Add Standby and Alarm Load for Required Ampere Hour Battery __________ ...

Страница 84: ...tput devices Use the charts on the following pages to help in zoning the system Note that monitor and control modules make up one group of 99 addresses It is critical that addresses of detectors are not duplicated and that monitor and control module addresses are not duplicated In the example on the following page Zone 1 has the following addressable devices assigned to it SD300 photoelectric dete...

Страница 85: ...o Zones FIGURE B 1 Zoning Example SD300 01 SD300 02 M300 01 C304 05 C304 04 ZONE 01 M301 02 CP300 03 CP300 04 C304 07 C304 06 C304 03 ZONE 02 SD300 05 SD300 06 CP300 07 C304 09 C304 08 ZONE 03 Input Devices Zones Output Devices Technical Manuals Online http www tech man com firealarmresources com ...

Страница 86: ...IRST HALL 51 02 SD300 1 ELEV LOBBY 52 03 CP300 2 2ND FLOOR 53 04 CP300 2 ROOM 210 54 05 SD300 3 3RD FLOOR 55 06 SD300 3 MEZZANINE 56 07 CP300 3 MECH ROOM 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 ...

Страница 87: ...2 M301 2 EAST STAIRWELL 52 03 C304 1 2 3 2ND FLOOR 53 04 C304 1 1ST FLOOR 54 05 C304 1 EAST HALL 55 06 C304 2 ELEV LOBBY 56 07 C304 2 MEZZANINE 57 08 C304 3 3RD FLOOR 58 09 C304 3 MECH ROOM 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 ...

Страница 88: ...Document 15668 Rev I 04 20 98 P N 15668 I 85 Software Zones FIGURE B 2 Blank Zoning Sheet Input Devices Zones Output Devices Technical Manuals Online http www tech man com firealarmresources com ...

Страница 89: ...e Zone Number ADJ 5 charact max NOUN 9 charact max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 50 Technical Manuals Online http www tech man com firea...

Страница 90: ...ce Type Zone Number ADJ 5 charact max NOUN 9 charact max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 50 Technical Manuals Online http www tech man com...

Страница 91: ...he DIM 485 with the standoff inserted into the main circuit board Carefully seat the DIM 485 connector on the main circuit board J11 connector and press to seat the DIM 485 on the standoff FIGURE C 1 LCD 40 Series Wiring LCD 40 Series in grounded box LCD 40 Series in grounded box Ferrite Core P N FBD 1 Required Ferrite Core P N FBD 1 Required EIA 485 DIM 485 J11 24 VDC TB4 Terms 3 4 MS 9200 in gro...

Страница 92: ...zones of alarm and trouble indications remote Acknowledge Step Alarm Silence Drill and System Reset keys System Supervisory AC Fail and Trouble indica tions Use AKS 1F keyswitch to prevent unauthorized actuation of control switches Refer to the AFM Manual for further details AFM 16ATX AEM 16ATF AEM 16ATF AEM 16ATF Ribbon Cable Ribbon Cable Ribbon Cable 8 Zones Alarm Trouble 4 switches IACK SIL DRI...

Страница 93: ...ation provides 16 alarm and trouble LEDs System Trouble LED On Line Power LED local Silence Acknowledge Drill and Reset remote switches and piezo sounder Only one per system The following configuration provides 32 alarm LEDs On Line Power LED System Trouble LED and local Silence Acknowledge switch Only one per system AFM 32AX AFM 32AX Ribbon Cable MS 9200 MS 9200 AFM 16ATF AFM 32AF MS 9200 Technic...

Страница 94: ...wing configuration provides 16 red alarm LEDs System Trouble LED On Line Power LED local Silence Acknowledge switch and piezo sounder All AFM 16AF annunciators will show the same information EIA 485 Power MS 9200 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 95: ...ted on the last four annunciators which dupli cate the previous set Ribbon Cable Ribbon Cable Ribbon Cable AFM 32AX AEM 32AF Ribbon Cable MS 9200 Ribbon Cable Ribbon Cable Ribbon Cable AFM 16ATX AEM 16ATF AEM 16ATF AEM 16ATF AFM 16ATX AEM 16ATF AEM 16ATF AEM 16ATF Receive Only No Control Switches Receive Only System Switches Don t Function Receive Transmit Control Switches Function Technical Manua...

Страница 96: ...ation Service Protected Premises Unit and Remote Station Service requires MS 5012 for connection to a compatible listed Central Station DACR or Protected Premises Receiv ing Unit This unit must be installed as outlined in Figure E 1 Central Station Service Using MS 5012 on page 94 OR UDACT F may be installed as illustrated in Refer to Figure 2 31 UDACT F Mounting to MS 9200 on page 47 and Figure 2...

Страница 97: ...erence the MS 5012 Manual for additional information 2 Program the MS 5012 for slave operation 3 SW2 Trouble No AC switch located on the bottom right of the MS 9200 main circuit board must be posi tioned in the down position for this application This prevents the transmission of a trouble on the loss of AC power TABLE E 1 MS 5012 Connections to MS 9200 MS 5012 MS 9200 Alarm TB2 1 TB3 5 TB2 2 TB3 3...

Страница 98: ...t of RTM 8F module and circuit 3 Refer to Figure 2 8 Typical UL Power limited Wiring Requirements on page 27 and UL Power limited Wiring Requirements on page 27 for information on UL power limited wiring requirements FIGURE E 2 Municipal Box Connected to RTM 8F Relay Transmitter Module FIRE Gamewell Model M34 56 Local Energy Municipal Box Polarities shown in alarm condition Dummy load with a 1N400...

Страница 99: ...er UL listed Refer to Fire Lite Alarms Inc Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby RTM 8F Relay Transmitter Module not suitable for transmission of separate alarm and trouble signals to Remote Station Cut JP1 Jumper JP2 must be in position ALARM TROUBLE REVERSE POLARITY for use in alarm and trouble transmission or ALARM ONLY for alarm transmission...

Страница 100: ...uble contact which will automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm MS 9200 Main Board MS 9200 Addressable Fire Control Panel Notes 1 Connection between the MS 9200 and the transmitter are supervised by the transmitter 2 This MS 9200 Transmitter arrangement can be employed for NFPA 72 Proprietary Pro tective Signaling System Technica...

Страница 101: ...m2 Genesis 4408 4608 Signal 98430 Belden 9581 WPW995 16 AWG 1 30 mm2 Genesis 4406 4606 Signal 98630 Belden 9575 WPW991 18 AWG 0 75 mm2 Genesis 4402 4602 Signal 98300 Belden 9574 WPW975 Untwisted unshielded pair 1 000 300 m 12 18 AWG 3 25 0 75 mm2 EIA 485 power limited Connects to annunciator modules Twisted shielded pair with a characteristic impedance of 120 ohms 6 000 1 800 m 18 AWG 0 75 mm2 EIA...

Страница 102: ... Press 2 Clear Event File Press 3 Walktest Press 4 Time Press 5 Program Check Disable Enable Press AA ENTER ENTER to Clear Hist Backspace to Escape Walktest 1 Silent 2 Pulse Sounders Press 00000 Press ENTER Change Time Date 00 00A TUE 00 00 00 Program Check OK Retest Panel Now 0 Clr 1 Auto 2 Point 3 Sys 4 Pword 5 Load Press 0 Press ENTER Press 1 Press ENTER Press 2 Press ENTER Press 3 Press ENTER ...

Страница 103: ...EXAMPLE NORMAL MONITOR M01 Z V N I N A N P N C M A U M L P N S 4 R N EXAMPLE OFF SOFTWARE ZONE Z EXAMPLE OFF BELL CKT B01 PANEL CIRCUIT Z EVENT HISTORY START EVENTS IN HIST XXXX Press 1 ENTER Program Status Print Press 2 ENTER History Print LEGEND Text inside box actually appears in LCD display Text inside oval indi cates key press Write Protect Switch on the MS 9200 motherboard Write Protect Tech...

Страница 104: ...Document 15668 Rev I 04 20 98 P N 15668 I 101 Notes Technical Manuals Online http www tech man com firealarmresources com ...

Страница 105: ...102 Document 15668 Rev I 04 20 98 P N 15668 I Notes Technical Manuals Online http www tech man com firealarmresources com ...

Страница 106: ...Document 15668 Rev I 04 20 98 P N 15668 I 103 Notes Technical Manuals Online http www tech man com firealarmresources com ...

Страница 107: ...id to Fire Lite 12 Clintonville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by Fire Lite with respect to its prod ucts Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an in...

Отзывы: