The Control Module
42
Document #15668 Rev.I 04/20/98 P/N 15668:I
Caution: Failure to break the tabs when configuring the module for Form-C operation can cause damage to the C304
module.
Communications Loop Connections
Connect the MS-9200 Communications SLC loop to C304 Terminals 1(-) and 2(+). The C304 occupies one module
address on the loop. Set the rotary switches on the module to the particular loop address required.
Contact Connections
Wire the common and the normally-open or normally closed contacts to the module as needed.
Contact Ratings
Resistive:
2 amps @ 30 VDC
1
Inductive:
1 amp @ 30 VDC (0.6 PF)
Pilot Duty:
0.6 amps @ 30 VDC (0.35 PF)
0.3 amps @ 110 VDC (0.35 PF)
0.3 amps @ 120 VAC (0.35 PF)
1. Certain electromechanical devices exhibit inductive loading characteristics. For these types of devices, derate the outputs to 1
amp. Refer to the Device Compatibility Document for load characteristics by device.
!
FIGURE 2-24:
C304 Control Module - Utilized as Form-C Relay
1 2 3 4 5 6
T
B
6
A B B+ A+ B- A-
Shield
SLC (+) TB6-3
SLC (-) TB6-5
MS-9200
+ To next device
- on Loop
Common Contact
Normally-Closed Contact
Break off Tabs
Normally-Open Contact
CAUTION! Do not loop wiring
under any terminals. Break wire
run to maintain supervision.
C304
-
-
-
-
+
+
+
+