Wiring Detectors
2.14 Wiring Detectors
To install addressable detectors:
1.
Connect the MS-9200 Communications SLC loop to Terminal (-) and (+) on the removable terminal block.
2.
If an RA400Z Remote LED Annunciator is being employed, connect the RA400Z positive terminal to the
RA+ terminal on the removable terminal block and the negative terminal to the RA(-) terminal on the remov-
able block.
3.
Before installing the appropriate addressable detector head, set the detector’s address on the head with a small
flathead screwdriver. Mark this address on the head.
4.
Place the removable terminal block into the connector in the detector head. Be certain to properly align and
snap-in securely.
FIGURE 2-27:
Wiring Detector with Removable Plug-in Connector
Channel (+)
Channel (-)
Channel (+)
Channel (-)
to next device
on Loop
Communications
SLC Loop
SD300 with removable
plug-in connector
RA400Z Remote LED
Annunciator
COMM