MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
37
Appendix B: NFPA Standard-Specific Requirements
Minimum System Requirements
The control panel has been designed for use in commercial, industrial, and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
•
Fire Alarm Control Panel.
Contains the main control board, cabinet (backbox and door), main
supply transformer and power supply.
•
Batteries.
Refer to "Appendix A: Secondary Power Calculations" on page 35.
•
Initiating Devices.
Connected to one of the control panel's Initiating Device Circuits.
•
Notification Appliances.
Connected to one of the control panel's Notification Appliance Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The
relay contacts of this control panel may be used to trip any dialer that is UL listed for Central Station/Remote
Station services. The illustrations in this appendix provide examples of possible system configurations.
Note:
Applications which require the the NOTI-FIRE 911AC or the Potter EFT-C are not FM approved.
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
•
NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter
connected to a compatible
listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm
Communicator/Transmitter - Noti-Fire 911AC" on page 38 for installation instructions for this unit.
•
411UDAC Universal Digital Alarm Communicator
connected to a compatible listed Central
Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator
- 411UDAC" on page 39 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
•
4XTMF (4412TM) Transmitter Module
for connection to a compatible listed Local Energy
Municipal Box. See "Local Energy Municipal Box" on page 40 for installation instructions for this
unit.
NFPA 72 - Remote Station Fire Alarm System
•
Fire•Lite RS82-9 Remote Station Receiver
connected to a 4XTMF (4412TM) Transmitter
Module. See "Remote Station Receiver - RS82-9" on page 41 for installation instructions for this
unit.
•
NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter
connected to a compatible
listed Central Station DACR. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC"
on page 38 for installation instructions for this unit.
•
411UDAC Universal Digital Alarm Communicator
connected to a compatible listed Central
Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 39 for
installation instructions for this unit.
NFPA 72 - Proprietary Fire Alarm System
•
Potter EFT-C McCulloh Transmitter
. See "Potter EFT-C McCulloh Transmitter" on page 42 for
installation instructions for this unit.
Содержание MS-4412B
Страница 34: ...3 System Operation System Events 34 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 Notes ...
Страница 48: ...48 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...
Страница 49: ...MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 49 ...
Страница 50: ...50 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...