Output Circuits
2. Installation
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
19
Output Circuits
Notification Appliance Circuits
The control panel provides two Notification Appliance Circuits (Style Y). Each circuit is capable of 1.5
amps of current. Total current drawn from all four circuits cannot exceed 2.25 amps. NACs are supervised
and power-limited.
Note:
Refer to the Device Compatibility Document for suitable devices.
For details on how jumper configurations affect panel functions see "Supervisory Configuration" on page
20.
• For DIP switch configuration, see "Setting Mode of Operation" on page 27.
• For non-silenceable service on Initiating Zone #1, see "Non-Silenceable Service" on page 32.
• Unused circuits must be connected with a dummy load as shown.
Figure 8 Notification Appliance Circuits
TB3
MS4
4
B-n
a
c.cd
r
Polarized
Horn
Polarized
Strobe
Polarized
Bell
Style Y
(Class B)
24 Volt -
4.7K, 1/2-Watt ELR
PN 71252 (UL listed)
12 Volt -
2.2K, 1/2-Watt ELR
PN R-2.2K (UL listed)