Zone Relay Module - 4XZMF (4412ZM)
Relay #1 through #4 will activate with Input #1 through #4 and remain latched unless jumper “LATCH”
is cut. For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact,
the relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note:
If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.
Figure 15 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring
Requirements" on page 16.
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
• If this module is used to drive both nonpower-limited and power-limited relays that are
next to each
other
, refer to the figure below which shows the one allowable arrangement.
Figure 16 Mixing Power-Limited and Nonpower-Limited Circuits
TB1
LATCH
DISABLE
J2
Disable Switch
“Latch” Jumper
4X
ZMF
.cdr
Power-Limited
Circuit
Nonpower-Limited
Circuit
MS44
--
4xzm
f1
.cd
r
No Connection
Содержание MS-4412B
Страница 34: ...3 System Operation System Events 34 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 Notes ...
Страница 48: ...48 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...
Страница 49: ...MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 49 ...
Страница 50: ...50 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...