Appendix A: Secondary Power Calculations
Standby Battery Requirements
The Standby Battery Current obtained in the table below represents the amount of current that must be
supplied by the secondary power source (batteries) to sustain control panel operation for one hour.
Note:
The control panel will support the installation of one or two optional modules, including two of the same type of
module. Only one 4XLMF (4412LM) can be included in this count.
Table 1 Standby Battery Current
Device Type
# of
Devices
Current
(amps)
Total Current
(amps)
Main Circuit Board
1
X
0.088
=
0.088
4XZMF/4412ZM
ZoneRelay Module
[ ]
X
0.008
=
4XTMF/4412TM
Transmitter
Module
[ ]
X
0.011
=
• Reverse Polarity
Alarm output
[ ]
X
0.005
=
• Reverse Polarity
Trouble output
[ ]
X
0.005
=
RZA-4XF/4XLMF
(4412LM)
Remote Annunciator
[ ]
(1 max)
X
0.019
=
4XMMF
Meter Module
[ ]
X
0.001
=
2-wire
Detector Heads
[ ]
X
[ ]
1
1. Refer to the Device Compatibility Document for smoke detector standby current.
=
4-wire
Detector Heads
[ ]
X
[ ]
1
=
End-of-line Relays
2
2. Must use compatible listed Power Supervision Relay.
[ ]
X
[ ]
=
Current Draw from
TB2 (nonalarm)
3
3. The total standby current must include both the resettable (TB2 - VR terminals) and
nonresettable (TB2 - VNR terminals) power. Caution must be taken to ensure that current drawn
from these outputs during alarm does not exceed maximum ratings specified.
[ ]
X
[ ]
=
Standby Battery Current
=
amps
Содержание MS-4412B
Страница 34: ...3 System Operation System Events 34 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 Notes ...
Страница 48: ...48 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...
Страница 49: ...MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 49 ...
Страница 50: ...50 MS 4412B MS 4424B Instruction Manual PN 15125 G1 10 22 02 ...