GAS SUPPLY AND PRESSURE REGULATOR
Gas supply: These cooktops are shipped from the factory set for either natural gas or LP gas. Check to be sure
you have the correct cooktop for the type of gas being used.
The pressure regulator must be connected in series with the manifold of the cooktop and must remain in series
with the supply line regardless type of gas being used.
The natural gas model is designed to operate at 5″ water column pressure. A regulator is required at the
natural
gas source to provide a minimum of 6″ water column to the cooktop
regulator
The liquid propane model is designed to operate at 10″ water column pressure. A regulator is
required at the LP
Gas source to provide a minimum of 11″water column to the cooktop
regulator.
For ease of installation, if local codes permit the gas supply line into the cooktop should be 1/2″or 3/4″ ID flexible
metal appliance connector with three to five feet long.
NOTE:
Purchase new flexible line. DO NOT USE OLD, PREVIOUSLY USED FLEXIBLE LINE
The gas inlet is located on the bottom of the burner box at the rear and center.
Make gas connection through rear wall, or on cabinet floor at rear, as illustrated.
Install the house gas supply at least 1. from the back wall. Locate the electrical outlet 12. below the countertop.