4.3 LEVEL 0 - Performance parameter, vibratory conveyor drive
After power ON, the display switches to the "Amplitude" root display. Depending on this, the 2 and 3 keys
can be used to roll to every individual parameter on this level. The following parameters are available:
Parameter: Amplitude [V~]
Without code
Value can be set from 1 - 230 max.
Increment 1 V~
Max.
voltage
depends
on
mains
voltage
range.
Parameter: min. amplitude limit [V~]
Code B
Value can be set from 1 - 230, depending on the mains voltage range
Increment 1 V~
Limited
by
max.
amplitude
limit
Parameter: max. amplitude limit [V~]
Code B
Value can be set from 1 - 230, depending on the mains voltage range
Increment 1 V~
Limited
by
min.
amplitude
limit
Parameter: Current limitation [A~] for
the
vibratory conveyor
Code B
Value can be set from 0.1 - 6.0
Increment 0.1 A~
For
protection
of
the
magnets
the
value is set to the max. permissible current
of
all
connected
magnets.
Parameter: Frequency [Hz]
Code B
Value can be set from 5.0 - 99.9 / 100 - 200
Increment 0.1 Hz, then starting from 100 Hz, increment is 1 Hz
The
specified
frequency
is
equivalent to the mains frequency, i.e. set 50 Hz
corresponds to the mains frequency of 50 Hz -> 6.000 oscillations per minute.
Vibrations per minute = frequency x 60 x 2
Parameter: Soft start [s]
Code A and B
Value can be set from 0.1 - 5.0
Increment 0.1 s
Voltage ramp from 0V~ to the set amplitude value
within
the
set
time.