Operating instructions FS-26E
Status as of 10 / 2019
Page 17
Parameter: Soft stop [s]
Code A and B
Value can be set from 0.1 - 5.0
Increment 0.1 s
Voltage ramp from the set amplitude value to 0V~ within the
set
time.
Parameter:
Setpoint specification [function]
Code A and B
Value can be set to F, I, P, U,
b
F
-
Setpoint
specified
via
membrane
keypad
I - Setpoint specified via analog current 4 - 20 mA=
U - Setpoint specified via analog voltage 0 - 10 V=
P - Setpoint specified via potentiometer 10K
b - Setpoint specified via acceleration sensor
Parameter acceleration sensor selection
Code B
Value can be set to 0, U, I,
Visible after code input
0 - No acceleration sensor connected
U -
Acceleration sensor with voltage output
I - Acceleration sensor with current output
If a sensor type is activated, the menu for the setpoint specification is supplemented with menu item b.
Setpoint specification for acceleration sensor.
Parameter wave form selection [function]
Code B
Value can be set to G, H
G
-
Full-wave
^^^^^^
H - Half-wave ^ ^ ^ (only every other oscillation is output)
Parameter min. acceleration limit [g]
Code B
Value can be set to 0.0 - 20.0
Visible after code input
increment 0.1 g
Lower
value
in
readjustment
range
Parameter max. acceleration limit [g]
Code B
Value can be set to 0.0 - 20.0
Visible after code input
increment 0.1 g
Upper
value
in
readjustment
range
Control parameter proportional component (closed-loop gain)
Code B
Value can be set to 0.1 - 19.9
Visible after code input
increment 0.1 g
Default 5.0