Operating instructions FS-26E
Status as of 10 / 2019
Page 31
4.12 Safely setting up the vibratory conveyor
First the following connection values of the vibratory conveyor must be determined:
Maximum permissible voltage [V~]
Maximum permissible current consumption [A~]
Operating frequency [Hz] of the used AC oscillating magnets
Based on the determined values, the permissible working limits without a conveyor connected are now
set (vibration amplitude 30...80 V~).
Start in "Amplitude" root display
1 - 115/230 V~
Set the value to the maximum permissible voltage of the AC oscillating magnets of the conveyor by first
changing to programming mode (see the control panel and operator code).
Then switch to the next menu item, "Current limit".
0.1 - 6.0 A~
Set the maximum permissible total current of the conveyor here.
As another step, it can now be defined whether full-wave or half-wave mode should be worked with. In
half-wave mode, the set frequency is cut in half automatically, thereby increasing the total current. For
this reason, it is sensible to correctly set the current limit, since otherwise the magnets of the conveyor
could be damaged.
G or H
After the work limits and wave form have been set, they should be intermediately saved.
Next, the optimal working frequency of the conveyor is determined; to do this, go back to the menu item
0F.
5.0 - 200 Hz