| FR300V SERIES FUEL TRANSFER PUMPS
Electric Wiring
WARNING!
Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national electrical code NEC/ANSI/NFPA 70,
NFPA30, and NFPA 30A, as appropriate to the intended use of the pump. Threaded rigid conduit, sealed fittings, and conductor seal should be used. The pump
must be properly grounded. Improper installation or use of this pump can result in serious bodily injury, or death!
CAUTION!
All pumps should be operated at the Rated Nameplate Voltage. Power should be supplied to the pump from a dedicated 30 amp circuit breaker.
No other equipment should be powered by this circuit. Wiring must be of sufficient size to carry the correct current for the pump. Voltage drop will vary
with distance to pump and size of wire; refer to the National Electrical Code (NEC), or local codes, for Voltage Drop Compensation to be sure you are using
the correct size wire for your application.
Wiring Procedure
WARNING!
The “AUX.” wire IS A LIVE WIRE when the switch is on! The “AUX” lead wire is insulated and enclosed when shipped. DO NOT connect this wire without
first verifying the “ON” line voltage of the wire for compatibility with the equipment to be installed. Maximum amperage on this wire is 1 amp. The “AUX” wire must
be insulated and enclosed in the junction box if not used.
1. Remove the junction box cover and straighten the wires to make sure the stripped wire ends are accessible outside the junction box.
2. Connect the pump wires to the power supply lines according to the diagram. Be certain to properly insulate the connections with the appropriate wire nuts or other connectors.
Note that the ground wire MUST be connected.
3. Fold the wires back into the junction box and replace the cover, making sure the cover gasket is in place.
Use the Voltage Selector Switch on the end of the pump to select the input voltage for the pump. NOTE: The pump comes from the factory pre-set to 115V AC position.
IMPORTANT!
Be certain the gasket for the cover is in place, and the screws draw the cover down tight over the junction box. There must be no gap between
the junction box and it’s cover.
115 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
230 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
Pump Switch Lever
ON
OFF
Voltage Selector Switch
MOTOR
ORANGE
BLACK
WHITE
GREEN
GRN
NEU
AC
AUX
MOTOR
ORANGE
BLACK
WHITE
GREEN
GRN
AC
AC
AUX
MAX CABLE LENGTH IN FEET (METERS)
Solid Wire
Stranded Wire
AWG
14
12
10
8
6
4
14
12
10
8
6
4
115V AC
(60Hz motor)
62
99
158
250
--
--
61
96
154
245
389
620
230V AC
(50Hz motor)
214
340
542
859
--
--
209
331
529
844
--
--
230V AC
(60Hz motor)
221
351
560
887
--
--
216
342
546
871
--
--
115V AC
(60Hz motor)
44
71
113
178
--
--
43
69
110
175
278
443
230V AC
(50Hz motor)
146
232
369
585
--
--
142
226
360
574
--
--
230V AC
(60Hz motor)
149
237
377
598
--
--
145
231
368
587
--
--
1/2
H
P
3/4
H
P
Conduit opening
1/2" NPT
Содержание FR300V Series
Страница 1: ...MADE IN USA FR300V SERIES FUEL TRANSFER PUMPS Installation and operation manual...
Страница 13: ...MADE IN USA POMPE DE TRANSFERT DE CARBURANT S RIE FR300V Manuel d installation et d utilisation...
Страница 25: ...MADE IN USA BOMBA DE TRANSFERENCIA DE COMBUSTIBLE SERIE FR300V Manual de instalaci n y operaci n...
Страница 37: ...MADE IN USA KRAFTSTOFFTRANSFERPUMPE FR300V SERIES Einbau und Betriebsanleitung...