Installation and Operation Manual
FVA-IP Camera
50
P/N 06-523 (Rev. 6)
Revision Date: June, 2019
Fuel Source
Distance to
detector
2.8 mm FOV
6 mm FOV
8 mm FOV
EX 8 mm
FOV
1 ft pan of Heptane
100 ft
18
9
9
9
1 ft pan of JP‐8
100 ft
18
10
10
10
1 ft pan of Ethyl Alcohol
100 ft
21
10
11
11
1 ft pan of Isopropyl Alcohol
100 ft
16
9
9
10
1 ft pan of Unleaded Gasoline
100 ft
8
8
8
9
4 min Smoke Emitter
100 ft
301
94
52
63
4 min Smoke emitter
75 ft
43
24
22
48
6 in pan of Heptane
100 ft
100
10
9
10
Cardboard boxes and paper
4 ea. 10 x 10 x 4‐in. boxes
100 ft
278
83
101
97
6 in diameter pan of
Heptane/toluene 75/25
28 ft
19
19
20
18
Shredded newspaper
28 ft
127
150
102
151
Smoldering wood
28 ft
3062
3279
3027
2927
Wood Crib 6 x 6 x 2.5‐in.
28 ft
142
192
145
194
Known nuisance sources include: Welding, grinding, modulated light sources.
Содержание FVA-IP
Страница 40: ...Installation and Operation Manual FVA IP Camera 36 P N 06 523 Rev 6 Revision Date June 2019...
Страница 41: ...FVA IP Camera Installation and Operation Manual Revision Date June 2019 P N 06 523 Rev 5 37...
Страница 42: ...Installation and Operation Manual FVA IP Camera 38 P N 06 523 Rev 6 Revision Date June 2019...
Страница 48: ...Installation and Operation Manual FVA IP Camera 44 P N 06 523 Rev 6 Revision Date June 2019...
Страница 49: ...FVA IP Camera Installation and Operation Manual Revision Date June 2019 P N 06 523 Rev 5 45...
Страница 50: ...Installation and Operation Manual FVA IP Camera 46 P N 06 523 Rev 6 Revision Date June 2019...
Страница 51: ...FVA IP Camera Installation and Operation Manual Revision Date June 2019 P N 06 523 Rev 5 47...
Страница 52: ...Installation and Operation Manual FVA IP Camera 48 P N 06 523 Rev 6 Revision Date June 2019...