Switching behaviour diagrams, with multi-pin plug socket NECA-S1G9-P9-MP1
è
Fig.20 and with
multi-pin plug socket NECA-S1G9-P9-MP3/MP5
è
Status of valve
Signal contact
Control for pressurisation by EN1 and EN2
Open
Control for exhaust through EN1 and EN2
Closed
Malfunction (red LED flashing)
Open
Supply voltage is not connected
Open
Tab. 5 Switching statuses of the signal contact
Switch-through pressure/filling time
The flow control screw in the cover generates a gradual pressure build-up of outlet pressure p2. The
pressure rise can be adjusted by turning the flow control screw. When the outlet pressure p2 reaches
about 50% of the operating pressure p1, the valve opens and the maximum flow rate performance is
enabled.
1 Ratio of p2 to p1 [%]
2 Time axis
Fig. 11 Switch-through pressure tolerance field
Example:
At an operating pressure of p1 = 4 bar with reference to the approved tolerance of ± 20% a switch-
through pressure of 1.2 to 2.8 bar is permissible.
5.3
Safety function in accordance with EN ISO 13849
The product is a safe, redundant mechatronic system designed for implementation of the safety func-
tions:
–
Safe venting
–
Protection against unexpected pressure build-up (pressurisation).
Product Overview
15
Festo — MS6-SV-...-E-10V24 — 2019-10d