Festo – MS6(N)-SV-...-E-ASIS – 1205NH English
6.1
Connect the earth cable
•
Connect the earth terminal with low imped-
ance (short cable with large cross-sectional
area) to the earth potential.
This prevents interference from electromag-
netic sources and ensures electromagnetic
compatibility in accordance with EMC direct-
ives.
Fig. 6
Earth cable connection
6.2
Connect AS-i bus
Observe with branch lines:
–
The maximum overall length of the AS-i bus (100 m without repeater/extender)
–
Cable length for the load voltage connection (dependent on the current consumption and
fluctuations in the load voltage).
6.2.1
Connection to M12 plug
M12 plug, 4-pin (In)
M12 socket, 4-pin (Out)
Pin 1:
AS-i +
Pin 1:
AS-i +
Pin 2:
n.c.
Pin 2:
Addressing contact –
Pin 3:
AS-i –
Pin 3:
AS-i –
Pin 4:
n.c.
Pin 4:
Addressing c
Tab. 4
AS-interface bus connection
•
Seal unused connections with protective caps of type ISK M12 or UIFB1-02-1/4.
Note
Festo accessories can be found at:
www.festo.com/catalogue