MS6-SV-...-E-10V24
Festo – MS6-SV-...-E-10V24 – 1310b English
63
6.3
Inputs and outputs
Terminal in
multi-pin plug
socket NECA-...
I/O
Allocation
1
EN1
Enable signal 1 (static or
dynamic)
Input 0 V/24 V
(EN 61131-2 type 2)
Section 4.3
“Connection
examples”
2
EN2
Enable signal 2 (static or
dynamic)
Input 0 V/24 V
(EN 61131-2 type 2)
3
13
Signal contact, NO
Potential-free
contact
(semiconductor
relay),
Max. 120 mA
Max. 60 V DC
Section 4.4
“Signal contact”
4
14
5
A5
Contact for “Automatic
start” operating mode
–
Section 4.1 and
4.3
6
S34
Contact for “Automatic
start” or “Monitored
start” operating mode
Input 0 V/24 V
(EN 61131-2 type 2)
7
–
–
8
+L1
Operating voltage
+24 V DC ±10 %
9
M
GND
Tab. 4
Terminal assignment
7
Commissioning
Note
For easier commissioning, we recommend planning a reset button (normally closed) in
the power supply circuit. This simplifies resetting in case of error.
The following description of commissioning is graphically supported by the diagrams on the next pages
(with multi-pin plug socket NECA-S1G9-P9-MP1
Fig. 20; with multi-pin plug socket NECA-
S1G9-P9-MP3/MP5
Fig. 22). The diagrams show the switching characteristics of the inputs and
outputs in normal operation (if the “Automatic start” operating mode has been set). The operator’s
actions are marked in the diagram by an arrow.
To commission the device, proceed as follows:
1. Apply operating pressure p1.
2. Switch on the operating voltage. The MS6-SV-E automatically tests itself for errors.
•
Power LED (green)
–
illuminates during self test for around 6 s
–
flashes green after successful self test,