MS6-SV-...-E-10V24
Festo – MS6-SV-...-E-10V24 – 1310b English
49
4.2
Operational principle of the multi-pin plug socket NECA-…-MP1,
-MP3 and -MP5
Status of EN1
Status of EN2
Status of valve
with NECA-…-MP1
Status of valve
with NECA-…-MP3
Status of valve with
NECA-…-MP5
0 V
0 V
Unpressurized
Valve goes into
the fault mode
Valve does not go into the
fault mode, but remains in
the safe, unpressurized
status
Note:
Cross-circuit detection
and error detection/
evaluation via external
controller necessary
0 V
24 V
Valve goes into
the fault mode
Pressurized
Pressurized
24 V
24 V
Pressurized
Valve goes into
the fault mode
Valve does not go into the
fault mode, but remains in
the safe, unpressurized
status
Note:
Cross-circuit detection
and error detection/
evaluation via external
controller necessary
24 V
0 V
Valve goes into
the fault mode
Unpressurized
Unpressurized
Tab. 1
Operational principle of the multi-pin plug socket, NECA-...