3
Mounting and installation
80
Festo – P.BE-MPA-EN – 1309f – English
3.9.3
MPA-S valve terminal with multi-pin plug connection
–
Address allocation in ascending order without gaps (
example)
–
Address assignment does not depend on it is equipped with blanking plates or valve plates.
–
Depending on the electronics module, a valve position occupies the following number of addresses:
Number of addresses
Electronics module
MPA1
MPA2
One address per valve
position
VMPA1-MPM-EMM-
4
The E-module occupies 4
addresses.
VMPA2-MPM-EMM-
2
The E-module occupies 2
addresses.
Two addresses per valve
position
VMPA1-MPM-EMM-
8
The E-module occupies 8
addresses.
VMPA2-MPM-EMM-
4
The E-module occupies 4
addresses.
Tab. 3.13 Electronics module for multi-pin plug connection
–
If a valve location occupies 2 addresses, the following applies:
–
Solenoid coil 14 occupies the less significant address,
–
Solenoid coil 12 occupies the higher-value address.
Example of address assignment
Caution
Note that addresses may be shifted if the valve terminal is expanded subsequently.
In the subsequent example, an MPA-S valve terminal type MPA-MPM-PI with the following components
is addressed:
Component
MPA1
MPA2
In-line valve manifolds
2 (8 valve positions)
2 (4 valve positions)
Electronics module
1 V
MPA1
-MPM-EMM-
8
1
VMPA2
-MPM-EMM-
4
1
VMPA1
-MPM-EMM-
4
1
VMPA2
-MPM-EMM-
2
Tab. 3.14 Example: Electronics module for multi-pin plug connection
Содержание MPA-S
Страница 165: ...C Glossary Festo P BE MPA EN 1309f English 165 C Glossary...
Страница 168: ...C Glossary 168 Festo P BE MPA EN 1309f English...
Страница 172: ...MPA S 172 Festo P BE MPA EN 1309f English...
Страница 173: ......