![Festo CPX-P Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/festo/cpx-p/cpx-p_user-manual_2284200046.webp)
Subject to change – 2018/04
46
è
Internet: www.festo.com/catalogue/...
Terminal CPX-P
Technical data – Bus node CPX-FB13
Connection and display components
1
2
4
3
1
Bus status LEDs/bus fault
2
CPX-P-specific status LEDs
3
Fieldbus connection (9-pin Sub-D
socket)
4
DIL switch cover
Pin allocation for PROFIBUS DP interface
Pin allocation
Pin
Signal
Designation
Sub-D socket
1
n.c.
Not connected
2
n.c.
Not connected
3
RxD/TxD-P
Received/transmitted data P
4
CNTR-P
1)
Repeater control signal
5
DGND
Data reference potential (M5V)
6
VP
Supply voltage (P5V)
7
n.c.
Not connected
8
RxD/TxD-N
Received/transmitted data N
9
n.c.
Not connected
Hous
ing
Screened
Connection to housing
Bus connection M12 adapter (B-coded)
Incoming
1
n.c.
Not connected
2
RxD/TxD-N
Received/transmitted data N
3
n.c.
Not connected
4
RxD/TxD-P
Received/transmitted data P
5 and
M12
Screened
Connection to FE (functional earth)
Outgoing
1
VP
Supply voltage (P5V)
2
RxD/TxD-N
Received/transmitted data N
3
DGND
Data reference potential (M5V)
4
RxD/TxD-P
Received/transmitted data P
5 and
M12
Screened
Connection to FE (functional earth)
1)
The repeater control signal CNTR-P is a TTL signal..
Содержание CPX-P