Terminal CPX-P
Technical data – CPX Maintenance Tool
Function
CPX-P Maintenance Tool (CPX-FMT)
combines service software with a con
necting adapter. The service software
is a tool for the design, parameterisa
tion and online diagnostics of the
CPX-P terminal. The USB-to-M12
adapter features built-in galvanic
isolation (between CPX-P and PC) and
enables a PC to be connected to the
diagnostic interface of the CPX-P
terminal.
Adapter
Software on CD-ROM
Application
Only from Festo
The CPX-FMT software enables access
to CPX-P valve terminals via Ethernet
with the control block CPX-CEC and the
bus nodes PROFINET (FB 33, FB 34,
FB 35). The bus nodes or control block
can be connected directly to the PC via
a USB adapter from Festo. Similar to
the operator unit (CPX-MMI),
diagnostic data such as the error trace
or module diagnostics can be read out
and parameters can be modified in
plain text. In contrast to the operator
unit (CPX-MMI), the data can be used
directly on a PC. There is an option,
for example, to send screenshots of a
configuration or the current error trace
directly via e-mail. In addition, CPX-P
configurations can also be saved and
archived directly as a CPX-FMT project.
Undocumented changes can
subsequently be identified using the
online/offline comparison function.
On-site tests such as the actuation of
valves or the emulation of sensor
feedback (in both cases called
"forcing"), for example, can be
performed without an existing
controller infrastructure. It must be
noted that with both the CPX-P
Maintenance Tool (CPX-FMT) and the
operator unit (CPX-MMI), only local
parameters on the CPX-P valve
terminal can be changed and saved.
The configuration of the networks or
controller software cannot be
influenced.
General technical data
Type
NEFC-M12G5-0.3-U1G5
System requirements
PC
IBM-compatible
Drive
CD-ROM
Interfaces
USB port (specification USB 1.1 or higher)
Operating system
Microsoft Windows 2000 or XP
Functional range
Configuration and parameterisation
Reading out of system, module, channel diagnostics and error trace
Saving of the configuration as a project
Integration of plug-ins/links to self-executing programs
Scope of delivery
Adapter M12, 5-pin to mini USB socket
CD-ROM with installation program
Type of mounting
Screw-in
Electrical connection
Plug M12x1, 5-pin
Adapter cable composition
4 x 0.34 mm
2
Cable length
[m]
0.3
Protection class to EN 60529
IP20
CE marking (see declaration of conformity)
To EU EMC Directive
Ambient temperature
[°C]
–5 … +50
Material
Housing
ABS
Cable sheath
PUR
Pin contact
Gold-plated brass
Note on materials
RoHS-compliant