Commissioning
23
No.
Question
Relevant
Done
7
Are the implemented protective measures mutually compatible?
Yes
o
No
o
o
8
Has adequate consideration been given to the potential conse-
quences of using a machine designed for commercial/industrial pur-
poses in a non-commercial/non-industrial area?
Yes
o
No
o
o
9
Can it be guaranteed that the implemented measures will not severely
impair the machine’s ability to perform its function?
Yes
o
No
o
o
Tab. 7: Questions for validation in accordance with EN ISO 12100 (example)
Questions for validation in accordance with EN ISO 13849-2 (example)
No.
Question
Relevant
Done
1
Has a risk assessment been carried out?
Yes
o
No
o
o
2
Have a list of issues and a validation plan been drawn up?
Yes
o
No
o
o
3
Has the validation plan – including analysis and inspection – been
worked through and has a validation report been created? The fol-
lowing must be inspected as a minimum as part of the validation:
Yes
o
No
o
o
3a
Inspection of components: is the servo drive described here being
used (check using the rating plate)?
Yes
o
No
o
o
3b
Is the wiring correct (check using the circuit diagram)?
Yes
o
No
o
o
3b1
When using an EC motor with a safety classification of SIL 3, cat. 3,
Pl e: have the inputs for STO been connected to the safety relay unit
via 2 channels?
When using a stepper motor with a safety classification of SIL 3,
cat. 3, Pl e or an EC motor with a safety classification of SIL 2, cat. 3,
Pl d: have the inputs for STO been connected to the safety relay unit
or the safe sensor via 2 channels?
Yes
o
No
o
o
3b2
When using an EC motor with a safety classification of SIL 3, cat. 3,
Pl e: has the diagnostic contact STA been connected to the safety
relay unit?
Yes
o
No
o
o
3b3
If multiple servo drives have been connected together (linked) via
X1A: have the connection instructions been taken into account? .
Yes
o
No
o
o
3c
Functional tests:
Yes
o
No
o
o
3c1
Actuation of the system emergency stop: is the drive brought to a
standstill in the desired manner?
Yes
o
No
o
o