Description of the safety function STO
19
Fig. 5: Time response when activating the SS1 safety function (external circuitry) with restart
Time
Description
Value
T_K1
Delay time between switching S1 and closing
instantaneous contact K1
è
Data sheet of the safety
relay unit
T_K1_V
Delay time between S1 and opening of the off-
delayed contacts K1
Adjustable on the safety
relay unit
T_STO-A/B_OFF
STO-A/B – switching time from high to low
data: electrical data of the
STO-A and STO-B inputs
T_STO-A/B_ON
STO-A/B – switching time from low to high
T_DRIVE_V
Delay of the CMMP-AS-M0
0 … 10 ms
T_DIN5_SU
Time that DIN5 must still be low after switching
on STO-A/B again and changing the status of the
STO module
>
20 ms