5.3 Technical data table
5.4 Diagrams
Pressure loss
Key
A
Pressure losses m H
2
O column
B
Delivery m
3
/h
MODEL
119
136
153
170
Powers
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Heating Capacity (Net
Heat Value - Hi)
kW
131
77
149
89
168
100
187
110
Useful Heating Power
kW
119
71
136
82
153
92
170
102
Gas supply
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pilot nozzle G20
mm
1 x 0.40
1 x 0.40
1 x 0.40
1 x 0.40
Pilot nozzle G31
mm
1 x 0.24
1 x 0.24
1 x 0.24
1 x 0.24
Main nozzles G20
mm
7 x 3.40
8 x 3.40
9 x 3.40
10 x 3.40
Supply pressure G20
mbar
20
20
20
20
Pressure at burner G20
mbar
13.3
4.8
13.3
4.8
13.3
4.8
13.3
4.8
Delivery G20
m3/h
13.8
8.1
15.8
9.4
17.9
10.6
19.8
11.6
Main nozzles G31
mm
7 x 2.15
8 x 2.15
9 x 2.15
10 x 2.15
Supply pressure G31
mbar
37
37
37
37
Pressure at burner G31
mbar
36
11.4
36
11.4
36
11.4
36
11.4
Delivery G31
kg/h
10.26
6.0
11.6
6.9
13.2
7.8
14.64
8.6
Heating
Max. working tempera-
ture
°C
100
100
100
100
Max. working pressure in
heating
bar
6
6
6
6
No. elements
8
9
10
11
Min. working pressure in
heating
bar
0.4
0.4
0.4
0.4
No. burner trains
7
8
9
10
Boiler water content
litres
38
42
46
50
Weight
Weight with packing
kg
470
530
575
625
Electrical power supply
Max. electrical input
W
32
32
60
60
Power voltage/frequency
V/Hz
230/50
230/50
230/50
230/50
Electrical protection rat-
ing
IP
X0D
X0D
X0D
X0D
MODEL
187
221
255
289
Powers
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Heating Capacity (Net
Heat Value - Hi)
kW
206
122
243
144
280
166
317
188
Useful Heating Capacity
kW
187
112
221
133
255
153
289
173
Gas supply
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pmax
Pmin
Pilot nozzle G20
mm
1 x 0.40
1 x 0.40
1 x 0.40
1 x 0.40
Pilot nozzle G31
mm
1 x 0.24
1 x 0.24
1 x 0.24
1 x 0.24
Main nozzles G20
mm
11 x 3.40
13 x 3.40
15 x 3.40
17 x 3.40
Supply pressure G20
mbar
20
20
20
20
Pressure at burner G20
mbar
13.3
4.8
13.3
4.8
13.3
4.8
13.3
4.8
Delivery G20
m3/h
21.8
12.9
25.7
15.2
29.6
17.6
33.5
19.9
Main nozzles G31
mm
11 x 2.15
13 x 2.15
15 x 2.15
17 x 2.15
Supply pressure G31
mbar
37
37
37
37
Pressure at burner G31
mbar
36
11.4
36
11.4
36
11.4
36
11.4
Delivery G31
kg/h
16.31
9.5
19.0
11.2
21.92
12.9
24.82
14.6
Heating
Max. working tempera-
ture
°C
100
100
100
100
Max. working pressure in
heating
bar
6
6
6
6
No. elements
12
14
16
18
Min. working pressure in
heating
bar
0.4
0.4
0.4
0.4
No. burner trains
11
13
15
17
Boiler water content
litres
54
62
70
78
Weight
Weight with packing
kg
665
760
875
945
Electrical power supply
Max. electrical input
W
32
32
60
60
Power voltage/frequency
V/Hz
230/50
230/50
230/50
230/50
Electrical protection rat-
ing
IP
X0D
X0D
X0D
X0D
40
3
4
5
6 7 8 9 10
20
30
6
5
2
3
4
0.6
0.7
0.8
0.9
1
221
289
119
136
255
0.2
0.3
0.4
0.5
153
170
187
A
B
cod. 3540T624 - Rev. 01 - 04/2018