3. INSTALLATION
3.1 General Instructions

B

This unit must only be used for its intended purpose.
This unit is designed to heat water to a temperature below boiling point at at-
mospheric pressure and must be connected to a heating system and/or a water
supply system for domestic use, compatible with its performance, characteris-
tics and its heating capacity. Any other use is considered improper.

THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED PERSONNEL, IN AC-
CORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL,
THE PROVISIONS OF CURRENT LAW, ANY LOCAL REGULATIONS AND THE
RULES OF PROPER WORKMANSHIP.
The Manufacturer declines any liability for damage or injury caused by incorrect installa-
tion.

3.2 Place of installation

This unit is an “open chamber” type and can only be installed and operated in perma-
nently ventilated rooms. An insufficient flow of combustion air to the boiler will affect its
normal operation and fume evacuation. Also, the fumes forming in these conditions (ox-
ides) are extremely harmful to the health if dispersed in the domestic environment.
Therefore the place of installation must be free of dust, flammable materials or objects
or corrosive gases. The room must be dry and not subject to freezing.
When positioning the boiler, leave sufficient space around it for normal maintenance ac-
tivities.

3.3 Plumbing connections
Instructions

The heating capacity of the unit must be previously established by calculating the build-
ing's heat requirement according to the current regulations. For proper operation and
long life of the boiler, the plumbing system must be adequate and complete with all ac-
cessories that guarantee regular operation and running.
If the delivery and return pipes follow a path where air pockets could form in certain plac-
es, it is advisable to install vent valves at these points. Also, install a discharge device at
the lowest point in the system to allow its complete emptying.
If the boiler is installed at a lower level than the system, it is advisable to provide a flow-
stop valve to prevent the natural circulation of system water.
The temperature drop between the delivery manifold and the return to the boiler should
not exceed 20°C.

B

Do not use the water system pipes to earth electrical appliances.

Before installation, carefully wash all the pipes of the system to remove any residuals or
impurities that could affect proper operation of the unit.
Carry out the relevant connections as indicated in fig. 10.
It is advisable to install on-off valves between the boiler and heating system allowing the
boiler to be isolated from the system if necessary.

B

Make the boiler connection in such a way that its internal pipes are free of
stress.

Water system characteristics

In the presence of water harder than 25° Fr, it is advisable to use suitably treated water,
in order to avoid possible scaling in the boiler caused by hard water, or corrosion pro-
duced by aggressive water. Due to its low thermal conductivity, scaling even just a few
mm thick causes significant overheating of the boiler walls with consequent serious prob-
lems.
Water treatment is indispensable in case of very large systems (containing large
amounts of water) or with frequent introduction of replenishing water in the system. If par-
tial or total emptying of the system becomes necessary in these cases, it is advisable to
refill with treated water.

Filling boiler and system

The filling pressure with system cold system must be approx. 1 bar. If, during operation,
the system pressure falls (due to the evaporation of gases dissolved in the water) to val-
ues below the minimum described above, the user must bring it to the initial value. For
correct operation of the boiler, when hot, its pressure must be approx. 1.5-2 bar.

3.4 Gas connection

B

Before carrying out the connection, make sure the unit is arranged for the type
of fuel available and carefully clean all the system gas pipes to remove any res-
idues that could affect proper boiler operation.

The gas must be connected to the relevant connection (see fig. 10) in conformity with the
current standards, with a rigid metal pipe or with a continuous flexible s/steel tube, install-
ing a gas cock between the system and boiler. Make sure all the gas connections are
tight.
The capacity of the gas meter must be sufficient for the simultaneous use of all equip-
ment connected to it. The diameter of the gas pipe leaving the boiler does not determine
the diameter of the pipe between the unit and the meter; it must be chosen according to
its length and pressure losses, in conformity with the current regulations.

B

Do not use the gas pipes to earth electrical appliances.

3.5 Electrical connections
Connection to the power supply

The boiler must be connected to a single-phase, 230 Volt-50 Hz electric line.

B

The unit's electrical safety is guaranteed only when it is correctly connected to
an efficient earthing system in conformity with the current safety regulations.
Have the efficiency and suitability of the earthing system checked by profes-
sionally qualified personnel; the Manufacturer declines any liability for damage
caused by failure to earth the system. Also make sure the electrical system is
adequate for the maximum power absorbed by the unit, as specified on the boil-
er dataplate, in particular ensuring that the section of the system's cables is
suitable for the input.

The boiler is prewired and supplied with a connector located inside the control panel, ar-
ranged for connection to an  electronic thermostatic controller (see wiring diagrams in
sec. 5.5). It is also equipped with a three-core cable for connection to the electric line.
The connections to the power supply must be made with a permanent connection and
equipped with a double-pole switch with contact gap of at least 3 mm, interposing fuses
of max. 3A between the boiler and line. It is important to respect the polarities (LINE:
brown wire / NEUTRAL: blue wire / EARTH : yellow/green wire) when making the con-
nections to the electric line.

Accessing the electrical terminal block and components inside the control panel

To access the electrical components inside the control panel, follow the sequence in
fig. 2. The layout of the terminals for the various connections is given in the wiring dia-
grams in the technical data section.

fig. 2 - Accessing the terminal block

Key

A

Undo the 2 self-tapping screws securing the boiler cover.

B

Lift by pressing upwards and remove the cover held to the sides of the boiler by
pins.

C

Undo and remove the two screws and the two plates holding the control panel.

D

Turn the control panel forwards.

Any additional sensitive elements of the system's control and safety devices, tempera-
ture probe, pressure switch, thermostat bulb, etc., must be located on the delivery pipe
within 40 cm of the boiler casing rear wall (see fig. 3).
Key

A

System delivery

B

System return

C

40 cm max.

fig. 3 - Delivery and return

3.6 Connection to the flue

The flue connection pipe diameter must not be less than that of the connection on the
anti-backflow device. Starting from the anti-backflow device it must have a vertical sec-
tion at least 50 cm long. Comply with the current regulations regarding installation and
sizes of the flues and connection pipe. The diameters of the anti-backflow device collars
are given in the table of fig. 10.

A

B

C

cod. 3540T624  -  Rev. 01 - 04/2018

Содержание PEGASUS F3 N 2S

Страница 1: ...E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INST...

Страница 2: ...la caldaia Chiudere o inserire l eventuale interruttore o spina a monte della caldaia Portare l interruttore di caldaia 7 sulla posizione 1 fig 1 Posizionare la manopola 6 sulla temperatura prescelta...

Страница 3: ...mento ad impianto freddo deve essere di circa 1 bar Qualora durante il fun zionamento la pressione dell impianto scendesse a causa dell evaporazione dei gas disciolti nell acqua a valori inferiori al...

Страница 4: ...lota inserendo gli ugelli indicati in tabella dati tecnici alla sez 5 3 2 Togliere dalla valvola gas il piccolo tappo 3 fig 4 avvitare sulla valvola il regolatore STEP di accensione 2 contenuto nel ki...

Страница 5: ...arla a questo valore Il vaso d espansione se presente deve essere carico La portata gas e la pressione devono corrispondere a quanto indicato nella tabella dati tecnici vedi sez 5 3 Le pompe di circol...

Страница 6: ...mente posizionati e senza incrostazioni vedere fig 8 Termostato di regolazione regolato troppo basso Controllare l alimentazione elettrica Controllare i collegamenti agli elettrodi d accensione e di i...

Страница 7: ...umi su camera fumi 11 Pressostato gas 12 Bruciatore pilota completo di elettrodi 13 Collettore gas 14 Presa di pressione 15 Rubinetto di scarico 16 Centralina elettronica di controllo fiamma 17 Valvol...

Страница 8: ...Hz 230 50 230 50 230 50 230 50 Indice di protezione elettrica IP X0D X0D X0D X0D MODELLO 187 221 255 289 Potenze Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Portata Termica Potere calori fico Inferiore H...

Страница 9: ...elettrici 24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elet...

Страница 10: ...24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elettronica di...

Страница 11: ...Garanzia La presente garanzia convenzionale valida per gli apparecchi Z d K d D E s Z E Z E Y d s FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933...

Страница 12: ...posici n 1 fig 1 Ajustar el mando 6 y el termostato de ambiente si est instalado a la temperatura deseada El quemador se enciende y la caldera comienza a funcionar autom tica mente controlada por los...

Страница 13: ...i sueltos en el agua por debajo del valor citado el usuario ha de restablecer el valor inicial Para un correcto funcionamiento de la caldera su presi n en caliente tiene que estar comprendida aproxima...

Страница 14: ...Quitar el tap n 3 fig 4 de la v lvula del gas enroscar en la v lvula el regulador STEP de encendido 2 incluido en el kit de transformaci n y colocar el tap n 3 en el regulador 3 Regular las presiones...

Страница 15: ...gan dentro de los valores indicados en la tabla de datos t cnicos v ase sec 5 3 Las bombas de circulaci n no est n bloqueadas Dispositivos de seguridad La caldera PEGASUS F3 N 2S cuenta con dispositiv...

Страница 16: ...y no tengan incrustaciones ver fig 8 Termostato de regulaci n ajustado en un valor demasiado bajo Controlar la alimentaci n el ctrica Controlar las conexiones a los electrodos de encendido y de ioniz...

Страница 17: ...de humos en c mara humos 11 Presostato del gas 12 Quemador piloto con electrodos 13 Colector de gas 14 Toma de presi n 15 Llave de descarga 16 Centralita electr nica de control de la llama 17 V lvula...

Страница 18: ...V Hz 230 50 230 50 230 50 230 50 ndice de protecci n el ctrica IP X0D X0D X0D X0D MODELO 187 221 255 289 Potencias Pm x Pm n Pm x Pm n Pm x Pm n Pm x Pm n Capacidad t rmica poder calo r fico inferior...

Страница 19: ...4 Electrodo de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83...

Страница 20: ...de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83 Centralita e...

Страница 21: ...A S L U F RROLI ESPA A S L U durante el per odo de garant a durante el per odo de garant a Si el montaje no respeta las instrucciones que se suministran en la m quina Si el montaje no respeta las inst...

Страница 22: ...c a n z Kombinin sivicini 7 1 konumuna getiriniz ek 1 D meyi 6 nceden se ilmi olan s cakl k de erine getiriniz ve ortam termostat n da istemi oldu unuz s cakl k de erine ayarlay n z Bu a amada br l r...

Страница 23: ...since e er sistem bas nc yukar da a klanmakta olan minimum bas n de erinin alt na d er se suda z nm olan gaz n buharla mas ndan kaynaklan r kullan c n n kombinin ilk de erlere geri ayarlamas gereklidi...

Страница 24: ...ve sez 5 3 b l m ndeki teknik veri tablosunda belirtildi i ekilde u lar tak n z 2 Ufak tapay 3 gaz valf ndan kart n z ek 4 d n t rme kitinde bulunmakta olan ate leme KADEME reg lat r n 2 valf zerine...

Страница 25: ...l d r e er de il ise bunu bu de ere ayarlay n z Genle me tank e er varsa doldurulmal d r Gaz ak ve bas n de eri teknik veriler tablosunda verilen de erlere denk gelmelidir bkz sez 5 3 Devir daim pompa...

Страница 26: ...ama termostat n n ayar ok d kt r Elektrik g c beslemesini kontrol ediniz Ate leme ve iyonizasyon elektrotlar n n ba lant lar n kontrol ediniz Elektronik alev kontrol r ndeki ba lant lar kontrol ediniz...

Страница 27: ...9 Duman odas ndaki duman k 11 Gaz presostat 12 Elektrotlu pilot br l r 13 Gaz kollekt r 14 Bas n noktas 15 Tahliye muslu u 16 Elektronik alev kontrol r 17 Gaz valf 18 2 Kademe operat r Tip ve model A...

Страница 28: ...Hz 230 50 230 50 230 50 230 50 Elektriksel koruma s n f IP X0D X0D X0D X0D MODEL 187 221 255 289 G Pmaks Pmin Pmaks Pmin Pmaks Pmin Pmaks Pmin Is tma G c D k Is tma De eri Hi kW 206 122 243 144 280 1...

Страница 29: ...rik emalar a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik k...

Страница 30: ...a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik kumanda mer...

Страница 31: ...ug ahead of the boiler Turn the boiler switch 7 to 1 fig 1 Turn the knob 6 to the required temperature and that of a possible room thermostat to the required temperature value The burner will light an...

Страница 32: ...issolved in the water to val ues below the minimum described above the user must bring it to the initial value For correct operation of the boiler when hot its pressure must be approx 1 5 2 bar 3 4 Ga...

Страница 33: ...r and pilot burner fitting the nozzles specified in the technical data table in sec 5 3 2 Remove the small cap 3 fig 4 from the gas valve screw the ignition STEP regu lator 2 contained in the conversi...

Страница 34: ...e filled The gas delivery and pressure must correspond to that given in the technical data table see sec 5 3 The circulating pumps must not be blocked Safety devices The boiler PEGASUS F3 N 2S is equi...

Страница 35: ...ctly positioned and free of deposits see fig 8 Control thermostat adjusted too low Check the power supply Check the connections to the ignition and ionisation electrodes Check the connections to the e...

Страница 36: ...t on fume chamber 11 Gas pressure switch 12 Pilot burner complete with electrodes 13 Gas manifold 14 Pressure point 15 Drain cock 16 Electronic flame controller 17 Gas valve 18 2nd stage operator Type...

Страница 37: ...30 50 230 50 230 50 230 50 Electrical protection rat ing IP X0D X0D X0D X0D MODEL 187 221 255 289 Powers Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Heating Capacity Net Heat Value Hi kW 206 122 243 144 2...

Страница 38: ...rams Key wiring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controlle...

Страница 39: ...iring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controller 98 Switc...

Страница 40: ...de la chaudi re Fermer ou ins rer l ventuel interrupteur ou fiche en amont de la chaudi re Mettre l interrupteur de la chaudi re 7 sur la position 1 fig 1 Positionner la manette 6 sur la temp rature...

Страница 41: ...and de remplir le circuit avec de l eau trait e Remplissage de la chaudi re et du circuit de l installation La pression de charge de l installation froid doit tre d environ 1 bar Si au cours du foncti...

Страница 42: ...ristiques techniques la page sez 5 3 2 Retirer le bouchon de la vanne de gaz 3 fig 4 visser sur la vanne le r gulateur STEP d allumage 2 contenu dans le kit de transformation et remettre le bouchon 3...

Страница 43: ...re d environ 1 bar si ce n est pas le cas ra mener la pression cette valeur Le vase d expansion si pr sent doit tre charg Le d bit et la pression de gaz doivent correspondre aux valeurs indiqu es dans...

Страница 44: ...t es voir fig 8 Thermostat de r glage r gl trop bas Contr ler l alimentation lectrique Contr ler les branchements lectriques aux lectrodes d allumage et d ionisation Contr ler les branchements lectriq...

Страница 45: ...de commande de flamme 9 Prise de fum es sur chambre de fum es 11 Pressostat de s curit gaz 12 Br leur pilote avec lectrodes 13 Collecteur de gaz 14 Prise de pression 15 Robinet de vidange 16 Contr le...

Страница 46: ...imentation fr quence V Hz 230 50 230 50 230 50 230 50 Indice de protection IP X0D X0D X0D X0D MOD LE 187 221 255 289 Puissances Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Puissance thermique Pou voir cal...

Страница 47: ...sch mas lectriques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectroniq...

Страница 48: ...triques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectronique de comman...

Страница 49: ...i i i i i 1 1 i 2 3 i i 4 5 6 i 7 0 1 TEST 2 3 i 7 1 1 1 i 6 i i i i i 1 1 A 5 15 i i i i A i 7 0 i i B i i i i 7 3 0 1 TEST i i i i i i i i 2 4 6 1 i i i i i i 30 90 i i 45 i 6 1 i i i i i 2 1 1 0 i...

Страница 50: ...i i i i i i i i i i i i i i i 1 i i i i i i i i i i i i i 1 5 2 3 4 B i i i i i i i i i i i i i 10 i i i i i i i i i i i i i i i i i i i i i i i B 3 5 i i i i 230 50 B i i i i i i i i i i i i i i sez...

Страница 51: ...30 i i i i i 2 3 i i i i G20 G25 G30 G31 i 1 sez 5 3 2 i i 3 4 i i STEP i 2 i i 3 3 sez 5 3 4 i 2 3 i 5 i i i i i i i STEP i 2 4 3 4 4 i i 1 2 STEP i i 3 4 5 6 1 i 7 O RING 8 9 i V Honeywell VR 4601...

Страница 52: ...i i i i i i i i i i i i 8 1 i sez 5 3 i i i i PEGASUS F3 N 2S i i i i i i i i 110 C i 10 C i i i i i 3 1 i i i i i i i 5 5 B i i i i i i i 6 1 i i 2 i i i i 3 i i i i 4 5 6 10 15 7 6 A i i i i i i i...

Страница 53: ...3 4 5 i 4 4 A i i i i i i i 3 3 4 mm 5 4 8 i i i i i i i i i i 8 i i i i i i i i i i i i i 8 i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i...

Страница 54: ...GASUS F3 N 119 2S 930 133 220 50 42 1050 2 2 1 PEGASUS F3 N 136 2S 1020 148 250 53 45 1050 2 2 1 PEGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 1 2 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1...

Страница 55: ...0 230 50 230 50 IP X0D X0D X0D X0D 187 221 255 289 i P P P P P P P P i Hi 206 122 243 144 280 166 317 188 i 187 112 221 133 255 153 289 173 P P P P P P P P i G31 1 x 0 40 1 x 0 40 1 x 0 40 1 x 0 40 i...

Страница 56: ...PEGASUS F3 N 2S 56 U 119 136 12 119 136 119 136 13 119 136 5 5 i 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 57: ...PEGASUS F3 N 2S 57 U 153 289 14 153 289 153 289 15 153 289 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 58: ...IRECTIVAS APLICABLES LA DECLARACI N DE CONFORMIDAD PUEDE SOLICITARSE AL FABRICANTE 7bARET7 R NLER7N Y R RL KTE OLAN Y NETMEL7KLER7N TEMEL GEREKL7L7KLER7NE UYGUN OLDU UNU BELGELEMEKTED7R UYGUNLUK B7LD7...

Страница 59: ...PEGASUS F3 N 2S 10 02 2015 01 3540T623 153 289 24 32 44 49 72 82 83 98 116 129 159 167 170 171 153 289 14 153 289 153 289 15 03 2015 01 354S125 3540T624 0 201 0...

Страница 60: ...PEGASUS F3 N 2S 9 02 2015 01 3540T623 5 5 119 136 24 32 44 49 72 82 83 98 116 129 159 167 170 171 119 136 12 119 136 119 136 13 03 2015 01 354S125 3540T624 0 201 0...

Страница 61: ...70 530 575 625 W 32 32 60 60 V Hz 230 50 230 50 230 50 230 50 IP X0D X0D X0D X0D 119 136 153 170 Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Hi kW 206 122 243 144 280 166 317 188 kW 187 112 221 133 255 15...

Страница 62: ...EGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 2 1 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1 2 1 PEGASUS F3 N 187 2S 1270 173 300 58 44 1050 2 2 1 2 1 PEGASUS F3 N 221 2S 1440 173 300 57 45...

Страница 63: ...PEGASUS F3 N 2S 6 02 2015 01 3540T623 8 1 2 3 4 5 6 7 8 9 5 5 9 1 2 3 4 5 4 4 8 8 50 C 03 2015 01 354S125 3540T624 04 2018 01...

Страница 64: ...PEGASUS F3 N 2S 5 02 2015 01 3540T623 15 4 4 0 1 TEST 3 7 5 0 1 7 0 1 7 3 4 8 1 5 3 PEGASUS F3 N 2S 110 C 10 C 1 3 5 5 6 1 2 3 4 5 6 10 15 7 6 7 A 7 B F E 7 C 7 D 7 03 2015 01 354S125 3540T624 0 201 0...

Страница 65: ...3 N 2S 5 3 4 1 2 11 14 3 4 4 1 4 B A 2 5 3 4 6 1 4 C B A 2 5 3 4 5 30 2 3 G30 G31 G20 G25 1 5 3 2 STEP 2 4 3 3 3 5 3 4 3 2 5 4 3 4 STEP 2 4 1 2 STEP 3 4 5 6 7 8 9 V Honeywell VR 4601 CB A B A B C 2 4...

Страница 66: ...PEGASUS F3 N 2S 3 02 2015 01 3540T623 3 1 3 2 3 3 3 flow stop 20 C 10 25 Fr 1 2 1 5 4 3 10 inox 5 3 230 Volt 50 Hz 5 5 3A 3 2 2 A B C D 40 3 A B 40 C 3 6 3 10 03 2015 01 354S125 3540T624 04 2018 01...

Страница 67: ...N 2S 2 02 2015 01 3540T623 1 2 1 2 FERROLI PEGASUS F3 N 2S PEGASUS F3 N 2S 2 2 1 1 2 3 4 5 6 7 1 0 3 2 1 1 7 6 1 1 5 15 0 7 0 1 TEST 3 7 4 2 1 6 90 30 45 1 6 1 0 1 2 5 2 1 1 5 03 2015 01 354S125 3540...

Страница 68: ...02 2015 01 3540T623 PEGASUS F3 N 2S 03 2015 01 354S125 3540T624 07 2018 01...

Отзывы: