4. SERVICE AND MAINTENANCE
4.1 Adjustments

All adjustment and conversion operations must be carried out by Qualified Personnel.
The manufacturer declines any liability for damage or injury caused by unqualified and
unauthorised people tampering with the unit.

Burner gas pressure adjustment

The boilers 

PEGASUS F3 N 2S

 are arranged to run on natural or liquefied gas. The pres-

sure setting and test are performed in the factory.
However, at first lighting, as there may be supply pressure variations, check and if nec-
essary adjust the pressure at the nozzles, respecting the values given in the technical
data table in sec. 5.3.
Pressure adjustment operations must be carried out with the boiler working, using the
pressure regulator on the 2-stage gas valves (see fig. 4)

Preliminary operations:

1.

Light the boiler and turn the control thermostat knob to minimum.

2.

Connect a pressure gauge to the pressure point on the gas manifold pipe of the
burner assembly (see part 14 of fig. 11).

3.

Remove the protection cap of the pressure regulator 4 of fig. 4.

Minimum power (1st stage) adjustment

1.

Turn the control thermostat knob slowly clockwise to the 1st click; the gas valve will
thus be supplied only on connections A and B (see fig. 4).

2.

Turn the screw 6 of fig. 4, checking that the pressure matches the values given in
the technical data table in sec. 5.3.

Maximum power (2nd stage) adjustment
1.

Turn the control thermostat knob to maximum; the gas valve will now be supplied
only on connections A, B and C (see fig. 4).

2.

Turn the screw 5 of fig. 4, checking that the pressure matches the values given in
the technical data table in sec. 5.3.

The adjustment operations must be performed uniformly on the pressure regulators of
all the valves.

B

The gas pressures measured at the burner gas manifold must be read at least
30 seconds after making the adjustments, i.e. when the flame has stabilised.

On completing the adjustment operations, turn the burner on and off 2 - 3 times with the
control thermostat and check that the pressure values are those just set; otherwise, it is
necessary to make another adjustment to bring the pressures to the correct values.

Gas conversion

The unit can work with Natural gas (G20-G25) or liquefied gas (G30-G31) and is factory-
set for use with one of the two gases, as clearly shown on the packing and dataplate.
Whenever the unit has to be used with a different gas, a conversion kit will be required,
proceeding as follows.
From natural to liquefied gas
1.

Replace the nozzles at the main burner and pilot burner, fitting the nozzles specified
in the technical data table in sec. 5.3.

2.

Remove the small cap 3 (fig. 4) from the gas valve, screw the ignition "STEP" regu-
lator 2 (contained in the conversion kit) onto the valve and refit the cap 3 on the reg-
ulator.

3.

Adjust the burner gas pressures for minimum and maximum power as described in
the previous section, setting the values given in the technical data table of section
sec. 5.3.

4.

Operations 2 and 3 must be performed on all the valves.

5.

Apply the sticker contained in the conversion kit, near the dataplate as proof of the
conversion.

From liquefied to natural gas
Carry out the same operations described above, making sure to remove the ignition
"STEP" regulator 2 of fig. 4 of the gas valve; the cap 3 of fig. 4 must be fitted directly on
the valve.

fig. 4 - Gas conversion

Key of main components

1

Pressure point upstream

2

Ignition "STEP" regulator for liquefied gas

3

Plug

4

Protection cap

5

Pressure adjustment screw for max. power

6

Pressure adjustment screw for min. power (1st stage)

7

O-ring

8

Decrease

9

Increase

V

Honeywell valve VR 4601 CB

Key of electrical connections

A + B =

Connections fed for min. power (1st stage)

A + B + C =

Connections fed for max. power (2nd stage)

4.2 Commissioning

B

Commissioning must be carried out by Qualified Personnel.

The following operations and checks must be carried out at first lighting, and after all
maintenance that involved disconnecting from the systems or work on safety devices or
parts of the boiler.

Before lighting the boiler

Open any shutoff valves between the boiler and the system.

Check the tightness of the gas system, proceeding with caution and using soapy wa-
ter to check for any leaks in connections.

Fill the water system and make sure all air contained in the boiler and the system
has been vented by opening the air valve on the boiler and any vent valves in the
system.

Make sure there are no water leaks in the system or boiler.

Make sure the electrical system is properly connected.

Make sure the unit is connected to an efficient earthing system.

Make sure the pressure and gas flow values are those required for heating.

Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler.

Boiler lighting

Open the gas cock ahead of the boiler.

Vent the air from the pipe ahead of the gas valve.

Turn on or insert any switch or plug ahead of the boiler.

Turn the boiler switch (pos. 7 - fig. 1) to position 1.

Turn the knob 6 (fig. 1) to a value above 50°C and that of the room thermostat (if
present) to the required temperature value. The burner will light and the boiler be-
gins to function automatically, controlled by its adjustment and safety devices.

8

9

5

4

6

V

cod. 3540T624  -  Rev. 01 - 04/2018

Содержание PEGASUS F3 N 2S

Страница 1: ...E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INST...

Страница 2: ...la caldaia Chiudere o inserire l eventuale interruttore o spina a monte della caldaia Portare l interruttore di caldaia 7 sulla posizione 1 fig 1 Posizionare la manopola 6 sulla temperatura prescelta...

Страница 3: ...mento ad impianto freddo deve essere di circa 1 bar Qualora durante il fun zionamento la pressione dell impianto scendesse a causa dell evaporazione dei gas disciolti nell acqua a valori inferiori al...

Страница 4: ...lota inserendo gli ugelli indicati in tabella dati tecnici alla sez 5 3 2 Togliere dalla valvola gas il piccolo tappo 3 fig 4 avvitare sulla valvola il regolatore STEP di accensione 2 contenuto nel ki...

Страница 5: ...arla a questo valore Il vaso d espansione se presente deve essere carico La portata gas e la pressione devono corrispondere a quanto indicato nella tabella dati tecnici vedi sez 5 3 Le pompe di circol...

Страница 6: ...mente posizionati e senza incrostazioni vedere fig 8 Termostato di regolazione regolato troppo basso Controllare l alimentazione elettrica Controllare i collegamenti agli elettrodi d accensione e di i...

Страница 7: ...umi su camera fumi 11 Pressostato gas 12 Bruciatore pilota completo di elettrodi 13 Collettore gas 14 Presa di pressione 15 Rubinetto di scarico 16 Centralina elettronica di controllo fiamma 17 Valvol...

Страница 8: ...Hz 230 50 230 50 230 50 230 50 Indice di protezione elettrica IP X0D X0D X0D X0D MODELLO 187 221 255 289 Potenze Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Portata Termica Potere calori fico Inferiore H...

Страница 9: ...elettrici 24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elet...

Страница 10: ...24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elettronica di...

Страница 11: ...Garanzia La presente garanzia convenzionale valida per gli apparecchi Z d K d D E s Z E Z E Y d s FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933...

Страница 12: ...posici n 1 fig 1 Ajustar el mando 6 y el termostato de ambiente si est instalado a la temperatura deseada El quemador se enciende y la caldera comienza a funcionar autom tica mente controlada por los...

Страница 13: ...i sueltos en el agua por debajo del valor citado el usuario ha de restablecer el valor inicial Para un correcto funcionamiento de la caldera su presi n en caliente tiene que estar comprendida aproxima...

Страница 14: ...Quitar el tap n 3 fig 4 de la v lvula del gas enroscar en la v lvula el regulador STEP de encendido 2 incluido en el kit de transformaci n y colocar el tap n 3 en el regulador 3 Regular las presiones...

Страница 15: ...gan dentro de los valores indicados en la tabla de datos t cnicos v ase sec 5 3 Las bombas de circulaci n no est n bloqueadas Dispositivos de seguridad La caldera PEGASUS F3 N 2S cuenta con dispositiv...

Страница 16: ...y no tengan incrustaciones ver fig 8 Termostato de regulaci n ajustado en un valor demasiado bajo Controlar la alimentaci n el ctrica Controlar las conexiones a los electrodos de encendido y de ioniz...

Страница 17: ...de humos en c mara humos 11 Presostato del gas 12 Quemador piloto con electrodos 13 Colector de gas 14 Toma de presi n 15 Llave de descarga 16 Centralita electr nica de control de la llama 17 V lvula...

Страница 18: ...V Hz 230 50 230 50 230 50 230 50 ndice de protecci n el ctrica IP X0D X0D X0D X0D MODELO 187 221 255 289 Potencias Pm x Pm n Pm x Pm n Pm x Pm n Pm x Pm n Capacidad t rmica poder calo r fico inferior...

Страница 19: ...4 Electrodo de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83...

Страница 20: ...de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83 Centralita e...

Страница 21: ...A S L U F RROLI ESPA A S L U durante el per odo de garant a durante el per odo de garant a Si el montaje no respeta las instrucciones que se suministran en la m quina Si el montaje no respeta las inst...

Страница 22: ...c a n z Kombinin sivicini 7 1 konumuna getiriniz ek 1 D meyi 6 nceden se ilmi olan s cakl k de erine getiriniz ve ortam termostat n da istemi oldu unuz s cakl k de erine ayarlay n z Bu a amada br l r...

Страница 23: ...since e er sistem bas nc yukar da a klanmakta olan minimum bas n de erinin alt na d er se suda z nm olan gaz n buharla mas ndan kaynaklan r kullan c n n kombinin ilk de erlere geri ayarlamas gereklidi...

Страница 24: ...ve sez 5 3 b l m ndeki teknik veri tablosunda belirtildi i ekilde u lar tak n z 2 Ufak tapay 3 gaz valf ndan kart n z ek 4 d n t rme kitinde bulunmakta olan ate leme KADEME reg lat r n 2 valf zerine...

Страница 25: ...l d r e er de il ise bunu bu de ere ayarlay n z Genle me tank e er varsa doldurulmal d r Gaz ak ve bas n de eri teknik veriler tablosunda verilen de erlere denk gelmelidir bkz sez 5 3 Devir daim pompa...

Страница 26: ...ama termostat n n ayar ok d kt r Elektrik g c beslemesini kontrol ediniz Ate leme ve iyonizasyon elektrotlar n n ba lant lar n kontrol ediniz Elektronik alev kontrol r ndeki ba lant lar kontrol ediniz...

Страница 27: ...9 Duman odas ndaki duman k 11 Gaz presostat 12 Elektrotlu pilot br l r 13 Gaz kollekt r 14 Bas n noktas 15 Tahliye muslu u 16 Elektronik alev kontrol r 17 Gaz valf 18 2 Kademe operat r Tip ve model A...

Страница 28: ...Hz 230 50 230 50 230 50 230 50 Elektriksel koruma s n f IP X0D X0D X0D X0D MODEL 187 221 255 289 G Pmaks Pmin Pmaks Pmin Pmaks Pmin Pmaks Pmin Is tma G c D k Is tma De eri Hi kW 206 122 243 144 280 1...

Страница 29: ...rik emalar a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik k...

Страница 30: ...a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik kumanda mer...

Страница 31: ...ug ahead of the boiler Turn the boiler switch 7 to 1 fig 1 Turn the knob 6 to the required temperature and that of a possible room thermostat to the required temperature value The burner will light an...

Страница 32: ...issolved in the water to val ues below the minimum described above the user must bring it to the initial value For correct operation of the boiler when hot its pressure must be approx 1 5 2 bar 3 4 Ga...

Страница 33: ...r and pilot burner fitting the nozzles specified in the technical data table in sec 5 3 2 Remove the small cap 3 fig 4 from the gas valve screw the ignition STEP regu lator 2 contained in the conversi...

Страница 34: ...e filled The gas delivery and pressure must correspond to that given in the technical data table see sec 5 3 The circulating pumps must not be blocked Safety devices The boiler PEGASUS F3 N 2S is equi...

Страница 35: ...ctly positioned and free of deposits see fig 8 Control thermostat adjusted too low Check the power supply Check the connections to the ignition and ionisation electrodes Check the connections to the e...

Страница 36: ...t on fume chamber 11 Gas pressure switch 12 Pilot burner complete with electrodes 13 Gas manifold 14 Pressure point 15 Drain cock 16 Electronic flame controller 17 Gas valve 18 2nd stage operator Type...

Страница 37: ...30 50 230 50 230 50 230 50 Electrical protection rat ing IP X0D X0D X0D X0D MODEL 187 221 255 289 Powers Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Heating Capacity Net Heat Value Hi kW 206 122 243 144 2...

Страница 38: ...rams Key wiring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controlle...

Страница 39: ...iring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controller 98 Switc...

Страница 40: ...de la chaudi re Fermer ou ins rer l ventuel interrupteur ou fiche en amont de la chaudi re Mettre l interrupteur de la chaudi re 7 sur la position 1 fig 1 Positionner la manette 6 sur la temp rature...

Страница 41: ...and de remplir le circuit avec de l eau trait e Remplissage de la chaudi re et du circuit de l installation La pression de charge de l installation froid doit tre d environ 1 bar Si au cours du foncti...

Страница 42: ...ristiques techniques la page sez 5 3 2 Retirer le bouchon de la vanne de gaz 3 fig 4 visser sur la vanne le r gulateur STEP d allumage 2 contenu dans le kit de transformation et remettre le bouchon 3...

Страница 43: ...re d environ 1 bar si ce n est pas le cas ra mener la pression cette valeur Le vase d expansion si pr sent doit tre charg Le d bit et la pression de gaz doivent correspondre aux valeurs indiqu es dans...

Страница 44: ...t es voir fig 8 Thermostat de r glage r gl trop bas Contr ler l alimentation lectrique Contr ler les branchements lectriques aux lectrodes d allumage et d ionisation Contr ler les branchements lectriq...

Страница 45: ...de commande de flamme 9 Prise de fum es sur chambre de fum es 11 Pressostat de s curit gaz 12 Br leur pilote avec lectrodes 13 Collecteur de gaz 14 Prise de pression 15 Robinet de vidange 16 Contr le...

Страница 46: ...imentation fr quence V Hz 230 50 230 50 230 50 230 50 Indice de protection IP X0D X0D X0D X0D MOD LE 187 221 255 289 Puissances Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Puissance thermique Pou voir cal...

Страница 47: ...sch mas lectriques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectroniq...

Страница 48: ...triques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectronique de comman...

Страница 49: ...i i i i i 1 1 i 2 3 i i 4 5 6 i 7 0 1 TEST 2 3 i 7 1 1 1 i 6 i i i i i 1 1 A 5 15 i i i i A i 7 0 i i B i i i i 7 3 0 1 TEST i i i i i i i i 2 4 6 1 i i i i i i 30 90 i i 45 i 6 1 i i i i i 2 1 1 0 i...

Страница 50: ...i i i i i i i i i i i i i i i 1 i i i i i i i i i i i i i 1 5 2 3 4 B i i i i i i i i i i i i i 10 i i i i i i i i i i i i i i i i i i i i i i i B 3 5 i i i i 230 50 B i i i i i i i i i i i i i i sez...

Страница 51: ...30 i i i i i 2 3 i i i i G20 G25 G30 G31 i 1 sez 5 3 2 i i 3 4 i i STEP i 2 i i 3 3 sez 5 3 4 i 2 3 i 5 i i i i i i i STEP i 2 4 3 4 4 i i 1 2 STEP i i 3 4 5 6 1 i 7 O RING 8 9 i V Honeywell VR 4601...

Страница 52: ...i i i i i i i i i i i i 8 1 i sez 5 3 i i i i PEGASUS F3 N 2S i i i i i i i i 110 C i 10 C i i i i i 3 1 i i i i i i i 5 5 B i i i i i i i 6 1 i i 2 i i i i 3 i i i i 4 5 6 10 15 7 6 A i i i i i i i...

Страница 53: ...3 4 5 i 4 4 A i i i i i i i 3 3 4 mm 5 4 8 i i i i i i i i i i 8 i i i i i i i i i i i i i 8 i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i...

Страница 54: ...GASUS F3 N 119 2S 930 133 220 50 42 1050 2 2 1 PEGASUS F3 N 136 2S 1020 148 250 53 45 1050 2 2 1 PEGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 1 2 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1...

Страница 55: ...0 230 50 230 50 IP X0D X0D X0D X0D 187 221 255 289 i P P P P P P P P i Hi 206 122 243 144 280 166 317 188 i 187 112 221 133 255 153 289 173 P P P P P P P P i G31 1 x 0 40 1 x 0 40 1 x 0 40 1 x 0 40 i...

Страница 56: ...PEGASUS F3 N 2S 56 U 119 136 12 119 136 119 136 13 119 136 5 5 i 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 57: ...PEGASUS F3 N 2S 57 U 153 289 14 153 289 153 289 15 153 289 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 58: ...IRECTIVAS APLICABLES LA DECLARACI N DE CONFORMIDAD PUEDE SOLICITARSE AL FABRICANTE 7bARET7 R NLER7N Y R RL KTE OLAN Y NETMEL7KLER7N TEMEL GEREKL7L7KLER7NE UYGUN OLDU UNU BELGELEMEKTED7R UYGUNLUK B7LD7...

Страница 59: ...PEGASUS F3 N 2S 10 02 2015 01 3540T623 153 289 24 32 44 49 72 82 83 98 116 129 159 167 170 171 153 289 14 153 289 153 289 15 03 2015 01 354S125 3540T624 0 201 0...

Страница 60: ...PEGASUS F3 N 2S 9 02 2015 01 3540T623 5 5 119 136 24 32 44 49 72 82 83 98 116 129 159 167 170 171 119 136 12 119 136 119 136 13 03 2015 01 354S125 3540T624 0 201 0...

Страница 61: ...70 530 575 625 W 32 32 60 60 V Hz 230 50 230 50 230 50 230 50 IP X0D X0D X0D X0D 119 136 153 170 Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Hi kW 206 122 243 144 280 166 317 188 kW 187 112 221 133 255 15...

Страница 62: ...EGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 2 1 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1 2 1 PEGASUS F3 N 187 2S 1270 173 300 58 44 1050 2 2 1 2 1 PEGASUS F3 N 221 2S 1440 173 300 57 45...

Страница 63: ...PEGASUS F3 N 2S 6 02 2015 01 3540T623 8 1 2 3 4 5 6 7 8 9 5 5 9 1 2 3 4 5 4 4 8 8 50 C 03 2015 01 354S125 3540T624 04 2018 01...

Страница 64: ...PEGASUS F3 N 2S 5 02 2015 01 3540T623 15 4 4 0 1 TEST 3 7 5 0 1 7 0 1 7 3 4 8 1 5 3 PEGASUS F3 N 2S 110 C 10 C 1 3 5 5 6 1 2 3 4 5 6 10 15 7 6 7 A 7 B F E 7 C 7 D 7 03 2015 01 354S125 3540T624 0 201 0...

Страница 65: ...3 N 2S 5 3 4 1 2 11 14 3 4 4 1 4 B A 2 5 3 4 6 1 4 C B A 2 5 3 4 5 30 2 3 G30 G31 G20 G25 1 5 3 2 STEP 2 4 3 3 3 5 3 4 3 2 5 4 3 4 STEP 2 4 1 2 STEP 3 4 5 6 7 8 9 V Honeywell VR 4601 CB A B A B C 2 4...

Страница 66: ...PEGASUS F3 N 2S 3 02 2015 01 3540T623 3 1 3 2 3 3 3 flow stop 20 C 10 25 Fr 1 2 1 5 4 3 10 inox 5 3 230 Volt 50 Hz 5 5 3A 3 2 2 A B C D 40 3 A B 40 C 3 6 3 10 03 2015 01 354S125 3540T624 04 2018 01...

Страница 67: ...N 2S 2 02 2015 01 3540T623 1 2 1 2 FERROLI PEGASUS F3 N 2S PEGASUS F3 N 2S 2 2 1 1 2 3 4 5 6 7 1 0 3 2 1 1 7 6 1 1 5 15 0 7 0 1 TEST 3 7 4 2 1 6 90 30 45 1 6 1 0 1 2 5 2 1 1 5 03 2015 01 354S125 3540...

Страница 68: ...02 2015 01 3540T623 PEGASUS F3 N 2S 03 2015 01 354S125 3540T624 07 2018 01...

Отзывы: