PEGASUS F3 N 2S

34

EN

B

If, after correctly carrying out the lighting procedure, the burners do not light and
the button-indicator comes on, wait about 15 seconds then press the above-
mentioned button. The reset controller will repeat the lighting cycle. If the burn-
ers do not light after the second attempt, refer to the section sec. 4.4.
The boiler switch 7 has 3 positions “0-1-TEST”; the first two have the on-off
function, the third (unstable) must only be used for service and maintenance
purposes.

A

In case of a power failure while the boiler is working, the burners will go out and
relight automatically when the power is restored.

Checks during operation

Make sure the fuel circuit and water systems are tight.

Check the efficiency of the flue and fume ducts while the boiler is working.

Make sure the water is circulating properly between the boiler and the system.

Check correct lighting of the boiler, by turning it on and off several times using the
room thermostat or boiler thermostat.

Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.

Turning off

To temporarily turn the boiler off, just turn the boiler switch 7 (fig. 1) to 0.
To turn the boiler off for a prolonged period:

Turn the knob of the boiler switch 7 (fig. 1) to 0;

Close the gas cock ahead of the boiler;

Disconnect the power to the unit;

B

To avoid damage caused by freezing during long shutdowns in winter, it is ad-
visable to drain all water from the boiler and the system; or add a suitable anti-
freeze to the heating system

4.3 Maintenance

B

THE FOLLOWING OPERATIONS MUST ONLY BE CARRIED OUT BY
QUALIFIED PERSONNEL.

Seasonal inspection of the boiler and flue

It is advisable to carry out the following checks at least once a year:

The control and safety devices (gas valve, thermostats, etc.) must function correctly.

The fume ducts must be free of obstructions and leaks.

The gas and water systems must be tight.

The burner and boiler shell must be clean. Follow the instructions in the next section.

The electrodes must be free of deposits and properly positioned (see fig. 8).

The water pressure in the system when cold must be approx. 1 bar; otherwise bring
it to that value.

The expansion tank, if present, must be filled.

The gas delivery and pressure must correspond to that given in the technical data
table (see sec. 5.3).

The circulating pumps must not be blocked.

Safety devices

The boiler 

PEGASUS F3 N 2S

 is equipped with devices that guarantee safety in case of

operation faults.
Temperature limiter (safety thermostat) with manual reset
This device prevents the water temperature in the system from exceeding boiling point.
The maximum cut-in temperature is 110°C.
Automatic reset of the temperature limiter can only occur on cooling of the boiler (the
temperature must drop by at least 10°C) and identification and elimination of the problem
that caused the shutdown. To reset the temperature limiter, unscrew the cover 3 of fig. 1
and press the button below.

Opening the front casing

To open the boiler front panel, see the sequence in fig. 5.

fig. 5 - Front panel opening

B

Before carrying out any operation inside the boiler, disconnect the power and
close the gas cock upstream.

Combustion analysis

A fume sampling point has been included in the upper part of the anti-backflow device
inside the boiler (see fig. 6).
To take the sample:
1.

Remove the top panel of the boiler

2.

Remove the insulation covering the anti-backflow device

3.

Open the fume sampling point;

4.

Insert the probe;

5.

Adjust the boiler temperature to maximum.

6.

Wait 10-15 minutes for the boiler to stabilise*

7.

Take the measurement.

fig. 6 - Combustion analysis

A

Analyses made with a non-stabilised boiler can cause measurement errors.

Burner assembly removal and cleaning

To remove the burner assembly:

Disconnect the power and turn off the gas ahead of the boiler.

Undo the two screws securing the electronic flame controller (detail 

B

 - fig. 7) to the gas valve (de-

tail 

A

 - fig. 7) and remove the controller.

Undo the screws fixing the connectors (

F

) to the gas valves and remove the connectors.

Disconnect the ignition and ionisation cables (

E

) from the electrode assembly.

Undo the nuts fixing the gas supply pipe ahead of the gas valves (detail 

C

 - fig. 7).

Undo the two nuts fixing the combustion chamber door to the cast iron elements of the boiler (detail

D

 - fig. 7).

Remove the burner assembly and combustion chamber door.

Then check and clean the burners. Only use a non-metallic brush or compressed air to clean the burners
and electrodes; never use chemical products.
Afterwards, refit everything in reverse order.

fig. 7 - Burner removal and cleaning

1

2

D

D

C

C

A

B

E

F

cod. 3540T624  -  Rev. 01 - 04/2018

Содержание PEGASUS F3 N 2S

Страница 1: ...E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INST...

Страница 2: ...la caldaia Chiudere o inserire l eventuale interruttore o spina a monte della caldaia Portare l interruttore di caldaia 7 sulla posizione 1 fig 1 Posizionare la manopola 6 sulla temperatura prescelta...

Страница 3: ...mento ad impianto freddo deve essere di circa 1 bar Qualora durante il fun zionamento la pressione dell impianto scendesse a causa dell evaporazione dei gas disciolti nell acqua a valori inferiori al...

Страница 4: ...lota inserendo gli ugelli indicati in tabella dati tecnici alla sez 5 3 2 Togliere dalla valvola gas il piccolo tappo 3 fig 4 avvitare sulla valvola il regolatore STEP di accensione 2 contenuto nel ki...

Страница 5: ...arla a questo valore Il vaso d espansione se presente deve essere carico La portata gas e la pressione devono corrispondere a quanto indicato nella tabella dati tecnici vedi sez 5 3 Le pompe di circol...

Страница 6: ...mente posizionati e senza incrostazioni vedere fig 8 Termostato di regolazione regolato troppo basso Controllare l alimentazione elettrica Controllare i collegamenti agli elettrodi d accensione e di i...

Страница 7: ...umi su camera fumi 11 Pressostato gas 12 Bruciatore pilota completo di elettrodi 13 Collettore gas 14 Presa di pressione 15 Rubinetto di scarico 16 Centralina elettronica di controllo fiamma 17 Valvol...

Страница 8: ...Hz 230 50 230 50 230 50 230 50 Indice di protezione elettrica IP X0D X0D X0D X0D MODELLO 187 221 255 289 Potenze Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Portata Termica Potere calori fico Inferiore H...

Страница 9: ...elettrici 24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elet...

Страница 10: ...24 Elettrodo d accensione 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83 Centralina elettronica di...

Страница 11: ...Garanzia La presente garanzia convenzionale valida per gli apparecchi Z d K d D E s Z E Z E Y d s FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933...

Страница 12: ...posici n 1 fig 1 Ajustar el mando 6 y el termostato de ambiente si est instalado a la temperatura deseada El quemador se enciende y la caldera comienza a funcionar autom tica mente controlada por los...

Страница 13: ...i sueltos en el agua por debajo del valor citado el usuario ha de restablecer el valor inicial Para un correcto funcionamiento de la caldera su presi n en caliente tiene que estar comprendida aproxima...

Страница 14: ...Quitar el tap n 3 fig 4 de la v lvula del gas enroscar en la v lvula el regulador STEP de encendido 2 incluido en el kit de transformaci n y colocar el tap n 3 en el regulador 3 Regular las presiones...

Страница 15: ...gan dentro de los valores indicados en la tabla de datos t cnicos v ase sec 5 3 Las bombas de circulaci n no est n bloqueadas Dispositivos de seguridad La caldera PEGASUS F3 N 2S cuenta con dispositiv...

Страница 16: ...y no tengan incrustaciones ver fig 8 Termostato de regulaci n ajustado en un valor demasiado bajo Controlar la alimentaci n el ctrica Controlar las conexiones a los electrodos de encendido y de ioniz...

Страница 17: ...de humos en c mara humos 11 Presostato del gas 12 Quemador piloto con electrodos 13 Colector de gas 14 Toma de presi n 15 Llave de descarga 16 Centralita electr nica de control de la llama 17 V lvula...

Страница 18: ...V Hz 230 50 230 50 230 50 230 50 ndice de protecci n el ctrica IP X0D X0D X0D X0D MODELO 187 221 255 289 Potencias Pm x Pm n Pm x Pm n Pm x Pm n Pm x Pm n Capacidad t rmica poder calo r fico inferior...

Страница 19: ...4 Electrodo de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83...

Страница 20: ...de encendido 32 Bomba de circulaci n de la calefacci n no suministrada 44 V lvula del gas 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83 Centralita e...

Страница 21: ...A S L U F RROLI ESPA A S L U durante el per odo de garant a durante el per odo de garant a Si el montaje no respeta las instrucciones que se suministran en la m quina Si el montaje no respeta las inst...

Страница 22: ...c a n z Kombinin sivicini 7 1 konumuna getiriniz ek 1 D meyi 6 nceden se ilmi olan s cakl k de erine getiriniz ve ortam termostat n da istemi oldu unuz s cakl k de erine ayarlay n z Bu a amada br l r...

Страница 23: ...since e er sistem bas nc yukar da a klanmakta olan minimum bas n de erinin alt na d er se suda z nm olan gaz n buharla mas ndan kaynaklan r kullan c n n kombinin ilk de erlere geri ayarlamas gereklidi...

Страница 24: ...ve sez 5 3 b l m ndeki teknik veri tablosunda belirtildi i ekilde u lar tak n z 2 Ufak tapay 3 gaz valf ndan kart n z ek 4 d n t rme kitinde bulunmakta olan ate leme KADEME reg lat r n 2 valf zerine...

Страница 25: ...l d r e er de il ise bunu bu de ere ayarlay n z Genle me tank e er varsa doldurulmal d r Gaz ak ve bas n de eri teknik veriler tablosunda verilen de erlere denk gelmelidir bkz sez 5 3 Devir daim pompa...

Страница 26: ...ama termostat n n ayar ok d kt r Elektrik g c beslemesini kontrol ediniz Ate leme ve iyonizasyon elektrotlar n n ba lant lar n kontrol ediniz Elektronik alev kontrol r ndeki ba lant lar kontrol ediniz...

Страница 27: ...9 Duman odas ndaki duman k 11 Gaz presostat 12 Elektrotlu pilot br l r 13 Gaz kollekt r 14 Bas n noktas 15 Tahliye muslu u 16 Elektronik alev kontrol r 17 Gaz valf 18 2 Kademe operat r Tip ve model A...

Страница 28: ...Hz 230 50 230 50 230 50 230 50 Elektriksel koruma s n f IP X0D X0D X0D X0D MODEL 187 221 255 289 G Pmaks Pmin Pmaks Pmin Pmaks Pmin Pmaks Pmin Is tma G c D k Is tma De eri Hi kW 206 122 243 144 280 1...

Страница 29: ...rik emalar a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik k...

Страница 30: ...a klamalar 24 Ate leme elektrotu 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83 Elektronik kumanda mer...

Страница 31: ...ug ahead of the boiler Turn the boiler switch 7 to 1 fig 1 Turn the knob 6 to the required temperature and that of a possible room thermostat to the required temperature value The burner will light an...

Страница 32: ...issolved in the water to val ues below the minimum described above the user must bring it to the initial value For correct operation of the boiler when hot its pressure must be approx 1 5 2 bar 3 4 Ga...

Страница 33: ...r and pilot burner fitting the nozzles specified in the technical data table in sec 5 3 2 Remove the small cap 3 fig 4 from the gas valve screw the ignition STEP regu lator 2 contained in the conversi...

Страница 34: ...e filled The gas delivery and pressure must correspond to that given in the technical data table see sec 5 3 The circulating pumps must not be blocked Safety devices The boiler PEGASUS F3 N 2S is equi...

Страница 35: ...ctly positioned and free of deposits see fig 8 Control thermostat adjusted too low Check the power supply Check the connections to the ignition and ionisation electrodes Check the connections to the e...

Страница 36: ...t on fume chamber 11 Gas pressure switch 12 Pilot burner complete with electrodes 13 Gas manifold 14 Pressure point 15 Drain cock 16 Electronic flame controller 17 Gas valve 18 2nd stage operator Type...

Страница 37: ...30 50 230 50 230 50 230 50 Electrical protection rat ing IP X0D X0D X0D X0D MODEL 187 221 255 289 Powers Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Heating Capacity Net Heat Value Hi kW 206 122 243 144 2...

Страница 38: ...rams Key wiring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controlle...

Страница 39: ...iring diagrams 24 Ignition electrode 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83 Electronic controller 98 Switc...

Страница 40: ...de la chaudi re Fermer ou ins rer l ventuel interrupteur ou fiche en amont de la chaudi re Mettre l interrupteur de la chaudi re 7 sur la position 1 fig 1 Positionner la manette 6 sur la temp rature...

Страница 41: ...and de remplir le circuit avec de l eau trait e Remplissage de la chaudi re et du circuit de l installation La pression de charge de l installation froid doit tre d environ 1 bar Si au cours du foncti...

Страница 42: ...ristiques techniques la page sez 5 3 2 Retirer le bouchon de la vanne de gaz 3 fig 4 visser sur la vanne le r gulateur STEP d allumage 2 contenu dans le kit de transformation et remettre le bouchon 3...

Страница 43: ...re d environ 1 bar si ce n est pas le cas ra mener la pression cette valeur Le vase d expansion si pr sent doit tre charg Le d bit et la pression de gaz doivent correspondre aux valeurs indiqu es dans...

Страница 44: ...t es voir fig 8 Thermostat de r glage r gl trop bas Contr ler l alimentation lectrique Contr ler les branchements lectriques aux lectrodes d allumage et d ionisation Contr ler les branchements lectriq...

Страница 45: ...de commande de flamme 9 Prise de fum es sur chambre de fum es 11 Pressostat de s curit gaz 12 Br leur pilote avec lectrodes 13 Collecteur de gaz 14 Prise de pression 15 Robinet de vidange 16 Contr le...

Страница 46: ...imentation fr quence V Hz 230 50 230 50 230 50 230 50 Indice de protection IP X0D X0D X0D X0D MOD LE 187 221 255 289 Puissances Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Puissance thermique Pou voir cal...

Страница 47: ...sch mas lectriques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectroniq...

Страница 48: ...triques 24 lectrode d allumage 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83 Module lectronique de comman...

Страница 49: ...i i i i i 1 1 i 2 3 i i 4 5 6 i 7 0 1 TEST 2 3 i 7 1 1 1 i 6 i i i i i 1 1 A 5 15 i i i i A i 7 0 i i B i i i i 7 3 0 1 TEST i i i i i i i i 2 4 6 1 i i i i i i 30 90 i i 45 i 6 1 i i i i i 2 1 1 0 i...

Страница 50: ...i i i i i i i i i i i i i i i 1 i i i i i i i i i i i i i 1 5 2 3 4 B i i i i i i i i i i i i i 10 i i i i i i i i i i i i i i i i i i i i i i i B 3 5 i i i i 230 50 B i i i i i i i i i i i i i i sez...

Страница 51: ...30 i i i i i 2 3 i i i i G20 G25 G30 G31 i 1 sez 5 3 2 i i 3 4 i i STEP i 2 i i 3 3 sez 5 3 4 i 2 3 i 5 i i i i i i i STEP i 2 4 3 4 4 i i 1 2 STEP i i 3 4 5 6 1 i 7 O RING 8 9 i V Honeywell VR 4601...

Страница 52: ...i i i i i i i i i i i i 8 1 i sez 5 3 i i i i PEGASUS F3 N 2S i i i i i i i i 110 C i 10 C i i i i i 3 1 i i i i i i i 5 5 B i i i i i i i 6 1 i i 2 i i i i 3 i i i i 4 5 6 10 15 7 6 A i i i i i i i...

Страница 53: ...3 4 5 i 4 4 A i i i i i i i 3 3 4 mm 5 4 8 i i i i i i i i i i 8 i i i i i i i i i i i i i 8 i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i...

Страница 54: ...GASUS F3 N 119 2S 930 133 220 50 42 1050 2 2 1 PEGASUS F3 N 136 2S 1020 148 250 53 45 1050 2 2 1 PEGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 1 2 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1...

Страница 55: ...0 230 50 230 50 IP X0D X0D X0D X0D 187 221 255 289 i P P P P P P P P i Hi 206 122 243 144 280 166 317 188 i 187 112 221 133 255 153 289 173 P P P P P P P P i G31 1 x 0 40 1 x 0 40 1 x 0 40 1 x 0 40 i...

Страница 56: ...PEGASUS F3 N 2S 56 U 119 136 12 119 136 119 136 13 119 136 5 5 i 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 57: ...PEGASUS F3 N 2S 57 U 153 289 14 153 289 153 289 15 153 289 24 32 i 44 49 72 i 82 83 98 116 129 159 167 2 170 1 171 2 cod 3540T624 Rev 01 04 2018...

Страница 58: ...IRECTIVAS APLICABLES LA DECLARACI N DE CONFORMIDAD PUEDE SOLICITARSE AL FABRICANTE 7bARET7 R NLER7N Y R RL KTE OLAN Y NETMEL7KLER7N TEMEL GEREKL7L7KLER7NE UYGUN OLDU UNU BELGELEMEKTED7R UYGUNLUK B7LD7...

Страница 59: ...PEGASUS F3 N 2S 10 02 2015 01 3540T623 153 289 24 32 44 49 72 82 83 98 116 129 159 167 170 171 153 289 14 153 289 153 289 15 03 2015 01 354S125 3540T624 0 201 0...

Страница 60: ...PEGASUS F3 N 2S 9 02 2015 01 3540T623 5 5 119 136 24 32 44 49 72 82 83 98 116 129 159 167 170 171 119 136 12 119 136 119 136 13 03 2015 01 354S125 3540T624 0 201 0...

Страница 61: ...70 530 575 625 W 32 32 60 60 V Hz 230 50 230 50 230 50 230 50 IP X0D X0D X0D X0D 119 136 153 170 Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Hi kW 206 122 243 144 280 166 317 188 kW 187 112 221 133 255 15...

Страница 62: ...EGASUS F3 N 153 2S 1100 148 250 58 43 1050 2 2 1 2 1 PEGASUS F3 N 170 2S 1190 173 300 60 46 1050 2 2 1 2 1 PEGASUS F3 N 187 2S 1270 173 300 58 44 1050 2 2 1 2 1 PEGASUS F3 N 221 2S 1440 173 300 57 45...

Страница 63: ...PEGASUS F3 N 2S 6 02 2015 01 3540T623 8 1 2 3 4 5 6 7 8 9 5 5 9 1 2 3 4 5 4 4 8 8 50 C 03 2015 01 354S125 3540T624 04 2018 01...

Страница 64: ...PEGASUS F3 N 2S 5 02 2015 01 3540T623 15 4 4 0 1 TEST 3 7 5 0 1 7 0 1 7 3 4 8 1 5 3 PEGASUS F3 N 2S 110 C 10 C 1 3 5 5 6 1 2 3 4 5 6 10 15 7 6 7 A 7 B F E 7 C 7 D 7 03 2015 01 354S125 3540T624 0 201 0...

Страница 65: ...3 N 2S 5 3 4 1 2 11 14 3 4 4 1 4 B A 2 5 3 4 6 1 4 C B A 2 5 3 4 5 30 2 3 G30 G31 G20 G25 1 5 3 2 STEP 2 4 3 3 3 5 3 4 3 2 5 4 3 4 STEP 2 4 1 2 STEP 3 4 5 6 7 8 9 V Honeywell VR 4601 CB A B A B C 2 4...

Страница 66: ...PEGASUS F3 N 2S 3 02 2015 01 3540T623 3 1 3 2 3 3 3 flow stop 20 C 10 25 Fr 1 2 1 5 4 3 10 inox 5 3 230 Volt 50 Hz 5 5 3A 3 2 2 A B C D 40 3 A B 40 C 3 6 3 10 03 2015 01 354S125 3540T624 04 2018 01...

Страница 67: ...N 2S 2 02 2015 01 3540T623 1 2 1 2 FERROLI PEGASUS F3 N 2S PEGASUS F3 N 2S 2 2 1 1 2 3 4 5 6 7 1 0 3 2 1 1 7 6 1 1 5 15 0 7 0 1 TEST 3 7 4 2 1 6 90 30 45 1 6 1 0 1 2 5 2 1 1 5 03 2015 01 354S125 3540...

Страница 68: ...02 2015 01 3540T623 PEGASUS F3 N 2S 03 2015 01 354S125 3540T624 07 2018 01...

Отзывы: