Installation & Operating Instructions
Page 19
5. Managing the Keypad
The drive is configured and its operation monitored via the built in keypad and display.
IP20 Drives: IP20 rated drives are supplied with a 7 segment LED display and a five button keypad
IP55 & IP66 Drives are supplied with an OLED multi-line text display and a seven button keypad
5.1 Keypad layout and Function - Standard LED Keypad (IP20 Drives)
NAVIGATE
Used to display real-time informa-
tion, to access and exit parameter
edit mode and to store parameter
changes
UP
Used to increase speed in real-time
mode or to increase parameter
values in parameter edit mode
DOWN
Used to decrease speed in real-time
mode or to decrease parameter
values in parameter edit mode
RESET/STOP
Used to reset a tripped drive. When
in keypad mode is used to Stop a
running drive
START
When in keypad mode, used to start
a stopped drive to reverse the direc-
tion of rotation if bidirectional keypad
mode is enabled
5.2. Changing Parameters - Standard LED Keypad (IP20 Drives)
Procedure
Display Shows...
Power on Drive
stop
Press and hold the for >2 seconds
P1-01
Press the key
P1-02
The and can be used to select the desired parameter
P1-03
Select the required parameter, e.g. P1-02
P1-02
Press the button
0.0
Use the and keys to adjust the value e.g. set to 10
10.0
Press the key
P1-02
The parameter value is now adjusted and automatically stored. Press the key for
>2 seconds to return to operating mode
stop