HVAC

Installation & Operating Instructions

 Page 15

4. Electrical Installation

4.1 Grounding the Drive

This manual is intended as a guide for proper 

installation. ERIKS Industrial Services cannot 

assume responsibility for the compliance or the 

non-compliance to any code, national, local or 

otherwise, for the proper installation of this drive or 

associated equipment. A hazard of personal injury and/or 

equipment damage exists if codes are ignored during 

installation.

This Fenner QD drive contains high voltage 

capacitors that take time to discharge after 

removal of the main supply. Before working on the 

drive, ensure isolation of the main supply from line 

inputs. Wait ten (10) minutes for the capacitors to discharge 

to safe voltage levels. Failure to observe this precaution 

could result in severe bodily injury or loss of life.

Only qualified electrical personnel familiar with the 

construction and operation of this equipment and 

the hazards involved should install, adjust, operate, 

or service this equipment. Read and understand 

this manual and other applicable manuals in their entirety 

before proceeding. Failure to observe this precaution could 

result in severe bodily injury or loss of life.

4.1.1 Grounding Guidelines

The ground terminal of each Fenner QD:HVAC should be 

individually connected DIRECTLY to the site ground bus bar 

(through the filter if installed). Fenner QD ground 

connections should not loop from one drive to another, or 

to, or from any other equipment. Ground loop impedance 

must confirm to local industrial safety regulations. To meet 

UL regulations, UL approved ring crimp terminals should be 

used for all ground wiring connections. The drive Safety 

Ground must be connected to system ground. Ground 

impedance must conform to the requirements of national 

and local industrial safety regulations and/or electrical 

codes. The integrity of all ground connections should be 

checked periodically.

4.1.2. Protective Earth Connector

The cross sectional area of the PE Conductor must be at 

least equal to that of the incoming supply conductor.

4.13 Safety Ground

This is the safety ground for the drive that is required by 

code. One of these points must be connected to adjacent 

building steel (girder, joist), a floor ground rod, or bus bar. 

Grounding points must comply with national and local 

industrial safety regulations and/or electrical codes.

4.1.4. Motor Ground

The motor ground must be connected to one of the ground 

terminals on the drive.

4.1.5. Ground Fault Monitoring

As with all inverters, a leakage current to earth can exist. 

The Fenner QD:HVAC is designed to produce the minimum 

possible leakage current whilst complying with worldwide 

standards. The level of current is affected by motor cable 

length and type, the effective switching frequency, the earth 

connections used and the type of RFI filter installed. If an 

ELCB (Earth Leakage Circuit Breaker) is to be used, the 

following conditions apply: 

• 

A Type B Device must be used

• 

The device must be suitable for protecting equipment 

with a DC component in the leakage current

• 

Individual ELCBs should be used for each Fenner drive

Drives with a EMC filter have an inherently higher leakage 

current to ground (Earth). For applications where tripping 

occurs the EMC filter can be disconnected (on IP20 units 

only) by removing the EMC screws on the side of the 

product.

The Fenner QD:HVAC range has input supply voltage surge 

supression components fitted to protect the drive from 

voltage transients, typically originating from lightening 

strikes or switching of high power equipment on the same 

supply.

4.1.6. Shield Termination (Cable Screen)

The safety ground terminal provides a grounding point for 

the motor cable shield. The motor cable shield connected to 

this terminal (drive end) should also be connected to the 

motor frame (motor end). Use a shield terminating or EMI 

clamp to connect the shield to the safety ground terminal.

Internal 

EMC 

Filter

Internal 

Surge 

Protection

EMC

VAR

Earth

L/L1

N/L2

L3

Содержание QD:HVAC

Страница 1: ...Installation and Operating Instructions AC Variable Speed Drive 0 75kW 160kW 200 480 Volt 1 3 Phase...

Страница 2: ...ecommended Use a screened shielded cable The shield should be bonded to earth at both ends Motor Connection Check for Star or Delta Connection Enter the Motor Nameplate data into the drive param eters...

Страница 3: ...r voltage rating see page 17 Enter the Motor Nameplate data into the drive parameters as follows l Motor RatedVoltage P1 07 l Motor Rated Current P1 08 l Motor Rated Frequency P1 09 l Motor Rated Spee...

Страница 4: ...pment into which this product is incorporated must comply with the EMC Directive 2004 108 EC When using an Fenner drive with an internal or optional external filter compliance with the following EMC C...

Страница 5: ...nging the Language on OLED Display 23 5 10 Selecting between Hand and Auto Control OLED23 6 Commissioning 24 7 HVAC Specific Feature Setup 25 7 1 Pump Staging DOL Cascade 25 7 2 Pump Staging Multiple...

Страница 6: ...er control cabling is close to power cabling maintain a minimum separation of 100 mm and arrange crossings at 90 degrees Ensure that all terminals are tightened to the appropriate torque setting Do no...

Страница 7: ...40 110 6 575F3037 37 50 150 6 575F3045 45 60 180 6 575F3055 55 75 202 6 575F3075 75 100 240 7 575F3090 90 120 300 7 kW Model with Filter 22kW HP Output Current A Frame Size 575F40P7 0 75 1 2 2 2 575F4...

Страница 8: ...utput Current A Frame Size 576F20P7 0 75 1 4 3 2 576F21P5 1 5 2 7 2 576F22P2 2 2 3 10 5 2 kW Model with Filter kW HP Output Current A Frame Size 576F40P7 0 75 1 2 2 2 576F41P5 1 5 2 4 1 2 576F42P2 2 2...

Страница 9: ...of the correct type and power requirements for the application Store the QD HVAC in its box until required Storage should be clean and dry and within the temperature range 40 C to 60 C 3 3 UL Complia...

Страница 10: ...33 4 25 0 167 7 5 0 295 5 540 21 26 515 20 28 520 20 47 8 0 315 270 10 63 235 9 25 175 6 89 4 25 0 167 7 5 0 295 6 865 34 06 830 32 68 840 33 07 10 0 394 340 13 39 290 11 42 200 7 87 5 5 0 217 11 0 43...

Страница 11: ...ve Size X Above Below Y Either Side mm in mm in 2 IP66 150 5 9 10 0 394 3 IP66 150 5 9 10 0 394 4 IP55 200 7 9 10 0 394 5 IP55 200 7 9 10 0 394 6 IP55 200 7 9 10 0 394 7 IP55 200 7 9 10 0 394 Note Typ...

Страница 12: ...er slide the top locating lugs upwards under the top cover then re fasten the lower cover screws 3 7 3 Frame Size 4 3 7 2 Frame Size 5 Using a suitable flat blade screwdriver rotate the four retaining...

Страница 13: ...www fptgroup com HVAC Installation Operating Instructions Page 13 3 7 4 Frame Size 7 Using a suitable flat blade screwdriver rotate the four retaining screws indicated until the screw slot is vertical...

Страница 14: ...erating Instructions Page 14 3 8 Lock Off Power Isolator Lock Off IP66 with Built in Isolater Option On the switched models the main power islator switch can be locked in the off position using a 20mm...

Страница 15: ...nections should be checked periodically 4 1 2 Protective Earth Connector The cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor 4 13 Safety Ground...

Страница 16: ...inutes should be allowed before removing the terminal covers or connection The maximum permissible short circuit current at the Fenner drive Power terminals as defined in IEC60439 1 is 100kA An option...

Страница 17: ...ermistor Connection Where a motor thermistor is to be used it should be connected as follows 1 2 8 7 6 5 4 3 10 9 ControlTerminal Strip Additional Information Compatible Thermistor PTC Type 2 5k trip...

Страница 18: ...A for user potentiometer 6 AI 1 Input 4 Digital 8 30V DC Analog Input 1 10 to 10V 0 4 to 20mA 7 0V 0 Volt Common 8 AO1 Output 1 1st Analog Digital Output 0 to 10V 4 to 20mA or 24VDC Digital 9 0V 0 Vol...

Страница 19: ...arameter edit mode DOWN Used to decrease speed in real time mode or to decrease parameter values in parameter edit mode RESET STOP Used to reset a tripped drive When in keypad mode is used to Stop a r...

Страница 20: ...ess Display shows P1 01 Select lowest Group Parameter Px xx The first parameter of a group is selected Display shows P1 10 Press Display shows P1 01 Set Parameter to minimum value Any numerical value...

Отзывы: