HVAC

Installation & Operating Instructions

 Page 16

4.2. Wiring Precautions

Connect the Fenner QD:HVAC according to section 4.3 and 

4.4, ensuring that motor terminal box connections are 

correct. There are two connections in general: Star and 

Delta. It is essential to ensure that the motor is connected 

in accordance with the voltage at which it will be operated. 

For more information, refer to section 4.5 Motor Terminal 

Box Connections. 
It is recommended that the power cabling should be 4-core 

PVC-insulated screened cable, laid in accordance with local 

industrial regulations and codes of practice.

4.3 Incoming Power Connection

• 

For a single phase supply, power should be connected to 

L1/L, L2/N.

• 

For 3 phase supplies power should be connected to L1, 

L2, and L3. Phase sequence is not important.

• 

For compliance with CE and C Tick EMC requirements, a 

symmetrical shielded cable is recommended.

• 

A fixed installation is required according to IEC61800-5-1 

with a suitable disconnecting device installed between 

the Fenner drive and the AC Power Source. The 

disconnecting device must conform to the local safety 

code / regulations (e.g. within Europe, EN60204-1, Safety 

of machinery). 

• 

The cables should be dimensions according to any local 

codes or regulations. Guideline dimensions are given in 

section13.4.

• 

Suitable fuses to provide wiring protection of the input 

power cable should be installed in the incoming supply 

line, according to the data in section 13.4. The fuses must 

comply with any local codes or regulations in place.  In 

general, type gG (IEC 60269) or UL type T fuses are 

suitable; however in some cases type aR fuses may be 

required. The operating time of the fuses must be below 

0.5 seconds.

• 

Where allowed by local regulations, suitably dimensioned 

type B MCB circuit breakers of equivalent rating may be 

utilised in place of fuses, providing that the clearing 

capacity is sufficient for the installation. 

• 

When the power supply is removed from the drive, a 

minimum of 30 seconds should be allowed before 

re-applying the power. A minimum of 10 minutes should 

be allowed before removing the terminal covers or 

connection.

• 

The maximum permissible short circuit current at the Fenner 

drive Power terminals as defined in IEC60439-1 is 100kA.

• 

An optional Input Choke is recommended to be installed 

in the supply line for drives where any of the following 

conditions occur:-

• 

The incoming supply impedance is low or the fault 

level / short circuit current is high

• 

The supply is prone to dips or brown outs

• 

An imbalance exists on the supply (3 phase drives)

• 

The power supply to the drive is via a bus-bar and 

brush gear system (typically overhead Cranes).

• 

In all other installations, an input choke is recommended 

to ensure protection of the drive against power supply 

faults. Refer to your local Fenner Authorised Distributor 

for available options

• 

Fenner QD:HVAC models in frame sizes 4 to 8 are factory 

fitted with an Input choke as standard.

4.4 Drive and Motor Connection

• 

The motor should be connected to the Fenner drive U, V, 

and W terminals using a suitable 3 or 4 core cable. Where 

a 3 core cable is utilised, with the shield operating as an 

earth conductor, the shield must have a cross sectional 

area at least equal to the phase conductors when they 

are made from the same material. Where a 4 core cable 

is utilised, the earth conductor must be of at least equal 

cross sectional area and manufactured from the same 

material as the phase conductors.

• 

The motor earth must be connected to one of the drive 

earth terminals.

• 

For compliance with the European EMC directive, a 

suitable screened (shielded) cable should be used. 

Braided or twisted type screened cable where the screen 

covers at least 85% of the cable surface area, designed 

with low impedance to HF signals are recommended as a 

minimum. Installation within a suitable steel or copper 

tube is generally also acceptable.

• 

The cable screen should be terminated at the motor end 

using an EMC type gland allowing connection to the 

motor body through the largest possible surface area

• 

Where drives are mounted in a steel control panel 

enclosure, the cable screen may be terminated directly to 

the control panel using a suitable EMC clamp or gland, as 

close to the drive as possible.

• 

For IP55 drives, connect the motor cable screen to the 

internal ground clamp

Содержание QD:HVAC

Страница 1: ...Installation and Operating Instructions AC Variable Speed Drive 0 75kW 160kW 200 480 Volt 1 3 Phase...

Страница 2: ...ecommended Use a screened shielded cable The shield should be bonded to earth at both ends Motor Connection Check for Star or Delta Connection Enter the Motor Nameplate data into the drive param eters...

Страница 3: ...r voltage rating see page 17 Enter the Motor Nameplate data into the drive parameters as follows l Motor RatedVoltage P1 07 l Motor Rated Current P1 08 l Motor Rated Frequency P1 09 l Motor Rated Spee...

Страница 4: ...pment into which this product is incorporated must comply with the EMC Directive 2004 108 EC When using an Fenner drive with an internal or optional external filter compliance with the following EMC C...

Страница 5: ...nging the Language on OLED Display 23 5 10 Selecting between Hand and Auto Control OLED23 6 Commissioning 24 7 HVAC Specific Feature Setup 25 7 1 Pump Staging DOL Cascade 25 7 2 Pump Staging Multiple...

Страница 6: ...er control cabling is close to power cabling maintain a minimum separation of 100 mm and arrange crossings at 90 degrees Ensure that all terminals are tightened to the appropriate torque setting Do no...

Страница 7: ...40 110 6 575F3037 37 50 150 6 575F3045 45 60 180 6 575F3055 55 75 202 6 575F3075 75 100 240 7 575F3090 90 120 300 7 kW Model with Filter 22kW HP Output Current A Frame Size 575F40P7 0 75 1 2 2 2 575F4...

Страница 8: ...utput Current A Frame Size 576F20P7 0 75 1 4 3 2 576F21P5 1 5 2 7 2 576F22P2 2 2 3 10 5 2 kW Model with Filter kW HP Output Current A Frame Size 576F40P7 0 75 1 2 2 2 576F41P5 1 5 2 4 1 2 576F42P2 2 2...

Страница 9: ...of the correct type and power requirements for the application Store the QD HVAC in its box until required Storage should be clean and dry and within the temperature range 40 C to 60 C 3 3 UL Complia...

Страница 10: ...33 4 25 0 167 7 5 0 295 5 540 21 26 515 20 28 520 20 47 8 0 315 270 10 63 235 9 25 175 6 89 4 25 0 167 7 5 0 295 6 865 34 06 830 32 68 840 33 07 10 0 394 340 13 39 290 11 42 200 7 87 5 5 0 217 11 0 43...

Страница 11: ...ve Size X Above Below Y Either Side mm in mm in 2 IP66 150 5 9 10 0 394 3 IP66 150 5 9 10 0 394 4 IP55 200 7 9 10 0 394 5 IP55 200 7 9 10 0 394 6 IP55 200 7 9 10 0 394 7 IP55 200 7 9 10 0 394 Note Typ...

Страница 12: ...er slide the top locating lugs upwards under the top cover then re fasten the lower cover screws 3 7 3 Frame Size 4 3 7 2 Frame Size 5 Using a suitable flat blade screwdriver rotate the four retaining...

Страница 13: ...www fptgroup com HVAC Installation Operating Instructions Page 13 3 7 4 Frame Size 7 Using a suitable flat blade screwdriver rotate the four retaining screws indicated until the screw slot is vertical...

Страница 14: ...erating Instructions Page 14 3 8 Lock Off Power Isolator Lock Off IP66 with Built in Isolater Option On the switched models the main power islator switch can be locked in the off position using a 20mm...

Страница 15: ...nections should be checked periodically 4 1 2 Protective Earth Connector The cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor 4 13 Safety Ground...

Страница 16: ...inutes should be allowed before removing the terminal covers or connection The maximum permissible short circuit current at the Fenner drive Power terminals as defined in IEC60439 1 is 100kA An option...

Страница 17: ...ermistor Connection Where a motor thermistor is to be used it should be connected as follows 1 2 8 7 6 5 4 3 10 9 ControlTerminal Strip Additional Information Compatible Thermistor PTC Type 2 5k trip...

Страница 18: ...A for user potentiometer 6 AI 1 Input 4 Digital 8 30V DC Analog Input 1 10 to 10V 0 4 to 20mA 7 0V 0 Volt Common 8 AO1 Output 1 1st Analog Digital Output 0 to 10V 4 to 20mA or 24VDC Digital 9 0V 0 Vol...

Страница 19: ...arameter edit mode DOWN Used to decrease speed in real time mode or to decrease parameter values in parameter edit mode RESET STOP Used to reset a tripped drive When in keypad mode is used to Stop a r...

Страница 20: ...ess Display shows P1 01 Select lowest Group Parameter Px xx The first parameter of a group is selected Display shows P1 10 Press Display shows P1 01 Set Parameter to minimum value Any numerical value...

Отзывы: