JP5 - Alarm Initiation Inputs
1 - ISO-GND
2 - Input #1
3 - ISO-GND
4 - Input #2
5 - ISO-GND
6 - Input #3
7 - ISO-GND
8 - Input #4

Ethernet Port

The Informer100 Speaker has an 8 pin Ethernet port for connecting to the network. 

Ethernet wire runs must be less than 328 feet from the nearest network switch. Do not 

install in a conduit carrying high voltage. The wired Ethernet port auto-negotiates a 

10/100, full or half duplex connection.  

Putting the Informer100 Speaker into Standalone Mode

Standalone mode allows the Informer100 Speaker to be activated from the Alarm 

Initiation Inputs without being connected to a network. The Informer100 requires setup 

prior to placing into standalone mode. All configuration should be performed prior to 

installing. Once the unit is configured and tested, place a shorting jumper across pins  

1 and 2 of JP3. To configure the Informer100 Speaker, use Commander software version 

14.9.0 or later. See the 

Informer Setup and Programming Manual

.

Relay Outputs 

The Informer100 Speaker has two independently programmable relay outputs. The relay 

timing is configured and programmed into the Informer100 Speaker from the Commander 

user interface.
The relay outputs are capable of controlling external devices. The normally outputs 

are located at pins 1 & 2 and pins 3 & 4 of the removable output connector JP4 on the 

controller board. The outputs can be wired in series with the power wired into the unit 

by using the power connections available on JP6 and JP7, providing switched AC or DC 

power to activate other devices.
Do not exceed the voltage and current ratings listed in the specifications section of this 

manual. When using this feature, the relay outputs turn on until one of the following 

occurs:
•  Until the programmed default timeout occurs
•  Until the CANCEL or RESET command is received
You can individually configure the relay outputs to open, close, and cycle based on a pre-

programmed sequence. Relays can also be configured to turn on when PA VOIP is active. 

Содержание I-IP100ACX

Страница 1: ...tion Manual 25500437 Rev A0 1117 Printed in U S A Copyright 2017 Federal Signal Corporation Informer100 Speaker Models I IP100ACX and I IP100DCX IP Enabled High Powered Indoor Outdoor Speaker For use in hazardous locations Strobe is optional ...

Страница 2: ...y is in lieu of all other warranties express or implied contractual or statutory including but not limited to the warranty of merchantability warranty of fitness for a particular purpose and any warranty against failure of its essential purpose 2645 Federal Signal Drive University Park Illinois 60484 3617 www fedsig com Customer Support 800 548 7229 1 708 534 3400 Technical Support 800 524 3021 1 ...

Страница 3: ...unting 16 Large Pole Mounting 6 in diameter or larger 16 Small Pole Mounting 2 3 8 in or 4 1 2 in diameter poles 16 Mounting with Omni Direction Bracket 2 3 8 in diameter pole 18 Mounting without Bracket 19 Opening the Housing 19 Wiring Power to the Control Board 20 Wiring to the Relay Outputs 22 Wiring to the Alarm Initiation Input Connections 22 Ethernet Port 23 Putting the Informer100 Speaker i...

Страница 4: ...acement Parts 24 Figures Figure 1 Front and Back of Informer100 Speaker 10 Figure 2 Bracket attached to speaker 13 Figure 3 Width and height of bracket 14 Figure 4 Depth and height with bracket 14 Figure 5 Top view of speaker 15 Figure 6 Ceiling mount 15 Figure 7 Bracket I IP100 PMW 16 Figure 8 Bracket I IP100 PM 17 Figure 9 Bracket I IP100 OMNI 18 Figure 10 Surface mount hole center dimensions 19...

Страница 5: ...dures may be needed to effectively warn people indoors The sound output of Informer100 Speaker is capable of causing permanent hearing damage To prevent excessive exposure carefully plan placement post warnings and restrict access to areas near sirens Activating the Informer100 Speaker may not result in people taking the desired actions if those to be warned are not properly trained about the mean...

Страница 6: ...posure limits specified in OSHA 29 CFR 1910 should not be exceeded These devices are intended for permanent installation and operation in accordance with Title 46 Code of Federal Regulations Parts 110 113 or Title 33 Code of Federal Regulations Part 183 Sub part I Section 183 410 and the applicable requirements of the American Boat and Yacht Council Inc and or ANSI NFPA 302 Fire Protection Standar...

Страница 7: ...y injury File these instructions in a safe place and refer to them periodically Give a copy of these instructions to new recruits and trainees Also give a copy to anyone who is going to service or repair the Informer100 Speaker To reduce the risk of electric shock do not perform any servicing other than what is contained in the operating instructions unless you are qualified to do so Refer all ser...

Страница 8: ...vels The Informer100 allows connection of up to four external switches to activate predefined alert events The Informer100 can be programmed and configured as a standalone device to only use the inputs to activate the Informer100 This may be useful if the location has no network connectivity but where voice and tone alerts from locally activated inputs is required The Informer100 can be networked ...

Страница 9: ...ce can be individually configured for volume and noise level adjustments Remote volume control for optimizing sound levels Speaker as microphone for talk back feature Alerts can be sent to single devices groups or zones or all devices Commander Software control and activation Wall or pole mount options Four local alarm initiation inputs to activate unit locally or standalone operation Momentary mo...

Страница 10: ...ndby 5 15 A during a function Relay Outputs 2 A at 30 Vdc or 250 Vac 25 A max inrush N O dry contacts Ethernet Port IEEE 802 3 10 100 Base T connection Alarm Initiating Inputs Four optically Isolated Inputs Dry Contact closure 1 K ohms NOTE The four optically isolated Alarm Initiation Inputs allow remote activation of tones and messages through a volt free dry contact closure The momentary contact...

Страница 11: ...dicates level of amplifier output D8 ACTIVATION INPUT 1 Red LED turns on when Activation input 1 is being activated D12 ACTIVATION INPUT 2 Red LED turns on when Activation input 2 is being activated D14 ACTIVATION INPUT 3 Red LED turns on when Activation input 3 is being activated D16 ACTIVATION INPUT 4 Red LED turns on when Activation input 4 is being activated D17 Table 3 Connectors and Jacks Co...

Страница 12: ...s drilling holes or lifting equipment Therefore experienced electricians in accordance with national and local electrical codes acting under the direction of the installation crew safety foreman should perform installation Determine a Suitable Location The Informer100 can be mounted on any relatively flat surface with the supplied mounting brackets The mounting surface must be capable of supportin...

Страница 13: ...the Mounting Brackets to the Speaker Housing Do the following to attach the brackets 1 The mounting brackets are attached to the speaker as shown below using the six supplied 20 x 5 8 in screws Note the orientation of the curved slots on the L shaped brackets this orientation is important to allow the speaker to be pivoted downward 2 Tighten the 20 x 5 8 in screws to approximately 80 in lb 3 Attac...

Страница 14: ...ion Informer100 Speaker Models I IP100ACX and I IP100DCX Figure 3 Width and height of bracket 2 00 in 5 00 in 2 88 in 1 44 in 5X 397 Figure 4 Depth and height with bracket 6 68 in 2 53 in 12 87 in 2 00 in 10 09 in ...

Страница 15: ...15 Installation Description Specifications and Installation Manual Figure 5 Top view of speaker 10 09 in 12 87 in 8 90 in Figure 6 Ceiling mount ...

Страница 16: ...t washers lock washers and 3 8 in nuts mount the speaker to the I IP100 PMW bracket as shown in Figure 2 4 Use the side pivot bolts to allow adjustment of the speaker up and down to optimize speaker effectiveness Figure 7 Bracket I IP100 PMW Small Pole Mounting 2 3 8 in or 4 1 2 in diameter poles Use the following procedure if mounting the speaker with the optional I IP100 PM bracket 1 Find suitab...

Страница 17: ...17 Installation Description Specifications and Installation Manual Figure 8 Bracket I IP100 PM ...

Страница 18: ... I IP100 OMNI bracket to create an omni directional speaker The speaker is mounted as described in the Small Pole Mount section with the omni bracket mounted at a distance of 2 0 inches from the speaker 1 Identify location for bracket 2 Attach bracket using supplied U bolts and hardware Figure 9 Bracket I IP100 OMNI 2 0 in Omni Bracket ...

Страница 19: ... hole center dimensions 5 20 in 2 60 in 3 00 6 00 7 39 C L C L 6 1 4 20 0 5 in THREAD DEPTH Opening the Housing Tools required 3 8 in socket 6 in extension To open the housing loosen the four cover screws while supporting the housing so it does not fall The cover screws are retained in the housing The front of the unit is heavy but it is attached to the rear housing with a pivot hinge to allow eas...

Страница 20: ...is recommended to leave the connector on the PCB With I IP100ACX units JP9 is wired from the factory to the power supply PCB With the I IP100DCX units JP9 is wired to the amplifier PCB Use JP6 and JP7 to wire external lights or strobes through JP4 which is a normally open relay Typical installation would use voltage to be wired through the JP4 relays contacts NOTE Current draw from JP6 JP7 and JP4...

Страница 21: ...communications Factory wiring Factory wiring JP6 24 V L2 NUE 24 Vdc GND 24 V 24 Vdc GND 24 V Serial Port 1 2 3 4 JP5 100 W Amp To Driver To Temperature Sense Fuse JP3 Pins 1 2 I IP100ACX 120 240Vac Model 120 Vac Hot is connected to JP8 terminal 1 L1 Hot 120 Vac Neutral is connected to JP8 terminal 2 L2 Neutral Earth Ground is connected to JP8 terminal 3 GND 240 Vac L1 is connected to JP8 terminal ...

Страница 22: ...tory wiring Factory wiring JP6 L2 NUE L2 NUE L1 Hot L2 NUE L1 Hot Serial Port 1 2 3 4 Fuse Fuse JP5 JP3 Pins 1 2 Wiring to the Relay Outputs JP4 Relay Outputs 1 2 Normally Open 3 4 Normally Open Wiring to the Alarm Initiation Input Connections The Alarm Initiation Inputs are activated by shorting the input to the ISO GND next to it usually through an normally open switch or normally open dry relay...

Страница 23: ...0 Speaker use Commander software version 14 9 0 or later See the Informer Setup and Programming Manual Relay Outputs The Informer100 Speaker has two independently programmable relay outputs The relay timing is configured and programmed into the Informer100 Speaker from the Commander user interface The relay outputs are capable of controlling external devices The normally outputs are located at pin...

Страница 24: ...ronment does not allow powering proceed to next step 6 Verify all connectors are seated Also verify wires are not strained and are not impeding ability to close unit 7 Lift front of unit and seat the front cover against the rear enclosure 8 Tighten the cover screws hand tight and then torque them in alternate pattern to 60 in lb 10 in lb Ordering Replacement Parts To order replacement parts call C...

Отзывы: