![Federal Signal Corporation I-IP100ACX Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/federal-signal-corporation/i-ip100acx/i-ip100acx_description-specifications-and-installation-manual_548413011.webp)
11
Specifications
Description, Specifications, and Installation Manual
The following indicators are for troubleshooting purposes only. These indicators are not
visible when the unit is closed.
Table 2 Visual Indications (Located on internal control board.)
POWER
Green LED turns on when power is connected. D5
ISOLATED POWER Green LED turns on when Isolated power for inputs and relay
outputs is functioning. D6
CPU
Flashing RED LED indicates the CPU is running its program. D18
NETWORK
Green LED turns on when unit has made a connection to the
network. D27
LISTEN
Red LED turns on when Commander is listening. Unit is sending
audio to Commander. D25
TALK
Green LED turns on when Commander is talking. Unit is playing
audio being sent. D26
AMPOUTPUT
VOLTAGE
Green LED turns on when amplifier is active. Brightness indicates
level of amplifier output. D2
AMPLIFIER
OUTPUT
CURRENT
Green LED turns on when amplifier is active. Brightness indicates
level of amplifier output. D8
ACTIVATION
INPUT #1
Red LED turns on when Activation input #1 is being activated. D12
ACTIVATION
INPUT #2
Red LED turns on when Activation input #2 is being activated. D14
ACTIVATION
INPUT #3
Red LED turns on when Activation input #3 is being activated. D16
ACTIVATION
INPUT #4
Red LED turns on when Activation input #4 is being activated. D17
Table 3 Connectors and Jacks (Control board connectors)
JP2
Serial Port for factory approved programming or for message board
display
JP3 Pin Jack
Short pins 1 and 2 for standalone mode
JP4 Relay Outputs
1 and 2 Relay 1 Normally Open
3 and 4 Relay 2 Normally Open
JP5 Initiation inputs 1 and 2 – ISO Ground/Input 1
3 and 4 – ISO Ground/Input 2
5 and 6 – ISO Ground/Input 3
7 and 8 – ISO Ground/Input 4
NOTE: JP6, JP7, JP8 and JP9 are physically connected to provide
a distribution of AC or DC power. The combined load of all power
should not exceed 8 amperes AC/DC, 25 A max inrush
JP6 and JP7
AC/DC Power
Distribution
1 – L1/Hot/(+) 24 Vdc
2 – L2/Neutral/(-) 24 Vdc Gnd
3 – Earth Ground
JP8
Input for AC/DC
Power Distribution
1 – L1/Hot/(+) 24 Vdc
2 – L2/Neutral/(-) 24 Vdc Gnd
3 – Earth Ground