Specifications
Informer100 Speaker (Models I-IP100ACX and I-IP100DCX)
The following is a picture of the Informer100 Speaker shown with optional FB2PST
Fireball
®
Strobe Warning Light and the back shown with standard wall-mount bracket.
Figure 1 Front and Back of Informer100 Speaker
Specifications
Table 1 Electrical
Operating Voltages I-IP100ACX
Switch-selectable 120 or 240 Vac
120 Vac nom, 50/60 Hz or
240 Vac nom, 50/60 Hz
Operating Current I-IP100ACX
120 Vac; 26 mA Standby, 1.50 A during a function
240 Vac; 21 mA Standby, 820 mA during a function
Operating Voltages I-IP100DCX 24 Vdc
Operating Current I-IP100DCX
24 Vdc; 100 mA Standby, 5.15 A during a function
Relay Outputs
2 A at 30 Vdc or 250 Vac, 25 A max inrush, N.O. dry
contacts
Ethernet Port
IEEE 802.3, 10/100 Base-T connection
Alarm Initiating Inputs
Four optically Isolated Inputs
Dry Contact closure < 1 K ohms
NOTE: The four optically isolated Alarm Initiation Inputs
allow remote activation of tones and messages through
a volt-free, dry-contact closure.
The momentary contact closure must be a minimum of
500 ms.
Audio Storage
Warning siren audio, seven factory installed tones: Wail,
Steady, Alternate Wail, Alternate Steady, Pulsed Wail,
Pulsed Steady, Auxiliary Chime
Prerecorded files
—
up to 250 messages with up to
15 minutes of recording time
Audio Data
8 bit 8 kHz mono WAV
Audio Frequency response
300 Hz to 3000 Hz, +1 to -3 dB per octave
Maximum Audio Output
100 W, 120 dBa tones/114.5 dBa for voice at 10 feet