2001-AC
15
Installation Instructions
2. Install 1 inch user supplied electrical conduit between the conduit fitting in the
bottom of the siren rotator housing and the conduit fitting at the bottom of the
Motor Starter Enclosure.
3. Route the two 2-AWG siren motor wires and the one 12 AWG rotator motor wire
(user-supplied) from the siren rotator housing to the Motor Starter Enclosure
through the conduit.
4. Connect the 12 AWG wire (48 VDC) from the terminal block in the rotator
housing terminal 1 (see Figure 5 Motor Starter Wiring) to the rotator control relay
K1-2 (user supplied
¼
inch ring terminal required - see Figure 4 Motor Starter
View A-A).
Figure 7 Terminal Block in Rotator Housing
5. Connect a 2 AWG wire (48 VDC) from the terminal block in the rotator housing
terminal 2 to the rotor control relay K2-2 (user supplied
¼
inch ring terminal
required).
6. Connect a 2 AWG wire (common) from the terminal block in the rotator housing
terminal 3 to TB1-1 in the control box (user supplied 5/16 inch ring terminal
required).
7. Tighten all connections securely to provide good electrical connections.
8. Remove any metal shavings or debris from the enclosures.
9. Ground the Siren and 2001-AC enclosure to earth ground.
Connecting the Transformer/Rectifier
Disconnect AC power and make sure transformer is de-energized before
making or changing electrical connections.
1. Route 1 inch conduit between the user-supplied fused disconnect switch and the
user-supplied conduit fitting in the bottom of the Transformer/Rectifier enclosure.