Installation Instructions 

   

 

Installation Instructions 

 

Electrocution or severe personal injury can occur when making electrical 
connections, drilling holes, or lifting equipment. Therefore, experienced 
electricians in accordance with national and local electrical codes, acting 
under the direction of the installation crew safety foreman, should perform 
installation.

 

Location and Installation 

This section provides guidelines for installing the 2001-AC. 

Locating the 2001-AC 

 

Mount the 2001-AC either indoors or outdoors. In order to minimize voltage loss, 
Federal Signal recommends that you install the 2001-AC within 50 feet of the 
siren or other equipment being activated. If it is necessary to make a longer cable 
run, Federal Signal recommends increasing the wire size to 1 AWG or larger. 
Mount the Motor Starter Enclosure as close as possible to the 
Transformer/Rectifier. Refer to Figure 3 Typical Siren Installation Drawing to see 
a typical installation. 

 

The Motor Starter Enclosure is supplied with a padlock hasp for security. 

 

The system operates from either 208, 220, or 240 VAC single phase, 50-60 Hz. 
Do not connect the 2001-AC to any other voltage source. 

 

Refer to the Specifications section to determine the total weight of the 2001-AC. 
Ensure that the mounting surface and fasteners can safely sustain the weight.  

Содержание 2001-AC

Страница 1: ...2001 AC DC Motor Starters and Transformer Rectifier Plus Options 2001HR Holding Relay Radio Activation Installation and Operation Manual 255252 Rev L4 0616 Printed in U S A...

Страница 2: ...2001 AC Copyright 2016 Federal Signal Corporation...

Страница 3: ...to the product or labor charges for removal and re installation of the product The Federal Signal Corporation warranty shall not apply to components or accessories that have a separate warranty by the...

Страница 4: ...2001 AC Website http www alertnotification net...

Страница 5: ...01HR 5 Battery Backup 5 Specifications 6 Installation Instructions 7 Location and Installation 7 Locating the 2001 AC 7 Installation Requirements 9 Installation 9 Pole Mounting 9 Flat Surface Mount 10...

Страница 6: ...gure 3 Typical Siren Installation Drawing 8 Figure 4 Motor Starter Enclosure Parts List 11 Figure 5 Motor Starter Wiring Diagram with HR Option 12 Figure 6 Typical Wiring Diagram 13 Figure 7 Terminal...

Страница 7: ...agement Agency for assistance with planning an outdoor warning system The Outdoor Warning Guide CPG 1 17 Civil Preparedness Principles of Warning CPG 1 14 FEMA REP 1 Appendix 3 Nuclear Plant Guideline...

Страница 8: ...rocution or severe personal injury can occur when performing various installation and service functions such as making electrical connections drilling holes or lifting equipment Therefore only experie...

Страница 9: ...ead and thoroughly understand all safety notices in this manual and all operations related items in all instruction manuals shipped with equipment Thoroughly discuss all contingency plans with those r...

Страница 10: ...as a siren Figure 1 2001 AC FC control purchased separately Describing the Motor Starter and the Transformer Rectifier The 2001 AC consists of two enclosures that you can separately mount for ease of...

Страница 11: ...FC Controllers are capable of both radio and local push button control These controllers are available in UHF and VHF bands Landline cellular satellite and IP options are available contact your local...

Страница 12: ...5 VAC at 10 Amps Operating Current 100 Amps Nom Fusing 200 Amps fast Contactors Contact Rating 200 A at 48 VDC Coil 48 VDC 110 ohms General Continuous Full Output Signaling Time 30 minutes Operating T...

Страница 13: ...eral Signal recommends that you install the 2001 AC within 50 feet of the siren or other equipment being activated If it is necessary to make a longer cable run Federal Signal recommends increasing th...

Страница 14: ...8 2001 AC Installation Instructions MERGEFORMAT Configuring the Informer IPFORMAT General Descriptionations Figure 3 Typical Siren Installation Drawing...

Страница 15: ...rminals 1 2 AWG inch ring terminal 1 12 AWG inch ring terminal 3 10 AWG wire nuts Approximately 50 feet of 1 inch conduit inch conduit length depends on install Ground wiring rod and or clamps Install...

Страница 16: ...accordance with local and national electric codes on the pole beneath or opposite the Control Unit Transformer Rectifier assembly in line with the primary AC service Flat Surface Mount To attach the...

Страница 17: ...2001 AC 11 Installation Instructions Figure 4 Motor Starter Enclosure Parts List...

Страница 18: ...12 2001 AC Installation Instructions MERGEFORMAT Configuring the Informer IPFORMAT General Descriptionations Figure 5 Motor Starter Wiring Diagram with HR Option...

Страница 19: ...2001 AC 13 Installation Instructions Figure 6 Typical Wiring Diagram...

Страница 20: ...Motor Starter Wiring and Figure 6 Typical Wiring Diagram Typical connections between the siren and control unit are accomplished using user supplied wires Two 2 AWG wires provide operating power to th...

Страница 21: ...al Block in Rotator Housing 5 Connect a 2 AWG wire 48 VDC from the terminal block in the rotator housing terminal 2 to the rotor control relay K2 2 user supplied inch ring terminal required 6 Connect...

Страница 22: ...Transformer Rectifier Enclosure and the Motor Starter Enclosure 5 Route two user supplied wires through the conduit that was just installed between the Transformer Rectifier and Motor Starter Use 3 A...

Страница 23: ...motor and the rotator motor are activated When the connection to ground is removed power to the siren motor is removed and the rotator motor remains on for fifteen 15 seconds to allow a single contac...

Страница 24: ...est the 2001 AC for proper operation at least once a month A daily test at noon curfew or other selected time is preferred This not only enhances the usefulness of the siren but also instills public c...

Страница 25: ...could occur when working on this equipment Service should only be performed by personnel familiar with 240 VAC power and only after reading this manual The following checklist should be completed if...

Страница 26: ...20 2001 AC Service and Maintenance MERGEFORMAT Configuring the Informer IPFORMAT General Descriptionations Figure 9 Transformer...

Страница 27: ...6 I Installation Instructions 7 Installation Requirements 9 Introduction to the 2001 AC 4 L Locating the 2001 AC 7 M Maintenance 18 Motor Starter 4 P Pole Mounting 9 Pre Operation Checkout 17 Preventi...

Страница 28: ...2645 Federal Signal Drive University Park IL 60484 3167 Phone 708 534 3400 Website http www alertnotification net...

Отзывы: