INSTALLATION 

DISCHARGE PIPING: 

Discharge piping should be as 

short  as  possible  and  sized  no  smaller  than  the 
pump’s  discharge  size. 

Do  not  reduce  the 

discharge pipe size below that which is provided 
on  the  pump. 

Both  check  valves  and  a  shut-off 

valve  are  recommended  for  each  pump.  The 
check  valve  is  used  to  prevent  backflow  into  the 
pit.  If  a  swing  check  valve  is  used,  it  is 
recommended to be installed at a 45

°

 agree with 

the pivot pin on top. The shut-off valve is used to 
manually  stop  system  flow  during  pump  testing 
and servicing.  

 
ELECTRICAL CONNECTIONS:  
1. POWER  CABLE: 

The  power  cable  mounted  to 

the  pump  must  not  be  modified  in  any  way 
except  for  shortening  or  splicing  to  a  specific 
applications. 1 Phase pumps are provided with 
a  3  wire  power  cord,  and  3  Phase  pumps  are 
provided  with  a  4  wire  power  cord.  Connect 
the  green  wire  to  ground.  Under  no 
circumstances  should  the  green  wire  be 
connected  to  the  power  supply.  Every  pump 

must 

be grounded. 

DO NOT USE THE POWER 

CABLE  TO  LIFE  PUMP

.  Do  not  use  an 

extension  cord  for  1  Phase  pump(s).  Always 
wire  the  pump  as  indicated  on  the  wiring 
diagram inside the control panel  

 

2. OVERLOAD  PROTECTION:

  On  submersible 

motors,  an  in-panel  overload  protector  is 
needed to act as an overheating protector and 
operates  on  the  combined  effect  of 
temperature and current. This means that the 
overload  protector  will  trip  out  and  shut  the 
pump  off  if  the  windings  become  too  hot,  or 
the  load  current  passing  through  them 

becomes  too  high.  (

IMPORTANT!!! 

–  The 

overload 

in 

the 

panel 

should 

NOT 

automatically  reset  and  start  the  pump  up 
after  the  motor  cools.)  In  the  event  of  an 
overload,  the  source  of  this  condition  should 
be determined and corrected immediately.  

 
 

I

WARNING: 

Never  let  the  end  of  the  cable 

contact water 

I

WARNING: 

If  the  cable  is  extended,  do  not 

immerse the splice in water 

I

CAUTION: 

Fasten  the  cable  to  the  discharge 

piping with zip tie 

I

CAUTION: 

Install the power cable so that it will 

not  overheat.  Overheating  is  typically  caused  by 
coiling the cable and exposing it to direct sunlight. 
 
 

IMPORTANT!!! 

Always  rely  on  a  Certified 

Electrician for installation 
 

•••••••••••••• 

Содержание BGP Series

Страница 1: ...i IMPORTANT READ ALL INSTRUCTIONS IN THIS MANUAL BEFORE OPERATING AND SERVING A PUMP...

Страница 2: ...ntained properly Sewage pumps provide for the lifting and disposal of sewage and sewage related fluids from retaining basins or concrete pits and are pumped to city water disposal lines where these fl...

Страница 3: ...NSURE EMPLOYEES WILL NOT BE EXPOSED TO HEALTH HAZARDS IN HANDLING SAID MATIERAL ALL APPLICABLE LAWS AND REGULATIONS SHALL APPLY IWARNING Installation wiring and junction connections must be in accorda...

Страница 4: ...alled in locations classified as hazardous in accordance with the National Electric Code ANSI NFPA 70 IWARNING The Uniform Plumbing Code UPC states that sewage systems shall have an audio and visual a...

Страница 5: ...or re boxed and stored in a dry location If the pump is to be stored for a long period of time rotate the pump shaft periodically to protect the bearings Units should not be stored where temperatures...

Страница 6: ...lled in a trench ditch or hole with a dirt bottom The legs will into the dirt and the suction will become plugged adequate working space A minimum of 8 diametrical clearance around the tank is recomme...

Страница 7: ...unded DO NOT USE THE POWER CABLE TO LIFE PUMP Do not use an extension cord for 1 Phase pump s Always wire the pump as indicated on the wiring diagram inside the control panel 2 OVERLOAD PROTECTION On...

Страница 8: ...ches SW1 SW2 SW3 and 1 high water alarm switch SW4 mounted to the style 1 pilot device with a duplex control panel The level control and high water alarm float should have adequate clearance so they c...

Страница 9: ...he motor before the pump is put into service The resistance values voltage and current should be recorded 5 PUMP DOWN TEST Be sure pump has been properly wired lowered into the basin or lift station C...

Страница 10: ...e any 2 of 3 power supply leads on the motor end of the starter or VFD to ensure proper impeller rotation 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits and fluid...

Страница 11: ...e 5 COOLING OIL INSPECTION Anytime the pump removed from operation the cooling oil in the motor housing should be checked visually for oil level and contamination To check oil set unit upright remove...

Страница 12: ...d PRESSURE TEST AIR FILL MOTOR Remove pipe plug from housing Apply pipe sealant to pressure gauge assembly and tighten into hold Pressurize housing to 10 PSI Use soap solution around the sealed areas...

Страница 13: ...g with washers and grommet d Pull cord through and disconnect the wires from the terminals on power cord Be sure to note wire connections for reassembly e Disconnect cable leads from motor leads and r...

Страница 14: ...ate the impeller by hand and check for smooth rotation If rotation is not smooth check for alignments in the bearing and scratches on the seal faces 2 Upon completion of reassembly rotate the impeller...

Страница 15: ...15 NOTES...

Страница 16: ...l apply to the equipment supplied hereunder or referred to herein or to its performance all such other warranties including any warranty of merchantability or fitness for any purpose being hereby disc...

Отзывы: