Supv.
Alarm
Total Supv.
Total Alarm
Qty Model
Description
Current
Current
Current
Current
1
FC-72-1
1 Zone Control Panel
.063 A
.370 A(*)
.063 A
.370 A
BMFC-6
Basic Master Fire Card
(*)
(*)
——
——
ADAM-6-1 Aux. DC Actuation Module
.013 A
.073 A
ADAM-6-2 Aux. DC Actuation Module
.026 A
.133 A(#)
APS-6
Aux. Power Supply
.020 A
——
——
AVM
Alarm Verification Module
.012 A
.030 A
BCM-6
Notification Appl. Circuit Module
(**)
(**)
——
——
BMC-6
Master Coder Module
(**)
(**)
——
——
BCM-6
Notification Appl. Circuit Module
(**)
(**)
——
——
TCM-6
Temporal Pattern Module
(**)
(**)
——
——
PNIS
PNIS Zone Coder Module
.004 A/zone .150 A
PS-6
Power Supply
——
——
——
——
RB-6
Aux. Relay Module
——
.070 A (#)
——
RDF
Releasing Device Interface
.002 A
.047 A
RRT
Remote Reset Capability
(##)
(##)
RTI
Remote Trouble Indicator
.002 A
.002 A
RZA
Remote Zone Annunciator (LED)
——
.002 A
——
SRB-6
Supervised Aux. Relay Module
.019 A
.079 A (#)
TBZ
Trouble By Zone Module
.003 A
.021A/zone
TDS438
Time Delay Switch
——
.001
——
VZM
Verification Zone Module
.010 A
.175 A
WTM
Walk Test Module
——
.040 A
——
ZMC
Zone Mother Card
——
——
——
——
ZDM
Zone Detector Module
.006 A
.163 A
ZDM-D
Zone Det. Module, Dual Density
.018 A
.298 A (#)
CPD-7051 Smoke Det., Ionization
.00005 A
⊕
——
PSD-7155/
PSD-7156 Smoke Det., Photoelectric
.00005 A
⊕
——
SBS-1101
Smoke Det., Ionization
.00010 A
⊕
——
SBS-1201 Smoke Det., Photoelectronic
.00012 A
⊕
——
301 Series Smoke Det.
.00012 A
⊕
——
4WSD
4 Wire Smoke Det/EOL Relay
NOTES:
(*) FC-72-1 contains BMFC-6, PS-6, one ZDM and one BCM-6, BMC-6, TCM-6, or CCM-6.
(**) Included in BMFC-6 and/or ADAM-6. Power requirements are as above.
(#) With both circuits in alarm.
(##) Consult factory.
⊕
Alarm current is limited by zone module circuitry and is not involved in battery calculation.
Modules DMM, ABM and DBM do not consume current and are not involved in calculations.
Table 2 FC-72 System Battery Standby Calculation Chart
A
Total Supv. Current from above chart
B
Enter number of standby hours (24 hrs for NFPA Local, Proprietary,
Central Station, 60 hrs for NFPA Auxiliary, Remote Station,
90 hours for FM Deluge/Preaction)
C
Multiply Line A times hours in Line B—enter
D
Total alarm current from above chart
E
Enter alarm sounding period in hours. (5 minutes = .084 hr.)**
F
Multiply Line D times Line E —enter
G
Total of Lines C&F—enter
H
Multiply Line G by 1.2 — enter (Total ampere/hours required*)
* Use next size battery with capacity greater than required.
**5 minute alarm period for NFPA, 10 minute period for FM Deluge/Preaction Service
Battery Calculations
9000-0007
Page 21 of 28
firealarmresources.com