4.0 JUMPERS AND JUMPER MATRIX
The jumpers and jumper matrix for the BMFC are shown in Table 1.
5.0 MUNICIPAL BOX CONNECTION
BMFC Terminals 1 and 2 are for the supervised connection of a local energy city box or solenoid. The alarm
output on these terminals is 20 VDC for municipal box, and 24 VDC for solenoid. A “CITY BOX DISCONNECT”
Switch is provided for use when testing and servicing the control. When the switch is in the OFF position,
operation of the master box/solenoid is inhibited, the yellow LED above the switch will light, and a System
Trouble will occur.
When a solenoid is connected, the switch will inhibit the alarm dry contacts from transferring on alarm
if Jumper JRR DISC. is cut.
To connect the master box or solenoid, remove the 220 ohm, 5 watt resistor from Terminals 1 and 2. DO NOT
connect this resistor to the master box or transmitter. Leave it in the bottom of the control cabinet for trouble
shooting purposes. Connect master box or solenoid wiring to Terminals 1(+) and 2 ( - ). For solenoid, verify that
R24 is replaced by a fuse, 4 amps @ 24 VDC. For master box, verify that field wiring does not exceed 35 ohms.
For solenoid field wiring, refer to the table. Check with a meter before making final connections. To disable the
city box switch, consult the factory.
JUMPER
FUNCTION
J-11
Cut if TCM-6, BMC-6 or CCM-6 module is installed.
J-12
Cut when Reversing Relay is being used to transmit an alarm via telephone lines.
J-13
Cut if RTI (Remote Trouble Indicator)is NOT used.
J-10A,B
Install to the right of the last zone in system unless followed by an auxiliary module
(ADAM, SRB, etc.)
J-RA,B
Remove this jumper on each zone where an RZA (Remote Zone Annunciator) is
used or when a ZDM-D is used.
JRR
Cut if the City Box Switch is required to disable the Polarity Rev. Output in alarm.
J-RTI
Cut if RTI is used—jumper located next to Terminals 17-19.
JT
Cut to transmit a system trouble to Remote Station via telephone lines.
(Terms. 25 & 26).
JS3
Cut for supervision of Terminals 3 & 4.
JL
Cut if K2 Reversing relay is to be non-latching
J20
Cut for remote reset function.
J5
Factory use only
J22
Cut if Alarm Bus 6 is being used.
JS5
Cut for supervision of Terminals 4 & 5.
J31-34
Install when using a ZDM-D module.
DIODE JUMPER
FUNCTION
POSITION
ZONES
ZONES
1, 3, 5 etc.
2, 4, 6 etc.
JIA
JIB
Alarm activates master box output only.
J2A
J2B
Alarm activates bus 2.
J3A
J3B
Alarm activates notification appliance circuits, reversing relay and city box circuit.
J4A
J4B
Alarm activates aux. alarm output only. (Terminals 3 - 5)
J5A
J5B
Alarm activates Bus 5.
J6A
J6B
Alarm activates Bus 6.
NOTE: If Alarm Busses 2 or 5 are used:
Cut CR71 and CR72 on BMFC,
Cut CR5 and CR22 on ZMC
Table 1
NOTE: This output is is fused at 4 amps. Do not exceed 3 amps. The output voltage depends on which device is
connected to the circuit. A minimum battery voltage of 23.3 VDC is required to operate the solenoid circuit.
Page 8 of 28
9000-0007