23.0 CENTRAL STATION TRANSMITTER CONNECTIONS
The FC-72 control panel may be used in conjunction with the below listed units to meet the requirements
for Central Station protective Signaling Service per NFPA 72. Signals for fire and trouble are transmitted over
two (2) separate circuits
•
Potter Model ATE-B Alarm and Trouble Transmitter.
•
Versus Subscriber Terminal Units STU-2Z-UL, or STU-11Z-UL
•
Keltron DMP-703/704 Central Station Alarm receiving unit.
See Figures 18, 19 and 20 for connections to the various units.
CONNECT ATTE-B TERMS. 4, 6, 7 TOGETHER
NOTE: CONNECT BMFC TERMS.
30
29
21
16
20
15
16, 20, 29 TOGETHER
7
8
6
TRANSMITTER
5
4
3
ATTE-B
POTTER
Figure 18 Connection of Potter ATTE-B Transmitter
6
STU-2Z-UL, STU-4Z-UL
ALARM CIRCUIT
TROUBLE
CIRCUIT
S2
S1
STU-11Z-UL
3
2
1
4 5
OR
STU EOL
21024-0001
UNIT
STU EOL
UNIT
21024-0001
15
16
20
BMFC
21
J1
J2
Figure 19 Connection to Versus STU Units
(C)
(N/O)
RESISTOR
ALARM CIRCUIT
KELTRON
DMP703/704
TO
15
14
16
TROUBLE CIRCUIT
LISTED
TO
KELTRON
DMP703/704
11K
EOL
CONTACTS
CONTACTS
ALARM
MODULE
RESISTOR
11K
LISTED
TROUBLE
BMFC-6
EOL
Figure 20 Connection to Keltron DMP-703/704
Page 22 of 28
9000-0007
firealarmresources.com