Notification Appliance Circuit 2 - Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 10 ( - ) and 13
(+), and connect resistor to Terminals 11 and 12. Connect field wiring to terminals per Figure 3.
Class B, Style Y Wiring
Notification Appliance Circuit 1 - Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 6 ( - ) and 9 (+),
then connect it in parallel within the last device on the circuit. Connect field wiring to these terminals per
Figure 4. Be sure to observe polarity, and check all wiring prior to connection.
Notification Appliance Circuit 2 - Follow the same procedure as above, except Terminal 10 is negative ( - ),
and Terminal 13 is positive (+).
7.2 Troubleshooting the Notification Appliance Circuit
Yellow LED on TCM/BCM
1. Open in ckt. wiring.
Remove the wiring and check for opens.
is lit
2. PTC open.
Hold the System Reset switch down for five (5) seconds.
3. Relay coil defective
Check the coil for 700 ohms resistance.
Replace if necessary.
“SHORT CIRCUIT” LED lit.
1. Short circuit in
Check notification appliance circuits for shorts.
the field wiring
(See section on “SHORT CIRCUIT” LED)
2. Non-polarized
appliances used.
Use only approved appliances.
Notification appliances
1. Reversed polarity
will not operate
on appliance.
Correct polarity of notification appliances
2. PTC open.
Hold the System Reset switch down for five (5) seconds
3. Signal relay
NOTE: Divide the load evenly between both notification appliance circuits. Be sure to observe polarity, and
check all wiring prior to connection.
PROBLEM
CAUSE
ACTION TO BE TAKEN
9000-0007
Page 11 of 28