24.0 PROPRIETARY SUPERVISING STATION SYSTEM CONNECTIONS
The FC-72 control may be used in conjunction with Keltron Model DMP703 or DMP704 Proprietary alarm
receiving units to meet the requirements for Proprietary Alarm Service per NFPA 72. Signals are transmitted
for fire, trouble and supervisory functions over three (3) separate circuits.
See Figure 23 for connections for fire and trouble transmissions. Figure 21 contains wiring for waterflow
and supervisory transmission.
WATERFLOW ALARMS
Remove the associated Zone Module, ZDM, from the mother card and install a jumper across the two
waterflow jumper pins on the module. Reinstall the module into the mother card. This will prevent the silencing
of notification appliances during a waterflow alarm.
SPRINKLER SUPERVISORY
Remove the associated Zone Module ZDM, from the mother card and cut the 1N4004 diode labeled “latch”.
On the diode matrix at the right of the Sprinkler Supervisory ZDM module, move the program diode down one
position from the factory installed position. Reinstall the module into the mother card. This will cause an output
on BMFC Terminals 4 and 5. Connect a UL Listed notification appliance to these terminals and install the
appliance inside the control panel if audible, or outside if visual.
5
4
UL LISTED
NOTIFICATION
APPLIANCE
SPRINKLER SUPERVISORY
CIRCUIT
TO
KELTRON
DMP-703/704
ZONE TERMINALS
BMFC-6
MODULE
11K
EOL
RESISTOR
LISTED
35 34 33
SUPERVISORY ZDM
Figure 21 Sprinkler Supervisory Connection to DMP703/704
9000-0007
Page 23 of 28