-38-
3.
Adjust the Write Analogue Output 16bit (6411h) value to output the High End value. Record the digital
data when it reaches the High End output.
4.
Enter the digital data recorded at Low End output and High End output into the following objects.
-
Analogue Output Calibration Low Value (2302h): Enter the digital data recorded at Low End output.
-
Analogue Output Calibration High Value (2302h): Enter the digital data recorded at High End