-32-
9.2.1.2.
1~5 [V] Voltage Output
In the voltage output range, the digital data 0~25,000 is convereted to 1~5 [V] output. Actually, the digital data -
1,250~26,250 is converted to 0.8~5.2 [V].
If the digital data is greater than 26,250, it outputs 5.2 [V]. Or if the digital data is less than -1,250, it outputs 0.8
[V].
The following formula is used when converting digital data to analogue signals.
Analogue Output[V] =
4
25000
× Digital Data + 1
Figure 9-2. Data Conversion for Output Range 1 ~ 5 [V]
9.2.1.3.
0~10 [V] Voltage Output
In the voltage output range, the digital data 0~25,000 is converted to 0~10 [V] output. Actually, the digital data -
1,250~26,250 is converted to -0.5~10.5 [V].
If the digital data is greater than 26,250, it outputs 10.5 [V]. Or if the digital data is less than -1,250, it outputs -
0.5 [V].
The following formula is used when converting digital data to analogue signals.
Analogue Output[V] =
10
25000
× Digital Data
Figure 9-3. Data Conversion for Output Range 0 ~ 10 [V]
Digital Data
Voltage
5.2 V
25000
26250
0
-1250
0.8 V
5 V
1 V
Digital Data
Voltage
10.5 V
25000
26250
0
-1250
-0.5 V
10 V
Содержание Ezi-IO EtherCAT DA
Страница 1: ...User Manual ...
Страница 9: ... 9 Configuration Chapter 2 2 1 Ezi IO EtherCAT DA Part Numbering 2 2 Ezi IO EtherCAT DA Part Number ...
Страница 10: ... 10 2 3 System Configuration ...
Страница 13: ... 13 3 3 Module Dimensions Unit mm Can be installed on 35mm DIN Rail Can be installed on 35mm DIN Rail ...
Страница 14: ... 14 Connection Panel View Chapter 4 4 1 Names and Functions Ezi IO EC DA04 T ...
Страница 20: ... 20 5 2 Internal Circuit Diagram Figure 5 4 Internal Circuit Diagram ...