INSTALLATION, OPERATION

AND MAINTENANCE GUIDE

WATER CASSETTES

FIXING THE PANEL

After installation of the unit, mount the grille using the 4 screws provided

(fig. 12).

!

 

N.B.: It is very important to fix the grille in the right position

for  correct  connection  of  the  receiver  panel  to  the  unit.

Fig. 12

Use a spirit level  (fig. 10) to make sure that the unit is level and check

that it is securely fixed to the ceiling. In high humidity environments,

metal supports must be insulated using adhesive insulating material.

Fig. 11

To fix the unit to the ceiling, use the threaded bar and suitable screw

anchors as shown in fig. 09 (material not included in the supply).

C

B

D

A

Fig. 10

Fig. 07

        

 

 ATTENTION!

Catch up the cassette on the four

corners. Don't lift or move the unit

through the exchanger pipelines or

the  exhaust  pipe  condense.

!

-  to fix the panel only use the four supplied screws. Do not use other

kinds of screws or you could damage the condensate drain pan.

- Do not bend or narrow the unit piping.

- Do not remove the cap from the unit piping until immediately before

connecting the pipes.

- To prevent deformation of the air intake grille, do not overtighten the

screws.

CHANGE OF AIR AND RECIRCULATION SYSTEM

- Side knockouts allow connection of a duct for fresh air intake and for

conditioning an adjacent room.

- Remove the external prepunched anti-condensate insulator and

remove the knockout panels using a punch.

FRESH AIR RENEWAL

Remove  the  polystyrene  partition  and  insert  the  baffle  plate.

Use material purchased locally that is suitable for continuous operation

with temperatures of 60°C. The ducts may be in flexible polyester (with

steel spiral core) or in corrugated aluminium lagged with anti-condensate

material (fibreglass 12±25 mm thick). Upon completion of installation,

surfaces  that  have  not  been  insulated  may  be  covered  with  anti-

condensate insulating material (e.g.: 6 mm thick expanded neoprene).

Failure to comply with these instructions could cause dripping due

to the condensate; the manufacturer cannot be held responsible

for any damage. 

Any additional fan for external air intake (installer's

responsibility) must be connected to the terminal block as per the

enclosed  diagrams.  Fan  operation  is  in  parallel  to  the  damper

(electrothermal control valve), so that it stops when the valve closes.

Install an air inlet grille on the outside, with an inspectable filter holding

frame to prevent the entry of dust and leaves, which could irreparably

obstruct the unit heat exchanger coil.

RECEIVING, STORE AND MOVING THE UNITS

At the moment of the delivery of the unit, make sure that it corresponds

to the one indicated on the  transport document. Check the integrity of

the packing and the unit. Should there be any differences with the original

order or any damages, anomalies, or incomplete supply, please point

it out on the delivery note and inform the firm straight away. Never install

or use damaged apparatuses. The unit can be stored in room protected

from bad weather with temperature between the -20°C and the +55°C.

Transport the packed unit near as  possible to the installation place. To

avoid any damage to the unit, the plastic part (frontal panel and grille)

are furnished separately. The handling and the installation could be

facilitated cy use of an elevator(fig. 07).

INSTALLATION ACCESSORIES

n. 1 Cardboard mounting template;

n. 2 Batteries;

n. 1 Remote control;

n. 1 Auxiliary drain pan;

SELECTION OF CASSETTE INSTALLATION LOCATION

!

 

RECCOMENDATION!!

- The  unit  must  be  installed  in  a  solid  and  vibration-free  ceiling.

- There should be no obstruction of the air flow into and out of the unit

and the air should be evenly distributed throughout the whole room.

- Do not install the unit near sources of heat, steam or inflammable

gases.

- Install the unit near an electric socket or connect it directly to the

power supply.

- Do not install the unit in a place, which is exposed to direct sunlight.

- The selected place should allow easy drainage of the condensed

water.

- Periodically check appliance operation and leave sufficient space for

maintenance  around  the  appliance,  as  shown  in  the  figure  08.

- Install the unit so that the filter is easily accessible.

INSTALLATION

FIXING THE CASSETTE

Select a place of installation where there can be a clearance of a least

100 cm (see fig. 07) around the appliance. Make sure that the installation

does not interfere with existing electric wiring or plumbing. Establish the

position and size of the hole in the ceiling using the external diameter

of the cardboard mounting template (fig. 08).

>100

100 < H > 350

Fig. 08

Fig. 09

 Select the final position of the unit in the ceiling using the references

printed  on  the  cardboard  mounting  template  (fig.  09).

8

Содержание CSF21

Страница 1: ...INSTALLATION USE AND MAINTENANCE MANUAL 0706 6180666 rev 0 GB CSF Series WATER CASSETTES...

Страница 2: ...ATER CONNECTIONS 9 Standard water connection to heating cooling system 9 INSTALLATION OF AUXILIARY CONDENSATE DRAIN PAN 9 10 CONDENSATE DRAINAGE 10 ELECTRIC CONNECTIONS 10 Acces to the swhitchboard 10...

Страница 3: ...953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100 350x100 350x100 350x100 120x80 120x80 1...

Страница 4: ...nght of the panel Pp mm 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100...

Страница 5: ...90 kcal h 3 914 5 509 7 103 8 836 9 302 11 052 13 198 17 147 kPa 17 4 22 1 34 0 42 7 28 8 28 1 30 6 44 2 m c a 1 74 2 21 3 4 4 27 2 88 2 81 3 06 4 42 l h 391 550 709 882 928 1 103 1 317 1 711 l s 0 10...

Страница 6: ...4 360 5 310 6 880 8 480 10 110 12 340 kcal h 1 966 2 543 3 759 4 578 5 931 7 310 8 716 10 638 kPa 33 2 31 4 36 8 42 8 38 4 24 0 32 0 43 8 m c a 3 32 3 14 3 68 4 28 3 84 2 4 3 2 4 38 l h 196 254 375 4...

Страница 7: ...s with the low voltage EEC 73 23 and electromagnetic compatibly EEC 89 336 directives The installation should be carried out by a qualified installer Follow all current national safety code requiremen...

Страница 8: ...hermal control valve so that it stops when the valve closes Install an air inlet grille on the outside with an inspectable filter holding frame to prevent the entry of dust and leaves which could irre...

Страница 9: ...t valve is recommended to stop the flow of water in the event of pump failure Fig 13 A B C Fig 16 2 50 A few examples are shown schematically below of condensate drainage connection in a correct fig 2...

Страница 10: ...ower supply line should be fitted with at least a switch isolator in conformity with European standard EN60947 3 Make sure that the electrical system is suitable for providing not only the working cur...

Страница 11: ...ow green bianco yellow green white red blue black yellow green brown M1 1 white red blue black yellow green brown WIRING DIAGRAM OF 4 PIPE SYSTEM WATER CASSETTE WITH I R CSF 41 44 ST CSF 45 48 LT L N...

Страница 12: ...P POWER TIMER SLEEP COMP SW LV HR MIN START STOP SLEEP MODE FAN H TEMP COOL SLEEP SLEEP CLOCK START STOP LS1 NO NC red red blue black black M1 1 white yellow green white red blue black brown white red...

Страница 13: ...Do not allow the air conditioner to come into contact with water The electrical insulation could be damaged with consequent possible risk of electrocution Check installation conditions in order to id...

Страница 14: ...use the TEMP buttons and to set a temperature which is lower than the room temperature For example if there is a temperature of 28 C in the room a temperature lower than 27 C should be set in order f...

Страница 15: ...r on the display as shown in the drawing to the side The SLEEP mode automatically adjusts the temperature to make the sleeping environment more comfortable during the night During the cooling or dehum...

Страница 16: ...and water temperature sensor are damaged or not connected 5 TIMER indicator light blinks intermittently fig 44 B the filters must be cleaned When the cassette has been operating for more than 500 hou...

Страница 17: ...optional Press the SW button to start stop louver swing Louver direction adjustment optional Press the LV button to change the angle of the louvers which are controlled by the louver motor if the butt...

Страница 18: ...move the plug or turn off the automatic circuit breaker TROUBLESHOOTTING 1 If the appliance does not switch on check that the mains supply is reaching the unit that the plug is properly inserted if th...

Страница 19: ...INSTALLATION OPERATION AND MAINTENANCE GUIDE WATER CASSETTES 19...

Страница 20: ...the right to make all the modifications considered necessary for improving the product at any time FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 806311...

Отзывы: