INSTALLATION, OPERATION
AND MAINTENANCE GUIDE
WATER CASSETTES
Above mentioned technical data are calculate at the following operating conditions:
- Maximum fan speed
- Standard unit without ducts
(A) Cooling: inlet water temperature: 7 °C; Outlet water temperature: 12 °C; Inlet air temperature: 27 °C w.b. 19 °C d.b.
(B) Heating: inlet water temperature: 70 °C; Outlet water temperature: 60 °C; Inlet air temperature: 20 °C
(C) Heating: inlet water temperature: 50 °C; Same water flow as in cooling; Inlet air temperature: 20 °C
(D) Air flow and fan speed: fancoil performances with cleaned filter
(E) Sound power level: Sound power measured following ISO 23741
(F) Electrical data referred to the maximum available speed
GENERAL TECHNICAL DATA: 2 PIPE SYSTEM
W
1.980
2.870
3.260
4.490
5.730
6.760
8.080
10.540
Frig/h
1.707
2.474
2.810
3.871
4.940
5.828
6.966
9.086
W
1.505
2.009
2.347
3.233
4.182
4.934
5.979
7.588
Frig/h
1.297
1.732
2.023
2.787
3.605
4.254
5.154
6.541
kPa
20,6
26,1
40,2
50,4
35,1
34,3
37,3
53,9
m.c.a.
2,06
2,61
4,02
5,04
3,51
3,43
3,73
5,39
W
2.720
3.830
4.940
6.150
6.550
7.790
9.310
12.010
kcal/h
2.345
3.302
4.259
5.302
5.647
6.716
8.026
10.353
kPa
16,9
21,4
32,9
41,3
29,7
29,1
31,6
45,7
m.c.a.
1,69
2,14
3,29
4,13
2,97
2,91
3,16
4,57
l/h
341
494
561
773
986
1.163
1.390
1.814
l/s
0,095
0,137
0,156
0,215
0,274
0,323
0,386
0,504
W
4.540
6.390
8.240
10.250
10.790
12.820
15.310
19.890
kcal/h
3.914
5.509
7.103
8.836
9.302
11.052
13.198
17.147
kPa
17,4
22,1
34,0
42,7
28,8
28,1
30,6
44,2
m.c.a.
1,74
2,21
3,4
4,27
2,88
2,81
3,06
4,42
l/h
391
550
709
882
928
1.103
1.317
1.711
l/s
0,108
0,153
0,197
0,245
0,258
0,306
0,366
0,475
m3/h
543
611
680
815
832
1087
1087
1274
m3/s
0,151
0,170
0,189
0,226
0,231
0,302
0,302
0,354
g/min.
700
785
830
1100
540
610
610
630
dB(A)
51
53
57
62
54
58
58
62
W
58
126
126
124
58
126
126
124
A
0,41
0,57
0,57
0,66
0,41
0,57
0,57
0,66
Total cooling capacity
Sensible cooling capacity
Heating capacity
Water flow
Water pressure drops in heating
Air flow
Speed of the fan
Sound power level
Motor electrical power
Electrical supply: 230V / 1 / 50Hz
A
Heating capacity
C
Water flow
A-C
Water pressure drops in cooling
A
Water pressure drops in heating
C
B
D
E
F
1
0,55
0,58
0,49
0,56
0,80
0,79
0,78
0,80
2
0,73
0,75
0,68
0,67
0,87
0,88
0,87
0,86
3
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1
0,57
0,58
0,51
0,56
0,82
0,79
0,80
0,80
2
0,75
0,75
0,70
0,67
0,89
0,88
0,89
0,86
3
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1
0,57
0,59
0,51
0,57
0,82
0,80
0,80
0,81
2
0,75
0,76
0,70
0,68
0,89
0,89
0,89
0,87
3
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1
0,47
0,46
0,44
0,43
0,75
0,71
0,73
0,73
2
0,64
0,65
0,65
0,65
0,84
0,84
0,86
0,84
3
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
CORRECTION COEFFICIENT FOR THE DIFFERENT SPEED
Total cooling capacity
Sensible cooling capacity
Heating capacity
Air flow
Motor electrical input
MODEL
CSF21
CSF22 CSF23
CSF24
CSF25 CSF26
CSF27 CSF28
MODEL
CSF21
CSF22 CSF23
CSF24
CSF25 CSF26
CSF27 CSF28
5