INSTALLATION, OPERATION
AND MAINTENANCE GUIDE
WATER CASSETTES
WORKING LIMITS
Maximum inlet water temperature
70 °C
Minimum inlet water temperature
+ 4 °C
Maximal working pressure
8 bar
Maximal inlet air temperature
32 °C
Minimal inlet air temperature
+ 4 °C
ATTENTION!
Air stratification increases with the raise of inlet water temperature!
GENERAL FEATURES AND MAIN COMPONENTS
1 Airflow direction louvers
2 Air intake grille with filter
3 Airflow direction louvers
4 Indicator lights
5 Power
6 Sleep mode
7 Timer mode
8 Infrared remote control receiver
9
EMERGENCY
switch (used to switch on the air conditioner manually,
without using the remote control, following the order given below).
OFF
COOL
HEAT
Fig. 6
Fig. 5
ON
OFF
CSF 21-24
41-44
POWER SLEEP
TIMER EMERGENCY
OFF
COOL
HEAT
CSF 25-25
45-48
MOTOR FAN GROUP
Single-inlet centrifugal fan with statically and dynamically balanced plastic
impeller. The 3-speed electric motor, made to international standards,
has an overload cut-out and the run capacitor always connected. The
motor is directly coupled to the fan and cushioned with flexible mountings.
It is particularly efficient
and low noise.
DÉCOR PANEL
The décor panel has an innovative design so that the appliance may
be used in both dwellings and business premises. The white (RAL 9003)
panel is made in lightweight but strong plastic. Fixing to the load-bearing
structure is quick and easy. 4 adjustable louvers ensure best air
distribution throughout the room. Central intake grille with filter for
cleaning the air. The grille may be removed to access internal parts
without having to remove the panel from the ceiling.
ELIMINATION OF CONDENSATION
Condensate collecting system comprising:
- internal plastic tray for collecting condensation coming from the heat
exchanger;
- external auxiliary plastic tray for collecting condensation coming from
the valves and connecting pipes.
Electric pump, which is an integral part of the appliance and connected
to the external fitting.
WALL REMOTE CONTROL (accessory)
Wall remote control with 10 m wire
RECCOMENDATIONS FOR THE INSTALLER
Upon receiving the unit check for any damage, which should be reported
immediately. For the water cassette to operate correctly, it should be
installed according to the instructions given in this manual. Removal of
a water cassette after it has been installed is an operation that requires
special training: if this is necessary, please consult your dealer. After
installation, explain the correct operating procedure to the customer
using the booklet as a reference. Leave this manual with the customer
since it is part of the kit supplied with the appliance.
Take care not to scratch the units when handling them.
UNIT INSTALLATION
- Read this instruction manual thoroughly before starting installation.
- This unit complies with the low-voltage (EEC/73/23) and electromagnetic
compatibly (EEC/89/336) directives.
- The installation should be carried out by a qualified installer.
- Follow all current national safety code requirements. In particular
ensure that a properly sized and connected ground wire is in place.
- Check that the voltage and frequency of the mains power supply are
as required for the unit to be installed; the available power source
must be adequate to operate all other appliances connected to the
same line.
- Ensure that national safety code requirements have been followed
the main supply circuit.
- Where necessary, use field-supplied 25 mm I.D. PVC pipe of appropriate
length and with the correct thermal insulation for the condensate drain
extension.
- After installation thoroughly test system operation and explain all
system functions to the owner.
- Use this only for factory approved applications: the unit cannot be
used in laundry or stream pressing premises.
!
WARNING!
- Disconnect the mains power supply switch before servicing the system
or handling any internal parts of the unit.
- The manufacturer declines any liability for damage resulting from
modifications or errors in the electrical or water connections.
- Failure to observe the installation instructions, or use the unit under
conditions other than those indicated in table Operating limits of this
manual, will immediately invalidate the unit warranty.
- Failure to observe electric safety codes may cause a fire hazard in
the event of short circuits.
- Do not install or use damaged units.
- In case of malfunction turn the unit off, disconnect the mains power
supply and contact a qualified service engineer.
- Maintenance must only be carried out by qualified personnel.
- All of the manufacturing and packaging materials used for this appliance
are biodegradable and recyclable.
- Dispose of the packaging material in accordance with local
requirements.
STRUCTURE
Made in heavy-gauge galvanised sheet, the structure comes complete
with external brackets on the 4 corners for easy fixing to the ceiling.
Thermal-acoustic insulation: lining (polystyrene), external cladding (closed
cell). Set-up for distribution of air to adjacent rooms through knock-out
holes, either circular Ø 150 mm or rectangular 350x100 mm (CSF 21-
24 and 41-44), and rectangular 120 x 80 mm (CSF 25-28 and 45-48),
located on two sides of the appliance. Set-up for external air intake
through Ø 65 mm circular knock-out hole (CSF 21-24 and 41-44).
Rectangular 120x80 mm knock-out (CSF 25-28 and 45-48). Located on
a squared off corner of the appliance.
HEAT EXCHANGER
Coil in copper piping expanded into aluminium fins in continuous block.
The headers have easily accessible female gas fittings and air
vent/drainage valve located on the squared off corner of the appliance.
AIR FILTER
The filter comprises a plastic frame holding the filtering membrane.
Inserted in the inner part of the front panel, it may be easily removed
and cleaned using a vacuum cleaner followed by washing with water.
ON
OFF