background image

INSTALLATION, OPERATION

AND MAINTENANCE GUIDE

WATER CASSETTES

THE INFRARED REMOTE CONTROLLER

Turns the cassette 

ON

 or 

OFF

.

Selects operating mode following the order given below:

FAN

 (fan), 

COOL

 (cooling), 

DRY

 (dehumidying), 

HEAT

 (heating),

AUTO

 (automatic operation)

3

  Sets the required temperature between 18°C and 30°C. The

temperature is increased or decreased by pressing   and 

respectively.

4

  Selects the fan speed, following the order given below: 

AUTO

(automatic), 

HIGH

 (high), 

MED

 (medium), 

LOW

 (low)

5

Activates the 

SLEEP

 function. This function automatically adjusts

the temperature in order to provide maximum comfort during the

nighttime hours and save energy.

6

  Selects the current time on the remote control display.

7

  Increases the hours on the display

8

  Increases the minutes on the display

9

  Sets timed switching on

10

  Sets timed switching off

11

  Confirms the settings to the appliance.

12

  Activates or deactivates louver movement.

13

  Adjusts the louvers in order to direct the airflow in the best direction

!

 

The unit gives a beep to confirm that it has received each button

command correctly.

Battery replacement

When

:

- no beep of confirmation is received from the unit;

- the liquid crystal display is not working.

How

:

- Pull the cover downwards as shown in the drawing to the side (2 Type

AAA 1.5V batteries).

-  Insert  new  batteries  paying  attention  to  the  +  and  -  symbols.

N.B.: 

Only use new batteries

. Remove the batteries from the remote

control when the water cassette is not used.

Fig. 30

13

12

5

10

4

3

8

7

1

6

11

2

9

_

+

_

+

1,5 V
1,5 V

Fig. 31

Fig. 32

Fig. 33

Fig. 34

Fig. 35

COOLING  

When the 

MODE

 button is pressed and 

COOL

 is selected,

the cassette cools the room and at the same time reduces the humidity

in the air. To start the cooling cycle, use the 

TEMP

 buttons

   

and   to

set a temperature which is lower than the room temperature. For example:

if there is a temperature of 28°C in the room, a temperature lower than

27°C should be set in order for the compressor and cooling to start. The

appliance automatically adjusts operating cycles in order to keep the

room at the required temperature. Upon completion of settings, press

the 

SEND

 button and listen for the beep to make sure that the appliance

has received the command.

I.R. REMOTE CONTROL OPERATIONS

FAN 

When the 

MODE

 button is pressed and the 

FAN

 mode is selected,

the cassette will operate as an electrical fan only

DEHUMIDIFYING 

When the 

MODE

 button is pressed and the 

DRY

mode selected, the cassette alternates cooling and fan cycles. This

mode is used to dehumidify the air without excessively altering the room

temperature.

Operation is fully automatic: the appliance itself controls the fan speed.

HEATING 

When the 

MODE

 button is pressed and the 

HEAT

 mode is

selected, the cassette will heat the room. To start the heating cycle, use

the 

TEMP

 buttons   and   to set a temperature which is higher than

the room temperature. For example: if there is a temperature of 18°C

in the room, a temperature higher than 19°C should be set in order for

the compressor and heating to start. Upon completion of settings, press

the 

SEND

 button and listen for the beep to make sure that the appliance

has received the command.

AUTOMATIC OPERATION 

Access this mode by pressing the 

MODE

button. In the 

AUTO

 mode the electronic control automatically selects

the operating mode according to the room temperature (measured by

the built-in sensor):

- if the room temperature drops below 18°C, the appliance will start the

heating cycle. This will continue until the temperature rises to above

20°C;

- if the room temperature is above 26°C the appliance will start the

cooling cycle. This will continue until the temperature drops below 24°C.

14

All manuals and user guides at all-guides.com

Содержание CSF Series

Страница 1: ...INSTALLATION USE AND MAINTENANCE MANUAL 0706 6180666 rev 0 GB CSF Series WATER CASSETTES All manuals and user guides at all guides com a l l g u i d e s c o m ...

Страница 2: ...ndard water connection to heating cooling system 9 INSTALLATION OF AUXILIARY CONDENSATE DRAIN PAN 9 10 CONDENSATE DRAINAGE 10 ELECTRIC CONNECTIONS 10 Acces to the swhitchboard 10 Wiring diagram of 2 pipe system I R remote control 11 Wiring diagram of 4 pipe system I R remote control 11 Wiring diagram of 2 pipe system wall mounted control CD2 X7 12 Wiring diagram of 4 pipe system wall mounted contr...

Страница 3: ...of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room Ø A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80 Fresh air intake Ø D mm 65 65 65 65 Fresh air intake BxH E mm 120x80 120x80 120x80 120x80 B mm 225 225 225 225 180 325 325 325 X mm 65 5 65 5 65 5 65 5 70 73 73 73 Y mm 55 5 55 5 55 55 5 75 68 68 68 W mm 100 1...

Страница 4: ...m 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air supply in adjacent room Ø A mm 150 150 150 150 Air supply in adjacent room BxH C mm 350x100 350x100 350x100 350x100 120x80 120x80 120x80 120x80 Fresh air intake Ø D mm 65 65 65 65 Fresh air intake BxH E mm 120x80 120x80 120x80 120x80 B mm 225 225 225 225 180 325 325 325 X mm 65 5 65 5 65 5 65 5 86 73 73 73 Y mm...

Страница 5: ...7 103 8 836 9 302 11 052 13 198 17 147 kPa 17 4 22 1 34 0 42 7 28 8 28 1 30 6 44 2 m c a 1 74 2 21 3 4 4 27 2 88 2 81 3 06 4 42 l h 391 550 709 882 928 1 103 1 317 1 711 l s 0 108 0 153 0 197 0 245 0 258 0 306 0 366 0 475 m3 h 543 611 680 815 832 1087 1087 1274 m3 s 0 151 0 170 0 189 0 226 0 231 0 302 0 302 0 354 g min 700 785 830 1100 540 610 610 630 dB A 51 53 57 62 54 58 58 62 W 58 126 126 124 ...

Страница 6: ... 340 kcal h 1 966 2 543 3 759 4 578 5 931 7 310 8 716 10 638 kPa 33 2 31 4 36 8 42 8 38 4 24 0 32 0 43 8 m c a 3 32 3 14 3 68 4 28 3 84 2 4 3 2 4 38 l h 196 254 375 457 592 730 870 1 062 l s 0 054 0 071 0 104 0 127 0 164 0 203 0 242 0 295 m3 h 543 611 680 815 832 1087 1087 1274 m3 s 0 151 0 170 0 189 0 226 0 231 0 302 0 302 0 354 g min 700 785 830 1100 540 610 610 630 dB A 51 53 57 62 54 58 58 62 ...

Страница 7: ...EC 73 23 and electromagnetic compatibly EEC 89 336 directives The installation should be carried out by a qualified installer Follow all current national safety code requirements In particular ensure that a properly sized and connected ground wire is in place Check that the voltage and frequency of the mains power supply are as required for the unit to be installed the available power source must ...

Страница 8: ...o that it stops when the valve closes Install an air inlet grille on the outside with an inspectable filter holding frame to prevent the entry of dust and leaves which could irreparably obstruct the unit heat exchanger coil RECEIVING STORE AND MOVING THE UNITS At the moment of the delivery of the unit make sure that it corresponds to the one indicated on the transport document Check the integrity ...

Страница 9: ...o stop the flow of water in the event of pump failure Fig 13 A B C Fig 16 2 50 A few examples are shown schematically below of condensate drainage connection in a correct fig 20 21 and incorrect manner fig 22 23 Fig 19 200 mm Fig 17 Fig 20 CORRECT E D F Fig 15 3 way motor operated valve Water inlet Tap Tap Water outlet AIR SUPPLY TO AN ADJACENT ROOM Remove the polystyrene taking care not to damage...

Страница 10: ...d be fitted with at least a switch isolator in conformity with European standard EN60947 3 Make sure that the electrical system is suitable for providing not only the working current required by the appliance but also the necessary current for powering household and other electrical appliances already in use Any electrical and mechanical alterations or tampering render the warranty null and void T...

Страница 11: ... red blue black yellow green brown M1 1 white red blue black yellow green brown WIRING DIAGRAM OF 4 PIPE SYSTEM WATER CASSETTE WITH I R CSF 41 44 ST CSF 45 48 LT L N brown red red red red red red blue yellow black red black black yellow black red Electricalsupply 230Vac 50 Hz L N C1 Cool valve 230Vac 50 Hz Earth relay 9 relay 4 relay 6 relay 2 relay 1 relay 3 P23 P18 P19 P20 P26 P27 P25 P24 P13 P1...

Страница 12: ...MP SW LV HR MIN START STOP SLEEP MODE FAN H TEMP COOL SLEEP SLEEP CLOCK START STOP LS1 NO NC red red blue black black M1 1 white yellow green white red blue black brown white red blue black yellow green brown red red blue black black M1 1 white yellow green bianco red blue black brown white red blue black yellow green brown nero LEGENDA Connector Earth L Phase N Neutral Com Common M1 Fan motor 230...

Страница 13: ...conditioner to come into contact with water The electrical insulation could be damaged with consequent possible risk of electrocution Check installation conditions in order to identify possible damage After prolonged use apply to specialised service personnel to control the installation conditions of the air conditioner Do not use flammable gas near the air conditioner Always use the appliance wit...

Страница 14: ...and to set a temperature which is lower than the room temperature For example if there is a temperature of 28 C in the room a temperature lower than 27 C should be set in order for the compressor and cooling to start The appliance automatically adjusts operating cycles in order to keep the room at the required temperature Upon completion of settings press the SEND button and listen for the beep to...

Страница 15: ...own in the drawing to the side The SLEEP mode automatically adjusts the temperature to make the sleeping environment more comfortable during the night During the cooling or dehumidifying modes the set temperature is increased gradually by 2 C during the first two hours of operation During the heating mode the set temperature is decreased gradually by 2 C during the first 2 hours of operation Timed...

Страница 16: ...amaged or not connected 5 TIMER indicator light blinks intermittently fig 44 B the filters must be cleaned When the cassette has been operating for more than 500 hours a warning is displayed as a reminder to clean the filter N B Reset by cutting off the power for at least 10 seconds CONDENSATE DRAIN PUMP OPERATION SPECIFICATIONS Cool Unit in operation the pump operates continuously until the set t...

Страница 17: ...button to start stop louver swing Louver direction adjustment optional Press the LV button to change the angle of the louvers which are controlled by the louver motor if the button is pressed and released the angle of the louvers is changed very slightly if the button is pressed and held the angle of the louvers continues to change until the button is released SLEEP Press the SLEEP button to start...

Страница 18: ...off the automatic circuit breaker TROUBLESHOOTTING 1 If the appliance does not switch on check that the mains supply is reaching the unit that the plug is properly inserted if the circuit breaker has tripped if there been a failure in the mains supply 2 If the cooling or heating effect seems less than normal check that the temperature has been set correctly if a window or door has been opened the ...

Страница 19: ...INSTALLATION OPERATION AND MAINTENANCE GUIDE WATER CASSETTES 19 All manuals and user guides at all guides com ...

Страница 20: ... the modifications considered necessary for improving the product at any time FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 806311 Fax 0429 806340 E mail info fastaer com http www fastaer com 0706 6180666 rev 0 All manuals and user guides at all guides com ...

Отзывы: